Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> Additional copies of this page may be attached. <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ® Manufacturer ® Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: F.F.S. Incon TS-STS Sump Tester w/ + or— 0.002" graduations <br /> Sump/UDC ID UDC 3-4 <br /> Sump Manufacturer Poly <br /> Sump Depth (inches) <br /> 34" <br /> Sump Bottom to Top of 12" <br /> Highest Pipe Penetration <br /> inches <br /> Test Start Time 11:06am <br /> Initial Reading 4.7240" <br /> Test End Time 11:21am <br /> Final Reading 4.7248" <br /> Change in Reading -0.0008" <br /> Pass/Fail Criteria + or—0.002" + or—0.002" + or—0.002" + or—0.002" <br /> Tightness Test Results ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> inches <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria + or— 0.002" + or— 0.002" + or—0.002" + or— 0.002" <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />