Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST (continued) <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard X Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum X Hydrostatic <br /> Test Equipment Used: Cadwell Level Indicator, test fluid (H20) <br /> Sump/UDC ID 3-4 UDC 5-6 UDC 7-8 UDC 9-10 UDC <br /> Sump Manufacturer unknown unknown unknown unknown <br /> Sump Depth (inches) 28" 28" 28" 28" <br /> Sump Bottom to Top of 11" 11" 11" 11" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 30 minutes 30 minutes 30 minutes 30 minutes <br /> Initial Reading first circle first circle first circle first circle <br /> Test End Time 0 minutes 0 minutes 0 minutes 0 minutes <br /> Final Reading no change no change no change no change <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria 0.002/30mins 0.002/30mins 0.002/30mins 0.002/30mins <br /> Tightness Test Results X Pass ❑ Fail X Pass ❑ Fail X Pass ❑ Fail X Pass ❑ Fail <br /> Sump/UDC ID 11-12 UDC <br /> Sump Manufacturer unknown <br /> Sump Depth (inches) 28" <br /> Sump Bottom to Top of 11" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 30 minutes <br /> Initial Reading first circle <br /> Test End Time 0 minutes <br /> Final Reading no change <br /> Change in Reading 0 <br /> Pass/Fail Criteria 0.002/30mins 0.002/30mins 0.002/30mins 0.002/30mins <br /> Tightness Test Results X Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />