ELECTRICAL SPECIFICATIONS LEGEND <br /> A. GENERAL REQUIREMENTS: G. EXTERIOR LIGHTING CONTROL SYSTEM: (2) FOR OVERHEAD HOMERUNS: VERTICAL DROPS FROM JBOX IN <br /> CEILING THEN HORIZONTAL RUNS WITHIN WALLS TO OTHER 15. TELEPHONE AND SIGNAL CONDUIT BENDS WHERE REQUIRED SHALL HAVE A <br /> 1. ELECTRICAL INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS OF THE 1. PROVIDE A COMPLETE AND FULLY OPERATIONAL EXTERIOR LIGHTING CONTROL RECEPTACLES. HORIZONTAL RUNS IN CEILING SHALL BE IN RADIUS OF TEN TIMES THE CONDUIT TRADE SIZE. 0 FLUORESCENT LIGHT FIXTURE, RECESSED MOUNT CAP. LETTER=TYPE E) <br /> CALIFORNIA CODE OF REGULATIONS, TITLE 24, INCLUDING THE FOLLOWING: SYSTEM FOR EXTERIOR LIGHTING AS SPECIFIED HEREIN AND SHOWN ON THE DRAWINGS. SOLID STEEL CONDUITS. 0FLUORESCENT LIGHT FIXTURE, SURFACE MOUNT SM. LETTER=SWITCHING APEX <br /> THE 2016 CALIFORNIA BUILDING CODE (CBC) (d) NO OTHER USE IS PERMITTED WITHOUT SPECIFIC WRITTEN APPROVAL 16. PROVIDE PULL TAPE IN ALL EMPTY CONDUITS. <br /> THE 2016 CALIFORNIA ELECTRICAL CODE (CEC) 2. THE COMPLETE SYSTEM, INCLUDING ALL DEVICES SHALL BE IN COMPLIANCE WITH OF THE ARCHITECT OR OWNER. O CEILING LIGHT FIXTURE NUMBER=CIRCUIT ARCHITECTURE <br /> THE 2016 CALIFORNIA MECHANICAL CODE (CMC) THE 2013 CALIFORNIA ENERGY CODE. (4) ALL FITTINGS AND TERMINATIONS FOR THE MC CABLING SYSTEM SHALL 0. INSTALLATION OF SUPPORT SYSTEMS: RECESSED LIGHT FIXTURE <br /> THE 2016 CALIFORNIA PLUMBING CODE (CPC) BE METAL AND SUITABLE AND LISTED FOR SUCH USE. <br /> THE 2016 CALIFORNIA GREEN BUILDING STANDARDS CODE. 3. EXTERIOR LUMINAIRES SHALL BE PROVIDED WITH LED LAMP MODULES, DRIVERS ALL SUPPORTS, ATTACHMENTS SPACING SHALL BE PER CEC 330.30. 1. ALL CONDUITS AND FIXTURES SHALL BE SUPPORTED IN A FIRM AND SECURE Q WALL BRACKET LIGHT FIXTURE <br /> THE 2016 CALIFORNIA ENERGY CODE AND, WHERE SO SPECIFIED, INTEGRAL DIMMING TYPE MOTION SENSOR AND PHOTOCELL. �5� <br /> 6FOR MULTI-WIRE BRANCH CIRCUITS SUCH CABLES SHALL HAVE MULTIPLE MANNER AS REQUIRED BY CODE. MATERIALS SHALL BE SECURED TO THE 845 S. Commerce Street <br /> ALL APPLICABLE LOCAL CODES. NEUTRALS, ONE FOR EACH CIRCUIT. STRUCTURE BY MEANS OF SUITABLE CLAMPS AND HANGERS SPECIFICALLY ® LIGHT FIXTURE ON EMERGENCY POWER CIRCUIT WITH INTEGRAL EMERGENCY BATTERY PACK <br /> 4. FOR LIGHTS WHICH ARE CONTROLLED BY MOTION SENSORS, INTEGRAL OR EXTERNAL, DESIGNED FOR THE PURPOSE AND USING MACHINE SCREWS OR BOLTS ON ® LIGHT FIXTURE ON EMERGENCY POWER CIRCUIT WITH INTEGRAL EMERGENCY BATTERY PACK Stockton, CA. 95206 <br /> 2. THE CONTRACTOR IS REMINDED THIS PROJECT IS A COMPLETE REMODEL OF <br /> THEY SHALL COME ON FULL OUTPUT UPON ADVENT OF DUSK AND REDUCE TO 50% AFTER 6. LINE VOLTAGE CONDUCTORS SHALL BE COPPER CONDUCTORS TYPE THHN/THWN METAL OR WOOD SCREWS ON WOOD CONSTRUCTION. (209) 662-4874 <br /> AN EXISTING FULLY IMPROVED TENANT SPACE. EXISTING ELECTRICAL DISTRIBUTION A TIME DAY DURING WHICH NO MOTION IS DETECTED. UPON DETECTION OF MOTION LIGHTS UNLESS OTHERWISE NOTED OR REQUIRED BY CODE. 2. RIGID STEEL CONDUIT SHALL BE SUPPORTED AT INTERVALS NOT GREATER THAN ® RECESSED LIGHT FIXTURE POWER CIRCUIT WITH INTEGRAL EMERGENCY BATTERY PACK a ex tannin hotmail.com <br /> HAS NOT BEEN ENTIRELY VERIFIED AND THESE DRAWINGS MUST BE ACCEPTED WITH SHALL COME UP TO FULL OUTPUT. 10 FT, ELECTRICAL METALLIC TUBING AT INTERVALS NOT GREATER THAN 5 FT. EXIT LIGHT-HIGH LEVEL P P 9@ <br /> THIS UNDERSTANDING. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AT 7. ALL DEVICES, CONDUITS, RACEWAYS AND CABLES SHOWN ARE NEW TO BE <br /> THE SITE PRIOR TO BID. HE SHALL FURTHER FURNISH LABOR AND MATERIALSH. CONTROLLED 120V RECEPTACLES: <br /> PROVIDED UNLESS OTHERWISE NOTED. 3. A SUPPORT SHALL BE PROVIDED NOT MORE THAN 3 FT. FROM ANY CHANGE IN ALTERNATE DESIGNATION OF LIGHT FIXTURE SHOWING TYPE & LAMPS <br /> TO ACHIEVE INDICATED RESULTS EVEN THOUGH ALL DETAILS ARE NOT SHOWN. DIRECTION. ADDITIONAL SUPPORTS TO THOSE SPECIFIED ABOVE SHALL BE <br /> 1. CALIFORNIA ENERGY CODE SECTION 130.5(d) NOW REQUIRES THAT BOTH 8. FLASH AND COUNTERFLASH ALL ITEMS PASSING THROUGH THE ROOF. INSTALLED WHERE REQUIRED TO SUIT JOB CONDITIONS AND TO PROVIDE A $ LIGHT SWITCH - SPST UP 48" U.O.N. FLU H Steven Anthony Torres II <br /> 3. THE ELECTRICAL CONTRACTOR SHALL VERIFY ELECTRICAL SERVICE MODIFICATIONS CONTROLLED AND UNCONTROLLED 120V OUTLETS FOR PLUG LOADS BE PROVIDED SECURE INSTALLATION. ALL HANGERS AND SUPPORTS SHALL BE THE $3 LIGHT SWITCH - 3-WAY Architect # C32553 <br /> AT SITE PRIOR TO BIDDING. SERVICES TO CONFORM TO UTILITY COMPANY REQUIREMENTS. IN THE FOLLOWING LOCATIONS: 9. THE OWNER RESERVES THE RIGHT TO RELOCATE ALL LIGHTING, OUTLETS AND PRODUCTS OF ONE MANUFACTURER. <br /> ELECTRICAL CONTRACTOR SHALL CONTACT AND ARRANGE FOR SERVICE REMOVALS/ A. EACH PRIVATE OFFICE. SWITCHES BEFORE THEY ARE ROUGHED IN AT NO EXTRA COST. DIMMER SWITCH <br /> MODIFICATIONS/INSTALLATION PER UTILITY COMPANY REQUIREMENTS AND PAY ALL B. EACH OPEN OFFICE AREA. Q. WIRING METHODS: LOW VOLTAGE SYSTEMS: [$] OCCUPANCY SENSOR LIGHT SWITCH <br /> CUSTOMER CHARGED SERVICE COST. COORDINATE WITH OWNER AND UTILITY COMPANY 10. SEPARATION OF WIRING OF DIFFERENT VOLTAGE CLASSIFICATIONS: <br /> FOR SERVICE REMOVALS AND INSTALLATION SO AS TO MINIMIZE POWER OUTAGES. C. RECEPTION LOBBY. 1. ALL WIRING FOR LOW VOLTAGE SYSTEMS IS BY OWNER'S VENDORS. C OCCUPANCY SENSOR LIGHT SWITCH W/MANNUAL SWITCH <br /> PG&E CONTACT PERSON IS CHRIS WALPOLE, TELEPHONE NO. (209) 533-6036. D. CONFERENCE ROOM. A. WIRING FOR DIFFERENT VOLTAGE CLASSIFICATIONS SHALL BE dbv 120 VOLT DUPLEX WALL OUTLET FOR VIEWBOX <br /> E. KITCHENETTE AND BREAK ROOM IN OFFICE SPACES. INSTALLED IN ENTIRELY SEPARATE RACEWAYS/CONDUITS SYSTEM AND 2. THE ELECTRICAL CONTRACTOR SHALL PROVIDE POWER, LINE VOLTAGE WIRING <br /> 4. ELECTRICAL CONTRACTOR SHALL PROCURE AND PAY FOR ALL LICENSES, ENCLOSURES/BOXES. AND RACEWAYS/JUNCTION BOXES ONLY FOR SUCH SYSTEMS. db 120 VOLT DUPLEX WALL OUTLET UP 18" U.O.T <br /> PERMITS, ETC. REQUIRED TO CARRY ON AND COMPLETE THE WORK. F. COPY ROOM. CLASSIFICATION 1 - 0 TO 30V <br /> 5. PROVIDE ALL LABOR, MATERIALS, TOOLS, CLASSIFICATION 2 - 100 TO 250V 3. COORDINATE WITH OWNER'S VENDORS FOR ALL SUCH REQUIREMENTS. 120 VOLT FOURPLEX OUTLET <br /> "PLANT EQUIPMENT, TRANSPORTATION 2. CIRCUITS SERVING CONTROLLED RECEPTACLES SHALL BE AUTOMATICALLY BE CLASSIFICATION 3 - 251 TO 500V � 120V DUPLEX OUTLET MOUNTED AT +42" A.F.F. OR +4" ABOVE <br /> AND PERFORM ALL OPERATIONS NECESSARY FOR ANY REASONABLE INCIDENTAL TO SHUT-OFF IN ACCORDANCE WITH SECTION 130.1(c)1. R. WIRING: <br /> PROPER EXECUTION AND COMPLETION OF ALL ELECTRICAL WORK WHETHER B. PARTICULAR ATTENTION SHALL BE PAID TO THE WIRING FOR COUNTERTOP AS APPLICABLE <br /> SPECIFICALLY MENTIONED OR NOT; ALL AS INDICATED, SPECIFIED HEREIN, AND/OR 3. PROVIDE A SPLITWIRED QUADRUPLEX RECEPTACLE WITH ONE CONTROLLED 1. ROOF TOP CONVENIENCE OUTLETS FOR SERVICING ROOF TOP 1. ALL WIRING RUNS SHOWN ON ALL FLOOR PLANS ARE DIAGRAMMATIC <br /> IMPLIED THEREBY TO CARRY OUT THE APPARENT INTENT THEREOF. AND ONE UNCONTROLLED DUPLEX RECEPTACLE AS SHOWN ON THE PLANS. EQUIPMENT. ONLY. ® SPECIAL PURPOSE OUTLET. TYPE & RATING TO SUIT LOAD SERVED <br /> 6. ALL MATERIALS SHALL BE NEW AND LISTED WITH THE UNDERWRITERS' I. WIRING DEVICES: db 120V DUPLEX OUTLET, HALF-SWITCHED, +18" A.F.F. U.O.N., FLUSH <br /> LABORATORIES, INC., SHALL MEET THEIR REQUIREMENTS AND SHALL BEAR 2. LINE VOLTAGE CONTROLS FOR ROOF TOP HVAC AND OTHER 2. DETERMINE PROPOSED SURFACE RACEWAY RUNS IN FIELD AND OBTAIN db 120V DUPLEX OUTLET ON EMERGENCY POWER CIRCUIT, +18" <br /> THEIR LABEL WHEREVER STANDARDS HAVE BEEN ESTABLISHED AND LABEL 1. UNITS SHALL BE EQUAL TO THE DEVICES SET FORTH HEREIN, IN STANDARD REQUIREMENTS. ARCHITECT'S APPROVAL PRIOR TO ACTUAL INSTALLATION. <br /> A.F.F. U.O.N., FLUSH <br /> SERVICE IS REGULARLY FURNISHED BY THAT AGENCY. COLOR (WHITE) AS SELECTED BY THE <br /> C. DISCONNECTS SHALL NOT BE USED AS THROUGH RACEWAYS FOR WIRING S. PULL OR JUNCTION BOXES: <br /> ARCHITECT: NOT DIRECTLY SERVING THE DISCONNECTS. SERVICING OUTLETS SHALL O FLOOR DUPLEX OUTLET <br /> 7. ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH A. WIRING DEVICES LEVITON # HUBBELL # P & S # NOT BE MOUNTED ON DISCONNECTS. 1. INSTALL WHERE INDICATED, OR AS REQUIRED BY CODE, PULL BOXES AND JUNCTION <br /> THE SIZE AND LOCATIONS OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER GFI INDICATES GROUND FAULT INTERRUPTER OUTLET <br /> POSSIBLE, CONTRACTOR SHALL MAKE USE OF ALL DATA IN ALL CONTRACT <br /> SINGLE POLE SWITCH, 15A 1201-2 HBL1201 PS15AC1 BOXES OF SUFFICIENT SIZE AND CAPACITY TO FACILITATE ALL WIRING. BOXES SHALL BE <br /> DOCUMENTS AND VERIFY THIS INFORMATION AT THE SITE. CONTRACTOR SHALL DOUBLE POLE SWITCH, 15A 1202-2 HBL1202 PS15AC2 K. 120V AND 277V BRANCH CIRCUITS: SIZED TO PROPERLY ACCOMMODATE ALL CONDUCTORS ENTERING SAME. 0 TELEPHONE WALL OUTLET UP 18 U.O.N. FLUSH EL DORADO GAS <br /> BE RESPONSIBLE FOR LAYING OUT AND INSTALLING HIS WORK TO AVOID THREE WAY SWITCH, 15A 1203-2 HBL1203 PS15AC3 1. SUCH BRANCH CIRCUITS ARE NOW SUBJECT TO CALIFORNIA ENERGY CODE, T. DISCONNECT SWITCHES: 0 COMPUTER SYSTEM WALL OUTLET UP 18" U.O.N. FLUSH STATION <br /> INTERFERENCE WITH OTHER TRADES. <br /> DUPLEX CONV. OUTLET, 15A 5262 HBL5262 5262 SECTION 130.5(c) WITH RESPECT TO VOLTAGE DROP. ow TELEPHONE WALL OUTLET UP 54 U.O.N. FLUSH <br /> 1. UNITS SHALL BE HEAVY DUTY FUSED DISCONNECT SWITCHES, TWO OR THREE IMPROVEMENT <br /> 8. WORK SHOWN ON THE DRAWINGS TO BE INSTALLED UNDERGROUND SHALL DUPLEX CONV. OUTLET, 20A 5362 HBL5362 5362 2. SUCH BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR A MAXIMUM POLE TYPE, WHERE INDICATED ON THE DRAWINGS, OR AS REQUIRED BY CODE. SWITCHES [D INTERCOM SYSTEM STATION <br /> BE INSTALLED AT LEAST 24" BELOW GRADE UNLESS OTHERWISE NOTED. BACKFILL ISOL. GROUND OUTLET, 15A 5262IG IG5262 IG5262 VOLTAGE DROP OF 3 PERCENT AT DESIGNED LOAD. AND FUSES SHALL BE AS REQUIRED BY THE LOADS SERVING. <br /> IN 6" THICK, PROPERLY MOISTENED LAYERS, SOLIDLY PACKED AND IRON TAMPED O JUNCTION BOX 1605 S. EL DORADO STREET <br /> TO A DENSITY NOT LESS THAN THAT OF ADJACENT, UNDISTURBED EARTH. RESTORE ISOL. GROUND OUTLET, 20A 53621G IG5362 IG5362 Stockton, CA. 95206 <br /> SURFACES, ROADWAYS, WALKS, CURBS, WALLS AND EXISTING UNDERGROUND DUPLEX CONV. GFI OUTLET, 15A 6599 GF15 1595E 3. TO THIS EFFECT PROVIDE THE FOLLOWING CONDUCTOR SIZES: 2. DISCONNECTS FOR FRACTIONAL HORSE POWER MOTORS SHALL BE MOTOR-RATED TIME CLOCK <br /> INSTALLATIONS TO ORIGINAL CONDITION IN AN ACCEPTABLE MANNER. A. #12THWN COPPER FOR 120V, 20A BRANCH CIRCUITS UP TO 75FT. TOGGLE TYPE DISCONNECTS. a FUSED DISCONNECT <br /> DUPLEX CONV. GFI OUTLET, 20A 6899 GF15 2095E IN CABLE LENGTH, BASED ON 12AMPS LOAD (75% OF MAXIMUM ALLOWED <br /> B. CONFLICTS BETWEEN SPECIFICATIONS AND PLANS: LOAD) PER CIRCUIT. 3. DISCONNECTS FOR SINGLE PHASE MOTORS SHALL BE SINGLE PHASE AND NOT IJ MANUAL MOTOR STARTER/DISCONNECT <br /> 2. ALL CONTROLLED RECEPTACLES SHALL BE GREY TO DIFFERENTIATE THEM FROM THREE PHASE. <br /> 1. ANY CONFLICT BETWEEN ELECTRICAL SPECIFICATIONS AND ELECTRICAL PLANS; UNCONTROLLED RECEPTACLES. WHERE SUCH AN OUTLET IS PROVIDED BY ITSELF IT SHALL B. #10THWN COPPER FOR 120V, 20A BRANCH CIRCUITS UP TO 120FT. MOTOR OUTLET LIST OF CONSULTANTS <br /> OR BETWEEN ELECTRICAL PLANS AND PLANS OF ANOTHER DISCIPLINE SHALL BE BE PROVIDED WITH A GREY WALL PLATE WITH A PERMANENT LABEL STATING "CONTROLLED IN CABLE LENGTH, BASED ON 12AMPS LOAD (75% OF MAXIMUM ALLOWED 4. LOCATE DISCONNECTS IN ACCORDANCE WITH CEC 430.102. ENSURE ALL CODE- - -- CONDUIT CONCEALED IN WALL OR CEILING MIN. SIZE=1/2 C <br /> BROUGHT TO THE ATTENTION OF THE ENGINEER ANDA RESOLUTION RECEIVED PRIOR OUTLET". WHERE SUCH AN OUTLET IS PART OF A QUADRUPLEX OUTLET, WITH ONE LOAD) PER CIRCUIT. REQUIRED CLEARANCES. TICS=NO OF #12 WIRES ARCHITECTURAL <br /> CONTROLLED AND ONE UNCONTROLLED THE UNCONTROLLED OUTLET TOGETHER WITH THE CONDUIT WITH INSULATED GROUND WIRE <br /> TO PROCUREMENT OR INSTALLATION OF THE ITEM IN QUESTION. NO TICS=2#12 U.O.N. <br /> WALL PLATE SHALL BE STANDARD COLOR SELECTED BY ARCHITECT. PROVIDE PERMANENT L. BOXES: U. SECURING AND SUPPORTING. APEX ARCHITECTURE <br /> LABEL ON PLATE ABOVE GREY OUTLET "CONTROLLED OUTLET". � CONDUIT CONCEALED IN FLOOR OR UNDERGROUND GROUND NOT SHOWN 845 S. COMMERCE STREET <br /> 2. IF THE CONTRACTOR PROCEEDS WITH THE WORK WITHOUT RECEIVING ANY 1. BOXES SHALL BE OF THE SHAPE AND SIZE BEST SUITED FOR THE PARTICULAR 1. RACEWAYS, CABLE ASSEMBLIES, BOXES, CABINETS, AND FITTINGS SHALL BE , FLEXIBLE CONDUIT FOR LIGHTING ABOVE CEILING UNLESS ISOLATED STOCKTON, CA 95206 <br /> RESOLUTION TO THE CONFLICT HE/SHE DOES SO AT HIS/HER OWN RISK AND SHALL ALTERNATIVELY, THE CONTROLLED OUTLET SHALL HAVE PERMANENT UNIQUE MARKING APPLICATION AND SHALL BE SUPPORTED DIRECTLY TO STRUCTURAL MEMBERS, FRAMING SECURELY FASTENED IN PLACE PER CEC ARTICLE 300.11. SUPPORT WIRES THAT DO <br /> RECTIFY THE WORK TO THE SATISFACTION OF THE ENGINEER AT NO ADDITIONAL PROVIDED BY THE MANUFACTURER OF THE RECEPTACLE. OR BLOCKING BY MEANS OF SCREWS, ANCHORS, BOLTS OR EMBEDDED IN MASONRY. NOT PROVIDE SECURE SUPPORT SHALL NOT BE PERMITTED AS THE SOLE SUPPORT. ® DISTRIBUTION PANEL (209)662-4874 <br /> COST TO THE OWNER OR ENGINEER. EMAIL: apexplanning@hotmail.com <br /> SUPPORT WIRES AND ASSOCIATED FITTINGS THAT PROVIDE SECURE SUPPORT AND LIGHTING PANEL ARCHITECT: STEVEN A. TORRES II <br /> 3. THE MOUNTING HEIGHTS OF LIGHT SWITCHES, RECEPTACLES AND CONTROLS SHALL A. SWITCH AND RECEPTACLE BOX SHALL BE ONE PIECE DRAWN OR STAMPED THAT ARE INSTALLED IN ADDITION TO THE CEILING GRID SUPPORT WIRES SHALL BE <br /> C. MAIN SERVICE METER/MAIN: BE MAXIMUM 48" MEASURED TO THE TOP OF BOXES OR MINIMUM 16" TO THE BOTTOM STEEL BOXES MINIMUM SIZE SHALL BE FOUR INCHES (4") SQARE. BOXES SHALL PERMITTED AS THE SOLE SUPPORT. WHERE INDEPENDENT SUPPORT WIRE ARE USED, SIGNAL CABINET AS DESIGNATED <br /> 1. SERVICE PANEL SHALL BE AS MANUFACTURED BY B-LINE OR APPROVED OF BOXES. SEE LEGEND �FOR ACTUAL MOUNTING HEIGHTS OF DEVICES. VERIFY HEIGHT BE FITTED WITH FLUSH DEVICE COVERS, PLASTER RINGS, OR TILE SWITCH RINGS THEY SHALL BE SECURED AT BOTH ENDS. CABLES AND RACEWAYS SHALL NOT BE WALL MOUNT EMERGENCY LIGHT FIXTURE W BATTERY BACKUP <br /> WITH ARCHITECT WHERE AN ACTUAL MOUNTING HEIGHT IS NOT CALLED OUT ON PLANS. IN MASONRY IN AREA WHERE EXPOSED WIRING IS PERMISSIBLE, BOXES SHALL SUPPORTED BY CEILING GRIDS. W/ <br /> BATTERY <br /> METAL ENCLOSED UNIT WITH UGPS, METERING SECTION, MAIN DISCONNECT. BEFITTED WITH SURFACE TYPE COVERS. O PUSH BUTTON. FUNCTION AS INDICATED ON FLOOR PLAN HCS <br /> UNIT SHALL MEET ALL UTILITY COMPANY REQUIREMENTS AND BE APPROVED BY 4. SINGLE RECEPTACLE SERVED BY INDIVIDUAL 20A BRANCH CIRCUIT DEDICATED TO 2. FURNISH ALL NECESSARY FOUNDATIONS, SUPPORTS, BACKING, ETC., FOR ALL US MOTION SENSITIVE OCCUPANCY SENSOR, CEILING MOUNT <br /> THE SAME PRIOR TO PROCUREMENT AND INSTALLATION. THE OUTLET SHALL BE 20A RATED PER CEC 210.21(B)(1). ALL OTHERS SHALL BE D. WEATHERPROOF BOXES SHALL BE APPLETON FD SERIES AND FITTED WITH ELECTRICAL ENCLOSURES, CONDUITS AND EQUIPMENT. Engineering2. SERVICE PANEL SHALL BE ENCLOSED STRUCTURE OF CODE GAUGE STEEL 15A RATED. GASKETED CAST COVERS. PP POWER PACK FOR OCCUPANCY SENSOR. MOUNT IN CEILING SPACE <br /> 3. ATTACH ALL BOXES, CABINETS, ETC. TO WOOD WITH WOOD OR LAG SCREWS, 50 years <br /> PLATES WITH REMOVABLE FRONT. FULL FRONT ACCESS SHALL BE PROVIDED FOR 5. ALL 15A AND 20A, 120V OUTLETS IN KITCHEN SHALL BE GFIC PER CEC 210.8(B)(2). E. VOICE/DATA OUTLET BOXES SHALL BE 4_11/16" X 2_1/2" TO METAL WITH MACHINE SCREWS OR BOLTS AND TO CONCRETE WITH EXPANSION $DRC DIMMING RELAY CONTROLLER <br /> CONNECTIONS AND OPERATIONS. UNIT SHALL BE NEMA 1 FOR INDOOR INSTALLATION LOCATE SUCH OUTLETS SO THAT THEY ARE ACCESSIBLE AFTER APPLIANCES THAT ARE DEEP MINIMUM, FITTED WITH PLASTER RINGS. ANCHORS AND MACHINE SCREWS OR BOLTS. 4512 Feather River Or . Stockton,CA 95219 <br /> Pc PHOTOCELL 209-478-8270 <br /> AND NEMA 3R FOR OUTDOOR INSTALLATION. PLUGGED INTO THE OUTLETS ARE IN PLACE. wwwhcs-eng.com <br /> F. BOXES FOR SPECIAL EQUIPMENT SHALL BE SUITABLE FOR THE PARTICULAR Y. GROUNDING: [P DIMMER/OCCUPANCY SENSOR SWITCH <br /> 3. UNIT SHALL HAVE MINIMUM A.I.C. RATING EQUAL TO THE SHORT CIRCUIT 6. 120V RECEPTACLES ARE NOW SUBJECT TO CALIFORNIA ENERGY CODE, SECTION EQUIPMENT. In Richard C.Smith,PE richard@hcs-eng.com <br /> CURRENT AVAILABLE AT THE SERVICE PANEL FROM THE UTILITY COMPANY 130.5(d). ALL SUCH OUTLETS SHALL BE CONSIDERED AS UNCONTROLLED EXCEPT THOSE 1. GROUND AND BOND ALL EQUIPMENT AS REQUIRED BY GOVERNING CODES. ❑Bhupendra Patel,PE bhupendra@hcs-eng.com <br /> TRANSFORMER. WHICH ARE SPECIFICALLY CALLED OUT ON THE PLANS AS CONTROLLED. SEE "CONTROLLED G. BOXES SHALL BE LOCATED AND PLACED ACCORDING TO ARCHITECTURAL AND ❑Elizabeth Aguilar elizabeth@hcs-eng.com <br /> 120V RECEPTACLES" PARAGRAPH ABOVE. STRUCTURAL REQUIREMENTS. 2. PROVIDE EQUIPMENT GROUNDING CONDUCTORS IN ALL FEEDERS AND BRANCH <br /> 4. PROVIDE INCOMING SERVICE TERMINALS METERING SECTION, CTs, ETC. IN CIRCUITS, SIZED PER C.E.C. TABLE 250.122. PROJECT 2019.285 <br /> ACCORDANCE WITH THE UTILITY COMPANY AND PLANS. J. WIRING METHODS: LINE VOLTAGE SYSTEMS (120V AND ABOVE) M. DEVICE PLATES: 3. ALL GROUND WIRES SHALL BE INSULATED GROUND WIRES. <br /> 5. PROVIDE A GROUND BUS. 1. ALL WIRING SHALL BE INSTALLED IN CONDUITS. CONDUITS SHALL BE 1. ALL DEVICE PLATES FOR INDOOR USE SHALL BE NYLON. PROFESSION <br /> RUN CONCEALED IN WALLS AND CEILINGS WHERE FEASIBLE. ALL CONDUITS INSTALLED Z. HVAC SYSTEMS: ABBREVIATIONS R0 <br /> D. PANELBOARDS: SURFACE ON WALL SHALL BE PAINTED TO MATCH WALL FINISH. MOUNT EXTERIOR 2. ALL DEVICE BOXES WHICH ARE INSTALLED IN FIRE RATED WALL ASSEMBLY AND <br /> CONDUITS ON WALL ON GALVANIZED UNISTRUTS. ALL SURFACE CONDUIT INSTALLATION/ IS PROVIDED WITH A FIRE-STOPPING PUTTY PAD SHALL HAVE A BRUSHED STAINLESS 1. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL CONTRACTOR FOR <br /> 1. UNITS SHALL BE FLUSH OR SURFACE MOUNTED AS INDICATED ON THE RUNS SHALL BE APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION. STEEL COVERPLATE IN ACCORDANCE WITH THE REQUIREMENTS OF THE PUTTY PAD. EXACT LOCATIONS OF ALL HVAC UNITS, DISCONNECTS AND DEVICES IN FIELD. COORDINATE A.F.G. ABOVE FINISHED GRADE Na. E1a3o3 <br /> PANEL SCHEDULE, WITH THE NUMBER AND SIZE OF BREAKERS AS INDICATED ON THE ROOF PENETRATIONS FOR DISCONNECTS AND WEATHERPROOF OUTLETS WITH ELECTRICAL A.F.F. ABOVE FINISHED FLOOR Exp. 6-30-21 <br /> PANEL SCHEDULE. SINGLE POLE, TWO POLE, AND THREE POLE BREAKERS SHALL BE 2. ALL CONDUITS RUN WITHIN INTERIOR FINISHED SPACES SUCH AS OFFICES, 3. DEVICE COVERS FOR SURFACE MOUNTED BOXES SHALL BE 1/2" RAISED STEEL CONNECTION POINTS ON THE UNITS TO KEEP FLEXIBLE CONDUIT LENGTH TO A MINIMUM <br /> BOLT-ON TYPE. MULTIPLE POLE BREAKERS SHALL HAVE COMMON INTERNAL TRIP BREAKROOM, RESTROOM ETC. SHALL BE RUN CONCEALED. PLATES. (36 MAXIMUM). VERIFY AND CONFIRM THE ACTUAL MOUNTING LOCATION ON THE HVAC UG UNDERGROUND �, <ECTR�cP <br /> CONNECTION. SINGLE POLE BREAKERS SHALL NOT BE TIED AT HANDLES TO FORM UNIT FOR THE DISCONNECT. ALL SERVICING OUTLETS ON THE ROOF OR OUTDOORS FOR WP WEATHERPROOF 9TFoF <br /> MULTIPLE POLE BREAKERS. THE PANEL DOORS SHALL BE DOOR-IN-DOOR CONSTRUCTION 3. ALL CONDUITS RUN IN DEDICATED ELECTRICAL AND MECHANICAL ROOMS AND 4. DEVICE COVERS FOR DEVICES LOCATED IN DAMP LOCATIONS SHALL COMPLY WITH HVAC UNITS SHALL BE WP/GFI. CAu�F <br /> AND SHALL HAVE FLUSH TYPE LOCKS, ALL LOCKS SHALL BE KEYED ALIKE AND HAVE SHOP AREA SHALL BE RUN EXPOSED. CEC 406.9(A). CO CONDUIT ONLY <br /> TYPEWRITTEN DIRECTORIES INDICATING FIXTURES, EQUIPMENT, OR OUTLETS SERVICE BY 2. THE RATING OF THE DISCONNECT SHALL BE SUCH AS TO ENABLE THE LARGEST <br /> EACH BREAKER. PANELS SHALL HAVE COPPER BUSSING. 4. MINIMUM CONDUIT SIZE SHALL BE 1/2" ABOVE GRADE AND 3/4" UNDERGROUND. 5. DEVICE COVERS FOR DEVICES LOCATED IN WET LOCATIONS SHALL COMPLY WITH FUSE SIZE ON THE UNIT NAMEPLATE TO BE INSTALLED IN THE DISCONNECT. PROVIDE C CONDUIT <br /> CEC 406.9(B). FUSES OF THIS RATING. U.O.N. UNLESS OTHERWISE NOTED <br /> E. LIGHTING: 5. MINIMUM ACCEPTABLE CONDUITS ARE: PLAN REVIEW ACCEPTANCE <br /> A. GALVANIZED RIGID STEEL - FOR USE ON: N. INSTALLATION OF RACEWAYS AND FITTINGS 3. FURNISH AND INSTALL ALL LINE VOLTAGE CONDUITS AND LINE VOLTAGE WIRING NO. NUMBER <br /> 1. ALL LUMINAIRES SHALL BE CERTIFIED BY THE MANUFACTURER TO THE 1 EXTERIOR WALL SURFACES. (LOW VOLTAGE CONDUITS AND WIRING BY MECHANICAL) TO HVAC EQUIPMENT AND <br /> CALIFORNIA ENERGY COMMISSION: ( ) ASSOCIATED CONTROLS AND DEVICES AS SHOWN ON THE ELECTRICAL AND MECHANICAL MIN. MINIMUM <br /> B. GALVANISED STEEL EMT FOR USE: 1. CONCEAL RACEWAYS WITHIN CEILINGS, WALLS, AND FLOORS EXCEPT WHERE Aug4 2020 <br /> A. ALL LUMINAIRES SPECIFIED ON THIS PROJECT SHALL BE AS NOTED IN EXPOSED RACEWAYS ARE SPECIFICALLY PERMITTED. PLANS, UNLESS OTHERWISE NOTED. MAX. MAXIMUM 9 <br /> THE "LIGHT FIXTURE SCHEDULE" ON THESE PLANS. NO SUBSTITUTES �1) CONCEALED IN INDOOR FINISHED SPACES. <br /> ARE PERMITTED WITHOUT WRITTEN APPROVAL OF THE ENGINEER. 2 EXPOSED INSIDE ELECTRICAL & MECHANICAL ROOMS AND IN SHOP AREA. 2 WHERE CONDUIT IS ALLOWED TO BE EXPOSED, INSTALL THE CONDUIT PARALLEL 4. RUN ALL CONDUITS FOR ROOFTOP EQUIPMENT WITHIN CEILING SPACE BELOW. A, AMP AMPERE <br /> B. ALL INTERIOR LUMINAIRES SHALL BE PROVIDED WITH 0-10V DIMMING LED C. LIQUID TIGHT STEEL FLEX: WITH OR AT RIGHT ANGLES TO STRUCTURAL MEMBERS, WALLS, AND LINES OF SURFACE CONDUIT RUNS ON THE ROOF ARE NOT PERMITTED ON THIS PROJECT. W/ WITH WEST COAST CODE CONSULTANTS <br /> DRIVERS WITH INTEGRAL DIMMING MOTION SENSORS. (1) EOR FI L CONNECTION TO OUTDOOR EQUIPMENT. LENGTH SHALL NOT THE BUILDING. 5. DISCONNECTS SHALL NOT BE USED AS THROUGH RACEWAYS FOR WIRING NOT GFI GROUND FAULT INTERRUPTER <br /> C. ALL EXTERIOR LUMINAIRES SHALL BE PROVIDED WITH 0-10V DIMMING LED <br /> DRIVERS WITH INTEGRAL MOTION SENSORS. D. FLEXIBLE STEEL CONDUIT: 3. INSTALL WHERE INDICATED, OR AS REQUIRED BY CODE, PULLBOXES AND DIRECTLY SERVING THE DISCONNECTS. SERVICING OUTLETS SHALL NOT BE MOUNTED & AND <br /> (1) FOR INDOOR FINAL CONNECTION TO RECESSED LIGHT FIXTURES. LENGTH JUNCTION BOXES OF SUFFICIENT SIZE TO FACILITATE WIRING. BOXES SHALL ON DISCONNECTS. <br /> F. INTERIOR LIGHTING CONTROL SYSTEM: (2) SHALL NOT FOR INDOOR FINAL CONNECTION TO HVAC EQUIPMENT. LENGTH SHALL BE SIZED TO PROPERLY ACCOMMODATE ALL CONDUCTORS ENTERING SAME. M. SUBMITALLS: (e),(E) EXISTING R REMOVE ELECTRICAL <br /> 1. PROVIDE A COMPLETE AND FULLY OPERATIONAL INTERIOR LIGHTING CONTROL NOT EXCEED 36". 4. DO NOT INSTALL CONDUIT OR TUBING WHICH HAS BEEN CRUSHED OR 1. PROVIDE THE FOLOWING SUBMITTALS FOR REVIEW AND APPROVAL BY THE ARCHITECT <br /> SYSTEM FOR INTERIOR LIGHTING AS SPECIFIED HEREIN AND SHOWN ON THE DRAWINGS. E. PVC SCHEDULE 40: DEFORMED. AND ENGINEER. (RR) REMOVE, RELOCATE AND RECONNECT AT LOCATION SHOWN SPECIFICATIONS <br /> (1) FOR CONDUITS RUN UNDERGROUND AND FOR UNDER BUILDING SLAB. a. SERVICE SWITCHBOARD d. LIGHTING CONTROLS A.I.C. AMPERE INTERRUPTING CAPACITY <br /> 2. THE COMPLETE SYSTEM, INCLUDING ALL DEVICES SHALL BE IN COMPLIANCE WITH 2 CONDUIT STUBUPS THROUGH THE FLOOR OR GRADE SHALL BE IN 5. RUN CONDUCTORS OF SAME CIRCUIT IN SAME CONDUIT. RUN CONDUCTORS b. PANEL BOARDS <br /> THE 2013 CALIFORNIA ENERGY CODE. PVC ELBOW WITH RIGID STEEL COUPLING FLUSH WITH FLOOR. OF DIFFERENT VOLTAGE SYSTEMS IN SEPARATE CONDUITS. c. LIGHT FIXTURES GRD. GROUND <br /> (3) NOT PERMITTED FOR WIRING ABOVE FINISHED FLOOR INSIDE BUILDINGS 6. INSTALL NO CONDUCTORS UNTIL WORK WHICH MIGHT CAUSE DAMAGE TO SUCH V VOLT <br /> 3. THE COMPLETE SYSTEM SHALL BE AS MANUFACTURED BY nLIGHT CONSISTING OF: F. ALUMINUM CONDUITS, IMC CONDUITS OR ALUMINUM FITTINGS ARE NOT CONDUCTORS OR THE CONDUIT HAS BEEN COMPLETED. BB. ARC FLASH HAZARDS: <br /> A. LUMINAIRES WITH 0-10V DIMMING LED DRIVERS, nLIGHT ENABLED. APPROVED FOR USE ON THIS PROJECT. CKT. CIRCUIT <br /> B. LUMINAIRES WITH 0-10V DIMMING LED DRIVERS, NOT nLIGHT ENABLED. G. ALL CONDUIT FITTINGS SHALL BE MALLEABLE IRON/STEEL. 7. KEEP ALL CONDUITS AT LEAST SIX INCHES AWAY FROM THE COVERING ON HOT 1. PROVIDE WARNING LABEL ON ELECTRICAL EQUIPMENT OF POSSIBLE ARC FLASH KW KILOWATT <br /> C. LUMINAIRES WITH INTEGRAL MOTIONI SENSORS WHERE SO CALLED OUT. H. EMT COUPLING - APPLETON TWC-CS SERIES WATER OR STEAM PIPES. HAZARDS PER CEC 110.16. KVA KILOVOLT AMPERE <br /> EMT CONNECTOR - APPLETON TW-CSI SERIES CC. TESTING: THESE PLANS ARE SUBJECT <br /> D. WALL DIMMER SWITCHES THAT COMMUNICATE WITH THEIR RELATED/PAIRED FLEX CONDUIT CONNECTOR - T&B "TITE BITE", INSULATED 8. CAP RACEWAY ENDS DURING CONSTRUCTION. CLEAN OR REPLACE CONDUITS IN SP SPACE <br /> LIGHT FIXTURES. LIQUID TIGHT FLEX CONDUIT CONNECTOR - APPLETON "STB" SERIES WHICH WATER OR FOREIGN MATTER HAVE ACCUMULATED, TO THE SATISFACTION OF <br /> E. DEMAND RESPONSE CONTROLS PER CEC SECTION 130.1(e) WHERE UP TO 2", "ST" SERIES OVER 2". THE ARCHITECT. 1. THE ENTIRE ELECTRICAL INSTALLATION SHALL BE FREE FROM SHORT CIRCUITS CU COPPER TO FIELD APPROVAL <br /> APPLICABLE. 1. RIGID STEEL CONDUIT CONNECTED TO BOXES AND CABINETS SHALL BE AND IMPROPER GROUNDS. TEST ALL WIRING AND CONNECTIONS FOR CONTINUITY AND AL ALUMINUM 08-32 <br /> FITTED WITH TWO LOCKNUTS AND INSULATING BUSHING, OA "A" SERIES. 9. CONDUITS SHALL BE SUPPORTED WITH STRAPS, WITH GALVANIZED MALLEABLE GROUNDS BEFORE ANY FIXTURES OR EQUIPMENT ARE CONNECTED AND WHERE SUCH <br /> 4. ALL SYSTEM COMPONENTS SHALL BE UL LISTED. ALL SYSTEM CONTROL PROVIDE GROUNDING BUSHING OZ "BL" SERIES WHERE LOCKNUTS AND SPLIT RING AND ROD FOR INDIVIDUAL RUNS OR WITH KINDORF OR UNISTRUT CHANNEL TESTS INDICATE FAULTY INSULATION OR OTHER DEFECTS, THEY SHALL BE LOCATED, LC LIGHTING CONTACTOR PROJECT: <br /> COMPONENTS SHALL BE APPROVED BY THE CALIFORNIA ENERGY COMMISSION. BUSHING IS NOT USED. CONDUITS CONNECTED TO BOXES EXPOSED TO SUPPORTS FOR MULTIPLE RUNS. DISTANCE BETWEEN SUPPORTS SHALL NOT EXCEED REPAIRED AND RETESTED AT THE CONTRACTORS EXPENSE. PROVIDE ALL INSTRUMENTS IF THESE PLANS ARE NOT ON THE JOB <br /> WEATHER/MOISTURE SHALL BE FITTED WITH WATERTIGHT SEALING HUBS 10 FEET. CONDUITS SHALL BE SUPPORTED INDEPENDENTLY OF ONE ANOTHER. TO MAKE SUCH TESTS. NL NIGHT LIGHT SITE NO INSPECTIONS WILL BE MADE 10/16/2019 <br /> 5. ALL EQUIPMENT AND ITEMS OF CONTROL SHALL BE INSTALLED AND WIRED IN OF STEEL OR MALLEABLE IRON WITH SEALING RING AND INSULATED PB PULLBOX <br /> ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS. THREAT, T & B 370 SERIES. 10. CONDUITS CONNECTED TO BOXES AND CABINETS SHALL BE FITTED WITH TWO 2• DEMONSTRATE TO THE OWNER AND THE ARCHITECT, THAT THE ENTIRE <br /> J. TYPE NM AND NMC CABLES SHALL NOT BE USED ON THIS PROJECT. LOCKNUTS AND INSULATED BUSHING, OA "A" SERIES. INSTALLATION IS COMPLETE, IN PROPER OPERATING CONDITION AND THAT THE E.C. ELECTRICAL CONTRACTOR <br /> 6. PROVIDE WALL OCCUPANCY SENSOR LIGHT SWITCHES WHERE SO SHOWN ON K. THE PROJECT DRAWINGS ARE LAID OUT USING SOLID CONDUITS AND CONTRACT HAS BEEN PROPERLY AND FULLY EXECUTED. G.C. GENERAL CONTRACTOR <br /> PLANS. SUCH OCCUPANCY SENSOR SWITCHES SHALL BE SINGLE LEVEL AUTOMATIC CABLES PULLED THROUGH SUCH CONDUITS. MC CABLES MAY BE UTILIZED 11. CONDUITS NOT CONNECTED WITH LOCKNUTS AND BUSHINGS SHALL BE FITTED <br /> "ON"/AUTOMATIC "OFF" AS SHOWN ON PLANS. SENSORS SHALL COMPLY WITH AS DESCRIBED BELOW, WITH RESTRICTIONS NOTED. WITH GROUNDING BUSHING, OZ "BL" SERIES, U. L. APPROVED AND BONDED. P.C. PLUMBING CONTRACTOR - REV.# DATEISSUED DESCRIPTION <br /> SECTION 110.9 OF THE ENERGY CODE. <br /> (1) PRIOR APPROVAL OF OWNER/ARCHITECT REQUIRED. 12. CONDUIT STRAPS FOR INDIVIDUAL RUNS SHALL BE SECURED BY TOGGLE M.C. MECHANICAL CONTRACTOR REV11 11/20/19 PLAN CHECK <br /> 7. PROVIDE INSULATED GROUND WIRE TO EACH LINE VOLTAGE WALL BOX SENSOR. (2) MC CABLES SHALL BE AS MANUFACTURED BY SOUTHWIRE TYPE EZ-MC BOLTS ON HOLLOW MASONRY, EXPANSION ANCHORS ON SOLID CONCRETE OR <br /> DURACLAD TYPE WITH LIGHT WEIGHT STEEL ARMOR AND INSULATED MASONRY, MACHINE SCREWS OR BOLTS ON METAL SURFACES AND WOOD SCREWS <br /> 8. THE SYSTEM SHALL AUTOMATICALLY SWITCH OFF ALL LIGHTS WHEN CONTROLLED GREEN GROUNDING CONDUCTORS OR APPROVED EQUAL. ON WOOD CONSTRUCTION. THE USE OF NAILS TO ANCHOR STRAPS ON WOOD <br /> SPACE BECOMES UNOCCUPIED AND SWITCH ON LIGHTS WHEN THE SPACE IS (3) SHALL BE USED FOR BRANCH CIRCUITS ONLY AS NOTED BELOW. CONSTRUCTION IS PROHIBITED. STRAPS SHALL BE TWO HOLE MALLEABLE IRON OR <br /> RE-OCCUPIED. ALL SENSORS SHALL BE PROVIDED WITH USER ADJUSTABLE a CANNOT BE USED ANYWHERE EXPOSED. SNAP-TYPE STEEL WITH RIBBED BACK, GALVANIZED OR CADMIUM PLATED. THE USE CITY O F STOC KTO N <br /> TIME DELAY (15 SEC. TO 20 MINUTES) FOR SWITCH-OFF FUNCTION AND �b� LIGHTING: VERTICAL DROPS IN WALL FOR LIGHT SWITCHES FORM <br /> ADJUSTABLE SENSITIVITY. JBOX IN CEILING. HORIZONTAL RUNS IN CEILING SHALL BE IN 13. PLACEMENT OF ALL BOXES SHALL BE GOVERNED BY APPLICABLE ARCHITECTURAL <br /> SOLID STEEL CONDUITS. AND STRUCTURAL REQUIREMENTS. APPROVED PLAN S <br /> 9. WHERE LIGHT FIXTURES FALL UNDER THE PRIMARY AND SECONDARY DAYLIT <br /> (c) POWER RECEPTACLES: <br /> ZONES AS DEFINED BY SECTION 130.1(d) AND THE TOTAL INSTALLED GENERAL ( ) FOR UNDERGROUND HOMERUNS: VERTICAL CONDUIT RISER 14. CONDUIT FITTINGS: EXCEPT WHERE OTHERWISE NOTED, CONDUIT FITTINGS SHALL By:dhenry Date:08/06/2020 <br /> LIGHTING POWER IN THE PRIMARY DAYLIT ZONE IS NOT LESS THAN 120W (EXCEPTION BE APPLETON OR APPROVED EQUAL. UNILETS SHALL BE MALLEABLE IRON AND FITTED E ❑ ■ I <br /> WI <br /> JUNCTION BOX THEN HORIZONTAL RUNS WITHIN WALLS TO <br /> #1 TO SECTION 130.1(d)2) SUCH LIGHT FIXTURES SHALL BE PROVIDED WITH IN WALL FROM UNDERGROUND CONDUIT FIRST RECEPTACLE WITH COVERS AND GASKETS. <br /> AUTOMATIC CONTROLS IN ACCORDANCE WITH SECTION 130.1(d)(2)(D). OTHER RECEPTACLE BOXES CAN BE IN MC CABLES. <br /> Copyright APEX <br /> K:\2019\201-300\2019.285 APEX El Dorado Convenience Gas Station Improvement\Eo.1.dwg 11-20-19 09:26:51 AM richard <br />