Laserfiche WebLink
SAN J O A R N Environmental Health Department <br /> -:a U ;� i _# �V AMENDED <br /> 4/26/2021 <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> JD Service Station, Inc. 1 9015 WALNUT GROVE RD, THORNTON April 20, 2021 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 208 CCR 2716(a-e) Failure to comply with the designated operator inspection requirements. <br /> OBSERVATION: Designated operator reports were not signed within the required time frame. Multiple designated <br /> operator reports were not signed and dated by the owner/operator. <br /> REGULATORY GUIDANCE:Within 48 hours of the completion of the designated UST operator visual inspection, <br /> the designated operator shall sign and provide the owner or operator with a copy of the inspection report. Within 72 <br /> hours of being provided a signed copy of the report,the owner or operator shall provide a description of each <br /> corrective action taken or to be taken and shall sign and date the report, acknowledging the identified compliance <br /> issues. <br /> CORRECTIVE ACTION: Ensure all designated operator inspection reports are completed and signed within the <br /> required time frame in the future. <br /> This is a repeat violation, Class II. <br /> 209 CCR 2715(c)(3), 2715(c)(4) Failure to maintain a copy of the"Facility Employee Training Certificate"on-site. <br /> OBSERVATION: The Facility Employee Training Certificate dated 3/26/2021 does not list initial training dates for <br /> employees trained. <br /> REGULATION GUIDANCE:All site employees must be trained prior to taking responsibility as a facility employee if <br /> after October 1, 2018, or within 30 days of hire if prior to October 1, 2018. The Facility Employee Training <br /> Certificate shall contain accurate information for all employees trained. <br /> CORRECTIVE ACTION: Update the Facility Employee Training Certificate to contain the accurate information and <br /> submit a copy of the updated form to the EHD. <br /> This is a minor violation. <br /> 304 CCR 2631(a); HSC 25290.1(c) Failure to construct, operate, and maintain primary containment as product-tight. <br /> OBSERVATION: Dispenser 11/12 was observed to have liquid seeping from the shear valve and liquid was <br /> observed at the bottom of the UDC indicating a leak in the primary containment. <br /> REGULATION GUIDANCE:All primary containment for the UST system must be product tight. <br /> CORRECTIVE ACTION: Immediately have a properly licensed,trained, and certified contractor repair or replace the <br /> failed component(s), under permit and inspection of the EHD if necessary. <br /> This is a Class II violation. <br /> FA0014762 PR0521738 SCO01 04/20/2021 <br /> EHD 23-01 Rev.9/16/2020 Page 5 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />