Laserfiche WebLink
EXISTING PANEL- 99A" EXISTING PANEL- 9999 GENERAL ONE-LINE DIAGRAM NOTES <br /> FED FROM: EXISTING SWITCHBOARD 'MSB' MOUNTING: FLUSH MOUNTED FED FROM: PANEL "A" MOUNTING: FLUSH MOUNTED <br /> VOLTAGE: 120/208V, 3 PHASE, 4 WIRE ENCLOSURE: NEMA 1 VOLTAGE: 120/208V, 3 PHASE, 4 WIRE ENCLOSURE: NEMA 1 A. ANY EXISTING CONDITIONS INDICATED IN THIS SET OF DRAWINGS ARE BASED ON -- <br /> BUS MATERIAL: EXISTING FAULT CURRENT: EXISTING BUS MATERIAL: EXISTING FAULT CURRENT: EXISTING 14WBUS LOAD: 335 AMPS AIC/SCCR RATING: MATCH EXISTING BUS LOAD: 114 AMPS AIC/SCCR RATING: MATCH EXISTING INFORMATION PROVIDED BY OTHERS AND POSSIBLE LIMITED FIELD VERIFICATION. <br /> THE CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD CONDITIONS AT NOT <br /> BUS RATING: 400 AMPS OPTIONS*: BONDED EQUIPMENT GROUND BAR BUS RATING: 400 AMPS OPTIONS*: BONDED EQUIPMENT GROUND BAR <br /> ADDITIONAL EXPENSE TO THE OWNER. <br /> MAIN: 400/3 MAIN BREAKER MAIN: MAIN LUG ONLY B. THE CONTRACTOR SHALL VISIT THE PROJECT SITE, REVIEW EXISTING CONDITIONS <br /> LOAD (VA) LOAD (VA) LOAD (VA) LOAD (VA) AGAINST THE CONTRACT DOCUMENTS,AND FAMILIARIZE HIMSELF WITH THE WORK <br /> PRIOR TO BIDDING AND START OF THE WORK. BY SIGNING THE CONTRACT,THE <br /> NOTES CKT. LOAD DESCRIPTION A B C BREAKER BREAKER A B C LOAD DESCRIPTION CKT. NOTES NOTES CKT. LOAD DESCRIPTION A B C BREAKER BREAKER A B C LOAD DESCRIPTION CKT. NOTES CONTRACTOR ACKNOWLEDGES THE SITE VISIT HAS BEEN COMPLETED AND THE <br /> 1 HC-1 4000 50/3 20/1 1780 U/C REFRIG, INSTANT HOT 2 GFCI HLO 1 INVERTER 300 20/1 20/1 800 LTG - EXTERIOR WALL 2 LCP EXISTING CONDITIONS ARE ACCEPTED. <br /> 3 ----- 4000 --- 50/2 3500 ESPRESSO 4 GFCI LCP 3 TRACK LTG 400 20/1 20/1 800 LTG - EXTERIOR PARKING 4 LCP C. THE CONTRACTOR IS RESPONSIBLE FOR DEMOLITION OF EXISTING EQUIPMENT, <br /> DEVICES,AND LUMINARIES AS INDICATED AND/OR AS REQUIRED TO ALLOW FOR ©2017 STARBUCKS COFFEE COMPANY <br /> 5 ----- 4000 --- --- 3500 ----- 6 LCP 5 GENERAL LTG / EF-1 1515 20/1 20/1 800 LTG - EXTERIOR POLES 6 LCP INSTALLATION AND CONSTRUCTION OF THE NEW WORK. REMOVE ALL EQUIPMENT, <br /> 7 HC-2 4000 50/3 15/2 874 FOOD CASE 8 HPL 7 CONVENIENCE RECEPTACLE 180 20/1 20/1 100 EXIT SIGN / LTS 8 DEVICES, LUMINAIRES, CONDUITS, SUPPORTS, HANGERS, ETC.THAT ARE NOT <br /> 9 ----- 4000 --- --- 874 ----- 10 9 SHOW WINDOW REC. 720 20/1 20/1 1500 BUILDING SIGNAGE 10 LCP SHOWN AND ARE REQUIRED TO BE REMOVED IN ORDER TO COMPLETE THE NEW STARBUCKS COFFEE <br /> WORK. <br /> 11 ----- 4000 --- 20/1 1200 REACH IN REFRIG 12 GFCI LCP 11 BUILDING SIGNAGE 900 20/1 20/1 200 SITE SIGNAGE 12 LCP D. RECESSED BOXES AND CONDUITS CONCEALED WITHIN WALLS OR FLOORS THAT ARE COMPANY <br /> 13 HC-3 4000 50/3 20/1 700 EF-1 14 13 CONVENIENCE RECEPTACLE 360 20/1 20/1 852 MUSIC PLAYER/AMPLIFIER 14 TO REMAIN ARE PERMITTED TO BE ABANDONED IN PLACE ONLY IF THE OPENINGS <br /> ARE PATCHED AND THE CONDUCTORS ARE REMOVED. 2401 UTAH AVENUE SOUTH <br /> 15 --- 4000 --- 20/1 1800 BOOSTER PUMP 16 15 PC/PRINTER 821 20/1 20/1 360 PARTNER DESK 16 E. THE OWNER SHALL HAVE FIRST SALVAGE RIGHT ON ALL DEMOLISHED EQUIPMENT, SEATTLE,WASHINGTON 98134 <br /> 17 --- 4000 --- 20/1 200 ROOF RECEPT 18 17 MONEY COUNTER/FUTURE US 720 20/1 20/1 1500 MICROWAVE 18 DEVICES, LUMINAIRES,AND MATERIALS.THE CONTRACTOR SHALL DISPOSE OF ALL <br /> DEMOLISHED EQUIPMENT, DEVICES, LUMINAIRES,AND MATERIALS THE OWNER (206}318-1575 <br /> 19 FLY FAN POWER 1000 29/1 20/1 1320 REACH IN FREEZER 20 GFCI 19 UPS 1500 20/1 20/1 500 WATER SOFTENER 20 REJECTS. <br /> 21 SPARE 20/1 20/1 1320 REACH IN FREEZER 22 GFCI 21 MONEY COUNTER/FUTURE US 720 20/1 20/1 840 HWH-1 22 F. MAINTAIN CONTINUITY OF EXISTING CIRCUITS AS REQUIRED TO PROVIDE POWER THESE DRAWINGS AND SPECIFICATIONS ARE <br /> GFCI 23 COMPUTER/POS 480 20/1 30/2 2714 ICE MACHINE 24 HPL LCP 23 DT DIRECTIONAL SIGN 600 20/1 20/1 SPARE 24 TO REMAINING EQUIPMENT, DEVICES,AND LUMINAIRES THAT ARE NOT BEING CONFIDENTIAL AND SHALL REMAIN THE SOLE <br /> REMOVED. PROPERTY OF STARBUCKS CORPORATION <br /> GFCI 25 ESPRESSO 3500 50/2 --- 2714 ----- 26 LCP 25 DT PRE MENU 600 20/1 20/1 SPARE 26 G. ALL EXISTING FEEDER SIZES, OVERCURRENT PROTECTION DEVICES, ETC. NOTED <br /> 27 ----- 3500 --- 20/1 1760 SCALE/GRINDER 28 GFCI LCP 27 DT MENU 600 20/1 20/1 1200 CAFE AIR CURTAIN 28 ON THE ONE LINE DIAGRAM AND ALL EXISTING PANEL RATINGS INDICATED ON THE WHICH IS THE OWNER OF THE COPYRIGHT IN <br /> PANEL SCHEDULES ARE THE MINIMUM SIZES REQUIRED.THE ELECTRICAL THIS WORK. THEY SHALL NOT BE <br /> GFCI 29 U/C REFRIG, INSTANT HOT 1780 20/1 50/2 4170 DUAL SOFT HEATER BREWER 30 GFCI LCP 29 DT SPEAKER POST 600 20/1 20/1 600 WORKRM AIR CURTAIN 30 CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO BID. IF THE REPRODUCED(IN WHOLE OR IN PART), SHARED <br /> GFCI 31 COMPUTER/POS 960 20/1 --- 4170 ----- 32 GFCI 31 OVEN 3120 30/2 20/1 1300 COMMUNITY TABLE 32 EXISTING INSTALLATION DOES NOT MEET THE MINIMUM CRITERIA NOTED ON THE WITH THIRD PARTIES OR USED IN ANY MANNER <br /> HPL 33 WAREWASHER 3172 40/2 20 1 720 BREWER HEATER 34 GFCI 33 ----- 3120 --- 20 1 720 FUTURE MENU BOARDS 34 GFCI ONE LINE DIAGRAM AND WITHIN THE PANEL SCHEDULESTHE ELECTRICAL ON OTHER PROJECTS OR EXTENSIONS TO THIS <br /> / / / CONTRACTOR SHALL MAKE ALL NECESSARY MODIFICATI,ONS TO BRING THE EXISTING PROJECT WITHOUT THE PRIOR WRITTEN <br /> 35 ----- 3172 --- 20/1 300 BUILDING SIGNAGE 36 LCP GFCI 35 OVEN 3120 30/2 15/1 304 P-1 36 LCP INSTALLATION INTO COMPLIANCE WITH THE MINIMUM SIZES AND/OR RATINES CONSENT OF STARBUCKS CORPORATION. <br /> GFCI 37 HOT WATER DISPENSER 1300 20/1 20/1 180 CONVENIENCE RECEPTACLE 38 37 ----- 3120 --- 20/1 SPARE 38 INDICATED THEREIN AND INCLUDE THE COST OF ANY REQURIED MODIFICATIONS IN THESE DRAWINGS AND SPECIFICATIONS ARE <br /> THE INTIAL BID. POST-BID ADDITIONAL COSTS RESULTING FROM AN EXISTING <br /> GFCI 39 BLENDER 1800 20/1 20/1 180 SHOW WINDOW REC. 40 39 SPARE 20/1 20/1 SPARE 40 INSTALLATION THAT DOES NOT MEET THE MINIMUM CRITERIA INDICATED WILL NOT INTENDED TO EXPRESS DESIGN INTENT FOR A <br /> GFCI 41 RINSE SENSOR 360 20/1 20/1 1440 U/C REFRIG 42 GFCI 41 SPARE 20/1 20/1 SPARE 42 BE PERMITTED. IF THE EXISTING INSTALLATION MEETS OR EXCEEDS THE MINIMUM PROTOTYPICAL STARBUCKS STORE(WHICH IS <br /> CRITERIA INDICATED, MODIFICATIONS OF THE EXISTING INSTALLATION ARE NOT SUBJECT TO CHANGE AT ANYTIME)AND DO <br /> GFCI 43 NITRO DISPENSER 1440 20/1 20/1 720 DT TIMER SYSTEM 44 GFCI 43 SPARE 20/1 20/1 SPARE 44 REQURIRED. NOT REFLECT ACTUAL SITE CONDITIONS. <br /> GFCI 45 ORDER MONITOR 360 20/1 20/1 360 DT COMM. SYSTEM 46 GFCI 45 SPARE 20/1 20/1 SPARE 46 NEITHER PARTY SHALL HAVE ANY OBLIGATION <br /> GFCI 47 DT EXPEDITOR 360 20/1 20/1 960 U/C REFRIG 48 GFCI 47 SPARE 20/1 20/1 SPARE 48 NOR LIABILITY TO THE OTHER(EXCEPT STATED <br /> GFCI 49 FUTURE USE 360 20/1 20/1 1800 BLENDER 50 GFCI 49 SPARE 20/1 20/1 SPARE 50 ABOVE)UNTIL A WRITTEN AGREEMENT IS <br /> GFCI 51 U/C REFRIG 480 20/1 20/1 1020 REFRIG REACH-IN 1 DOOR 52 GFCI 51 SPARE 20/1 20/1 SPARE 52 FULLY EXECUTED BY BOTH PARTIES. <br /> GFCI 53 COMPUTER/POS 1560 20/1 20/1 1020 REFRIG REACH-IN 1 DOOR 54 GFCI 53 SPARE 20/1 20/1 SPARE 54 ALL BRANCH CIRCUITS HAVE BEEN DESIGNED SUCH THAT ONLY ONE LOAD <br /> FEED—THROUGH