Laserfiche WebLink
A NJ O A Q U l N Environmental Health Department <br /> COUNTY— V AMENDED <br /> 4/16/2021 <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> QUIK STOP MARKET#132 3555 W HAMMER LN, STOCKTON April 13, 2021 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 302 CCR 2630(d), 2641(a)Leak detection equipment not installed/maintained/located to detect leaks at earliest <br /> opportunity. <br /> OBSERVATION: The UDC 1/2, 3/4, 5/6, and 7/8 have multiple open cups on the bottom of the UDCs thus having <br /> multiple low points. The 208 sensor is placed in one of the open cups.There are also barriers in the UDCs that <br /> prevent liquid from all areas to reach the sensor. The barriers and multiple low points result in the sensor not located <br /> to detect a leak at the earliest opportunity. <br /> REGULATION GUIDANCE: Monitoring equipment shall be maintained to be able to detect a leak at the earliest <br /> possible opportunity. <br /> CORRECTIVE ACTION: Immediately relocate this sensor to the lowest point of the UDC 1/2, 3/4, 5/6, 7/8. <br /> This is a Class II violation. <br /> 306 HSC 25291(e)Failure to remove, analyze, and properly dispose of water in secondary containment(pre-Jul 2003). <br /> OBSERVATION: Liquid was observed in the 91 STP sump and UDCs 1/2 and 5/6. <br /> REGULATION GUIDANCE: If water could enter into the secondary containment by precipitation or infiltration, it <br /> must be removed and disposed of properly. <br /> CORRECTIVE ACTION: The service technician removed approximately 2 pints of liquid from the 91 STP sump, <br /> UDC 1/2 and UDC 5/6. Ensure that all sumps and annular spaces are maintained free of liquid. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> An inspection report was provided to the facility operator on the day of inspection. The report was amended and <br /> replaces the initial report. Violation#122 was removed. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, within 30 days of receiving the amended inspection report. <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: April 13, 2021 Inspector: Inspector Phone: <br /> Printed Name and Title: CAROL PRESTO, EH Specialist (209)616-3061 <br /> Dharminder Singh, Manager <br /> FA0002232 PR0231130 SCO01 04/13/2021 <br /> EHD 23-01 Rev.9/16/2020 Page 7 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />