SECTION 265100 - INTERIOR LIGHTING 9. Wireguards for any wall-mounted luminaires, including 3.03 INSTALLATION OF PATHWAYS
<br /> emergency lighting unit equipment and exit signs, located in A. All Pathways:
<br /> PART 1 GENERAL gymnasiums or where otherwise exposed to physical damage. 1. Install all pathways with the following minimum clearances: _
<br /> 1.01 QUALITY ASSURANCE 10. Fire-rated luminaire covers (tents) for luminaires installed a. 48 inches from motors, generators, frequency converters,
<br /> A. Verify all ceiling systems for proper coordination of luminaires and in fire-rated ceiling assemblies; coordinate locations of transformers, x-ray equipment, and uninterruptible power
<br /> accessories including any drywall frames, bar hangers, flanges, trim fire-rated ceiling assemblies with the Architectural plans. systems.
<br /> rings, etc. required for a complete, finished installation. 11. Any seismic bracing and/or restraints required by the b. 12 inches from power conduits and cables and
<br /> B. Provide only luminaires that are listed for the environment in which Authority Having Jurisdiction. panelboards. +•
<br /> they are installed. 12. Provide Bodine #GTD20A lighting relay control device for each C. 5 inches from fluorescent and high frequency lighting 14W
<br /> 1. Luminaires shall carry damp location and/or wet location circuit serving luminaires that are used for both normal and fixtures.
<br /> ratings as required. emergency lighting where a generator or central lighting d. 6 inches from flues, hot water pipes, and steam pipes.
<br /> 2. Luminaires shall be insulated ceiling (IC) rated when recessed inverter is used for emergency power and the luminaires are B. Conduit:
<br /> into insulated ceilings; coordinate locations of all insulated controlled by local switching, contactors, or relays. 1. Install conduit in compliance with Section 260534 unless
<br /> ceilings with the Architectural plans. indicated otherwise.
<br /> C. Coordinate exact locations of all luminaires with the Architectural PART 3 EXECUTION a. Do not install more than two 90 degree bends in a single
<br /> Reflected Ceiling Plans ; luminaire locations on the Architectural 3.01 INSTALLATION horizontal cable run.
<br /> Reflected Ceiling Plan s take precedence over locations indicated A. Install luminaires in locations shown on the Architectural Reflected b. Leave pull cords in place where cables are not initially
<br /> on the electrical lighting plans. Ceiling Plan(s); luminaire locations on the Architectural Reflected installed.
<br /> D. Coordinate mounting heights of all wall-mounted luminaires with the Ceiling Plan s take precedence over locations indicated on the C. Under floor slabs, locate conduit at 12 inches minimum ©2017 STARBUCKS COFFEE COMPANY
<br /> Architect prior to rough-in. electrical lighting plans. below vapor retarder and seal penetrations of vapor
<br /> E. Confirm all luminaire and accessory finishes with the Architect B. Install luminaires plumb and level and align with building lines and retarder around conduit.
<br /> prior to ordering. adjacent luminaires. 2. Underground Service Entrance: Install conduit at least 18 STARBUCKS COFFEE
<br /> F. Coordinate luminaire dimensions with the wall and/or ceiling C. Support all luminaires completely independent of any suspended inches below finish grade and encase in at least 3 inches
<br /> thickness prior to ordering. ceiling systems. thick concrete for at least 60 inches out from the building COMPANY
<br /> G. Coordinate mounting location, number of faces, and directional D. Connect luminaires to branch circuit. line.
<br /> arrows of exit signs as required to mark paths of egress to the 1. Circuit all exit signs, emergency lights, and nightlights C. Grounding and Bonding: Perform in accordance with ANSI/J-STD-607 2401 UTAH AVENUE SOUTH
<br /> satisfaction of the Authority Having Jurisdiction. ahead of any switching. and NFPA 70.
<br /> 2. Do not use multiwire branch circuits for circuits serving 3.04 INSTALLATION OF CABLES, PLUGS, AND JACKS SEATTLE,WASHINGTON 98134
<br /> PART 2 PRODUCTS emergency lighting equipment such as emergency batteries or A. Only if required pursuant to meeting with the Owner: (206)318-1575
<br /> 2.01 LUMINAIRES emergency lighting unit equipment. 1. Install cables from outlet to cross-connection equipment as
<br /> A. Provide as indicated on the Drawings. E. Provide all additional emergency lighting and/or exit signs directed by the Owner.
<br /> B. The acceptability of any substitute fixtures lies solely with the determined necessary by the Authority Having Jurisdiction during 2. Do not exceed 300 feet from outlet to switch. THESE DRAWINGS AND SPECIFICATIONS ARE
<br /> Architect and Engineer. inspections. 3. Do not bend cable tighter than the greater of the CONFIDENTIAL AND SHALL REMAIN THE SOLE
<br /> C. The specified luminaire shall be provided at no additional cost F. Install all remote ballasts, low voltage transformers, and drivers manufacturer's recommended bend radius or 4 times the cable PROPERTY OF STARBUCKS CORPORATION,
<br /> where a substitute fixture is not accepted by the Architect or in concealed accessible areas in close proximity to the associated diameter. WHICH IS THE OWNER OF THE COPYRIGHT IN
<br /> Engineer. luminaires and connect to the associated luminaires per the 4. Do not exceed the greater of the manufacturer's recommended THIS WORK. THEY SHALL NOT BE
<br /> 2.02 NON-DIMMING BALLASTS, TRANSFORMERS, AND DRIVERS manufacturer's recommendations, including adjusting wire sizes for cable pull tension or 25 pounds.
<br /> A. All Ballasts, Transformers, and Drivers voltage drop if required. 5. Use only lubricants approved by cable manufacturer when REPRODUCED(IN WHOLE OR IN PART), SHARED
<br /> 1. Provide low-temperature ballasts when installed in locations G. Prevent insulation from being installed above or within 3 inches installing cables in conduit and do not chafe or damage outer WITH THIRD PARTIES OR USED IN ANY MANNER
<br /> where ambient temperature can fall below 10 degrees C (50 away from any luminaire that is recessed into an insulated ceiling jacket. ON OTHER PROJECTS OR EXTENSIONS TO THIS
<br /> degrees F). but is not insulated ceiling (IC) rated. 6. Install plugs and jacks as required. PROJECT WITHOUT THE PRIOR WRITTEN
<br /> B. Electronic Linear Fluorescent Ballasts: H. Install fire-rated luminaire covers (tents) for luminaires installed 7. Provide the following minimum extra length of cable, looped CONSENT OF STARBUCKS CORPORATION.
<br /> 1. Description: Osram Sylvania Quicktronic High Efficiency in fire-rated ceiling assemblies; provide fire-rated boxes around neatly.
<br /> series or equalluminaires when fire-rated luminaire covers (tents) are not a. At Patch Panels: 10 feet. THESE DRAWINGS AND SPECIFICATIONS ARE
<br /> 2. Voltage: Universal (120 through 277 volts). available. b. At Outlets: 12 inches. INTENDED TO EXPRESS DESIGN INTENT FOR A
<br /> 3. Ballast Factor: Normal (0.88). I. Burn-in all fluorescent lamps controlled by wallbox dimmers or 8. Install labels complying with TIA/EIA-606 using coded PROTOTYPICAL STARBUCKS STORE(WHICH IS
<br /> 4. Total Harmonic Distortion: Less than 10 percent. dimming systems for a minimum of 100 hours prior to connecting to identifiers: SUBJECT TO CHANGE AT ANYTIME AND DO
<br /> 5. Sound Level Rating: Class A. dimmer. a. Cables: Color coded labels on each end. )
<br /> 6. Starting: Programmed rapid start. 3.02 CLOSEOUT b. Outlets: Label each jack on its cover plate with a NOT REFLECT ACTUAL SITE CONDITIONS.
<br /> 7. Accessories: Provide disconnecting means that opens all A. Replace any lamps and ballasts that expire before the Owner's unique numerical identifier as to its type and NEITHER PARTY SHALL HAVE ANY OBLIGATION
<br /> supply conductors including the neutral conductor. acceptance of the project. function. NOR LIABILITY TO THE OTHER(EXCEPT STATED
<br /> C. Electronic Compact Fluorescent Ballasts: B. Aim and adjust all luminaires to provide illumination levels, C. Patch Panels: Label each jack with a unique numerical ABOVE)UNTIL A WRITTEN AGREEMENT IS
<br /> 1. Description: Osram Sylvania Quicktronic Professional DULUX focusing, and distribution patterns to the Owner's satisfaction. identifier as to its type and function. FULLY EXECUTED BY BOTH PARTIES.
<br /> series or equal. END OF SECTION d. Patch Cords: Label with jack identifier corresponding
<br /> 2. Voltage: Universal (120 through 277 volts). to initial installation.
<br /> 3. Ballast Factor: Greater than 0.95. SECTION 271005 - TELEPHONE AND DATA SYSTEMS 3.05 INSTALLATION OF CROSS-CONNECTION EQUIPMENT
<br /> 4. Total Harmonic Distortion: Less than 10 percent. A. Only if required pursuant to meeting with the Owner: ARCHITECT OF RECORD
<br /> 5. Sound Level Rating: Class A. PART 1 GENERAL 1. Install connector blocks at backboards as directed by the mcg architecture
<br /> 6. Starting: Programmed rapid start unless indicated otherwise. 1.01 PREPARATION Owner.
<br /> D. Electronic Metal Halide Ballasts: A. Coordinate all demarcation locations with the serving utility and/or 2. Install patch panels in equipment racks as directed by the o
<br /> 1. Provide all metal halide luminaires rated at 100 watts or less the Landlord. Owner. y '�
<br /> with electronic ballast with matched ANSI code to the B. Hold meeting with the Owner prior to commencing work. 3. Install labels complying with TIA/EIA-606 using coded v
<br /> associated lamp. 1. Determine Scope of Work and Division of Responsibility. identifiers: ,_ E5
<br /> 2. Description: Osram Sylvania Quicktronic Metal Halide 2. Determine quantities of phone drops and data drops are a. Patch Panels: Label each jack with a unique numerical
<br /> cc
<br /> Professional series or equal. required at each outlet box. identifier as to its type and function.
<br /> 3. Voltage: Universal (120 through 277 volts). 3. Confirm all cabling, termination, cross-connection equipment, b. Patch Cords: Label with jack identifier corresponding
<br /> 4. Ballast Factor: 1.0. enclosure, and jack requirements. to initial installation. 111 Pacifica,Suite 280,Irvine,CA 92618
<br /> 5. Power Factor: Greater than 0.98. END OF SECTION P:949.553.1117 F:949.474.7056
<br /> 6. Total Harmonic Distortion: Less than 10 percent. PART 2 PRODUCTS
<br /> 7. Sound Level Rating: Class A. 2.01 ENCLOSURES
<br /> E. Magnetic Metal Halide Ballasts: A. Backboards: Provide 3/4 inch thick UL-labeled, fire-retardant, ENGINEER STAMP
<br /> 1. Permitted only for metal halide luminaires rated greater than interior grade plywood; size as indicated on the Drawings. QRpFESS/ON
<br /> 100 watts. B. Equipment Racks: Only if required pursuant to meeting with the p q�
<br /> 2. Description: Osram Sylvania Metalarc series or equal with Owner: �`� y ROY SCy F•
<br /> matched ANSI code to the associated lamp. 1. Wall-Mounted Racks: Chatsworth Products Standard Swing Gate
<br /> 3. Voltage: Multi-tap (120, 208, 240, 277, and 480 volts). series; 19 inches wide, depth as required for installed <v
<br /> 4. Circuit Type: Constant Wattage Autotransformer (CWA) components, and height as required for installed components m
<br /> 5. Power Factor: Greater than 0.90. plus 50 percent. w No. E14631 m
<br /> F. Low Voltage Transformers: 2. Floor-Mounted Racks: Chatsworth Products 50120 QuadraRack
<br /> 1. Description: Electronic or magnetic low voltage transformer series with vertical and horizontal cable management, top and
<br /> as required for and compatible with the associated bottom cable troughs, and grounding lug; 19 inches wide, 29 TRI
<br /> �P
<br /> luminaires. inches deep, and height as required for installed components q
<br /> 2. Primary Voltage: Coordinate with the circuit(s) serving the plus 50 percent. TF OF CALXFa
<br /> luminaires. 2.02 OUTLET BOXES
<br /> 3. Secondary Voltage: As required for the associated luminaires. A. Wall: 4-square by 2-1/8 inch deep outlet box with single gang mud
<br /> 4. Power Rating: As required for the total wattage of the ring and cover plate unless indicated otherwise or otherwise Date. 01/24/2020
<br /> luminaires served plus a minimum of 25 percent. required.
<br /> G. LED Drivers: As required for and compatible with the associated LED B. Floor: As indicated on the Drawings or within Section 260537 unless
<br /> module. indicated otherwise or otherwise required.
<br /> 2.03 DIMMING BALLASTS AND DRIVERS C. Wall Plates:
<br /> A. All Dimming Ballasts and Drivers: 1. Provide standard-size nylon blank wall plates unless indicated
<br /> 1. Provide appropriate dimming ballasts/drivers in all otherwise; color as selected by the Architect. Mid-size or
<br /> fluorescent and LED luminaires controlled by wallbox dimmer jumbo wall plates are not permitted.
<br /> switches or dimming systems whether or not specifically 2. When cabling is to be provided by this Contractor, provide
<br /> indicated within the specified luminaire's catalog number. standard-size nylon modular keystone jack cover plates
<br /> 2. All dimming ballasts/drivers shall be compatible with compatible with the associated modular keystone jacks and with
<br /> associated wallbox dimmer switches or centralized dimming appropriate number of jacks unless indicated otherwise; color
<br /> system control units. as selected by the Architect.
<br /> 3. Dimming Range: 100 percent to 5 percent. 2.03 PATHWAYS (0
<br /> 4. Voltage: Universal (120 through 277 volts). A. All Pathways: O
<br /> 5. Power Factor: Greater than 0.95. 1. See Section 260534 for permitted conduit types.
<br /> 6. Total Harmonic Distortion: Less than 10 percent. 2. Provide pullstring in each conduit. N
<br /> 7. Sound Level Rating: Class A. B. Service Entrance: Conduit with extended radius sweeps; size as
<br /> B. Fluorescent Dimming Ballasts: indicated or otherwise required.
<br /> 1. Three-Wire Linear Fluorescent: Lutron Hi-Lume 3D or equal; C. Branch Wiring: Provide 3/4 inch minimum conduit from all outlet
<br /> 1.0 ballast factor. boxes to accessible ceiling space unless indicated otherwise. W wQ
<br /> 2. Three-Wire Compact Fluorescent: Lutron EcoSystem series or 2.04 COPPER CABLES, PLUGS, AND JACKS: Only if required pursuant to meeting
<br /> ballast factor greater than or equal to 0.95. with the Owner: Cl)U)
<br /> equal; g q U)
<br /> 3. 0-10 Volt: Advance Mark 7 series or equal; ballast factor A. Data: w
<br /> greater than or equal to 0.95. 1. All Data Cabling: Unshielded twisted pair (UTP) Category 5e W 1[11� Q Z
<br /> C. LED Dimming Drivers: Advance Xitanium series or equal. unless indicated otherwise or otherwise required. Q p = O
<br /> 2.04 EMERGENCY POWER SUPPLIES 2. Backbone (Riser) Cabling: Type CMR when installed in conduit Q
<br /> A. Provide appropriate emergency battery in all fluorescent and LED and Type CMP when not installed in conduit; gray jacket unless Z Q
<br /> luminaires indicated as emergency fixtures whether or not indicated otherwise or otherwise required. U U U
<br /> specifically indicated within the specified luminaire's catalog 3. Horizontal Cabling: Type CM when installed in conduit and
<br /> number. Type CMP when not installed in conduit; blue jacket unless w 06 W
<br /> 1. Battery Type: Sealed nickel calcium (NiCad) with 7-year, indicated otherwise or otherwise required. O
<br /> minimum, life expectancy. 4. Plugs: Category 5e UTP non-keyed 8-wire modular plugs unless O O 0
<br /> 2. Illumination Time: 90 minutes minimum. indicated otherwise or otherwise required. 0� LO 0� (0
<br /> 3. Voltage: Universal (120 through 277 volts). 5. Jacks: Category 5e UTP non-keyed 8-wire RJ45 modular keystone U)
<br /> 4. Test Switch: Two-wire with LED indicator. jack unless indicated otherwise or otherwise required; color
<br /> 5. Lamp Operation: Two-lamp operation for luminaries equipped as selected by the Owner.
<br /> with more than one lamp. B. Telephone: STORE #: TBD
<br /> 6. Minimum Initial Illumination Rating: 1. All Telephone Cabling: Unshielded twisted pair (UTP) Category
<br /> a. Linear Fluorescent: 1400 lumens per luminaire. 3 unless indicated otherwise or otherwise required. PROJECT#: 85426-001
<br /> b. Compact Fluorescent: 1100 lumens per luminaire. 2. Horizontal Cabling: Type CM when installed in conduit and
<br /> C. Integrated LED 1000 Lumens and Less: 10 watt output. Type CMP when not installed in conduit; blue jacket unless CASEWORK CONCEPT: CORE
<br /> d. Integrated LED Greater than 1000 Lumens: 20 watt indicated otherwise or otherwise required.
<br /> output. 3. Plugs: Category 3 UTP non-keyed 8-wire modular plugs unless ISSUE DATE:
<br /> 2.05 LAMPS indicated otherwise or otherwise required. PROGRAM MANAGER:
<br /> A. All Lamps: 4. Jacks: Category 3 UTP non-keyed 8-wire RJ45 modular keystone STORE DESIGNER: S. BLEVINS
<br /> 1. Provide all incandescent lamps from the same manufacturer. jack unless indicated otherwise or otherwise required; color
<br /> 2. Provide all fluorescent lamps from the same manufacturer. as selected by the Owner. LEED®AP: N/A
<br /> 3. Provide all metal halide lamps from the same manufacturer. 2.05 CROSS-CONNECTION EQUIPMENT: Only if required pursuant to meeting with the
<br /> B. Incandescent: As indicated on the Drawings. Owner: CHECKED BY:
<br /> C. Linear T8 Fluorescent: Osram Sylvania OCTRON series extended life A. Connector Blocks for Category 3 Cabling: Type 66 insulation MCG PROJECT#: 19236
<br /> Ecologic lamps unless indicated otherwise. displacement connectors unless indicated otherwise or otherwise
<br /> D. Linear T5 Fluorescent: Osram Sylvania PENTRON series extended life required with capacity sufficient for cables to be terminated plus MCG PROD. MANAGER: C. LEE
<br /> Ecologic lamps unless indicated otherwise. 25 percent spare. MCG PROJ. SPECIALIST:
<br /> E. Compact Fluorescent: Osram Sylvania DULUX series Ecologic lamps B. Connector Blocks for Category 5e Cabling: Type 110 insulation
<br /> unless indicated otherwise. displacement connectors unless indicated otherwise or otherwise
<br /> F. Metal Halide: As required for the specified luminaire with matched required with capacity sufficient for cables to be terminated plus
<br /> ANSI code to the associated ballast. 25 percent spare. Revision Schedule
<br /> G. LED: As indicated on the Drawings. C. Patch Panels for Copper Cabling: Panduit DP5e series UTP patch
<br /> 2.06 ACCESSORIES panel unless indicated otherwise or otherwise required with quantity Rev Date By Description
<br /> A. Provide all supplementary items, appurtenances, and devices of ports sufficient for cables to be terminated plus 25 percent
<br /> incidental to or necessary for a sound, secure, and complete spare.
<br /> installation including, but not limited to: D. Patch Cords: Provide one Category 5e patch cord for each pair of
<br /> 1. Dimming ballasts for fluorescent and LED luminaires that are patch panel ports.
<br /> served by wallbox dimmer switches or dimming systems.
<br /> 2. Emergency power supplies for fluorescent and LED luminaires PART 3 EXECUTION
<br /> indicated as emergency fixtures. 3.01 INSTALLATION OF ENCLOSURES
<br /> 3. Multiple ballasts for fluorescent luminaires where indicated A. Backboards: Install at locations indicated on the Drawings.
<br /> to have multi-level switching. B. If required pursuant to meeting with the Owner: SHEET TITLE:
<br /> 4. All trim rings, extensions, stems, canopies, cords, pendant 1. Wall-Mounted Racks: Install to plywood backboard at locations
<br /> feeds, connectors, bar hangers, fittings, hold-down clips, directed by the Owner. ELECTRICAL
<br /> alignment clips/joiners, etc. necessary to mount the 2. Floor-Mounted Racks: Permanently anchor to floor in
<br /> luminaires in a proper and approved method. accordance with manufacturer's recommendations at locations SPECIFICATIONS
<br /> 5. All necessary low-voltage transformers, connectors, mounting directed by the Owner, connect adjacent racks together, and
<br /> hardware, etc. for a complete low-voltage lighting system. remove interior side panels. SCALE:AS SHOWN
<br /> 6. All necessary connectors, feeds, end caps, pendants, mounting 3.02 INSTALLATION OF OUTLET BOXES Schnackel
<br /> hardware, fittings, etc. for a complete track lighting A. Install in compliance with Section 260537.
<br /> system. B. Mounting Heights: See Section 262726. NewYork®Omaha®Los Angela mS Ind® SHEET NUMBER:
<br /> 7. Chain hangers for all suspended luminaires in unfinished
<br /> areas. 800-581-0963 wwwachnackeLoom
<br /> 8. Drywall frames for all linear fluorescent luminaires that are 80 South Lake Avenue, Suite 640 Pasadena, CA 91101 E-0003
<br /> recessed into drywall ceilings.
<br /> SE JOW: 190728