LUGS TYPE OUTLINED IN CALIFORNIA ENERGY CODE TABLE 130.5—B IS SERVED BY ARCHITECT OF RECORD <br /> 13657 FTL SUBFEED PANEL 'B' NOTES: ANY ONE BRANCH CIRCUIT, ALLOWING FUTURE MEASUREMENT DEVICES TO mcg architecture <br /> 12906 FTL ------ SEE SPECIFICATIONS FOR OTHER OPTIONS REQUIRED BUT NOT NECESSARILY NOTED HERE BE INSTALLED ON EACH BRANCH CIRCUIT, MEETING THE REQUIREMENTS OF <br /> GFCI CIRCUIT BREAKER SHALL BE GROUND—FAULT CIRCUIT INTERRUPTING (GFCI) TYPE <br /> 12113 FTL ------ HLO CIRCUIT BREAKER SHALL BE EQUIPPED WITH HANDLE LOCK—ON DEVICE (SQUARE D #HLO1 OR EQUAL) CALIFORNIA ENERGY CODE SECTION 130.5(b). THIS METHOD OF LOAD <br /> E <br /> SEPARATION HAS BEEN APPROVED BY THE CALIFORNIA ENERGY COMMISSION <br /> Cz <br /> NOTES: SEE SPECIFICATIONS FOR OTHER OPTIONS REQUIRED BUT NOT NECESSARILY NOTED HERE <br /> PER EXAMPLE 8-8 OF THE 2019 NONRESIDENTIAL COMPLIANCE MANUAL. <br /> LO D ANA IS F R PANEL >B (INCLUDING SUBF ) � <br /> GFCI CIRCUIT BREAKER SHALL BE GROUND-FAULT CIRCUIT INTERRUPTING (GFCI) TYPE <br /> 111 Pacifica,Suite 280,Irvine,CA 92618 <br /> HPL CIRCUIT BREAKER SHALL HAVE PERMANENTLY-INSTALLED HANDLE PADLOCK ATTACHMENT TO LOCK BREAKER IN OPEN DEMAND PHASE A (VA) PHASE B (VA) PHASE C (VA) TOTAL (VA) P:949.553.1117 F:949.474.7056 <br /> POSITION (SQUARE D #QO*PAF OR EQUAL) LOAD DESCRIPTION FACTOR CONNECT. DEMAND CONNECT. DEMAND CONNECT. DEMAND CONNECT. DEMAND <br /> LCP CIRCUIT SHALL BE ROUTED THROUGH LUTRON CONTROL PANEL FOR TIME BASED CONTROL. REFER TO LUTRON CONTROL <br /> DIAGRAMS FOR MORE INFORMA110N. LIGHTING: 125% 1200 1500 1200 1500 2315 2894 4715 5894 ENGINEER STAMP QRCFESS/ON <br /> RECEPTACLE: 100% 2692 2692 2621 2621 720 720 6033 6033 ROY Scyti <br /> q� <br /> OTHER CONTINUOUS: 125% 2100 2625 2820 3525 2300 2875 7220 9025 <br /> LOAD ANALYSIS FOR PANEL "A" (INCLUDING SUBFEEDS) OTHER NONCONTINUOUS: 100% 500 500 0 0 1500 1500 2000 2000 9m z <br /> DEMAND PHASE A (VA) PHASE B (VA) PHASE C (VA) TOTAL (VA) WATER HEATING: N <br /> 100% 0 0 840 840 0 0 840 840 ca c� m <br /> w o. E14631 � m <br /> LOAD DESCRIPTION FACTOR CONNECT. DEMAND CONNECT. DEMAND CONNECT. DEMAND CONNECT. DEMAND KITCHEN: 100% 6240 6240 3120 3120 3120 3120 12480 12480 <br /> LIGHTING: 125% 1200 1500 1200 1500 2315 2894 4715 5894 MOTOR: 100% 0 0 1200 1200 904 904 2104 2104 <br /> ADD 25% OF LARGEST MOTOR: 100% 100 100 100 100 100 100 300 300 <br /> RECEPTACLE: 100% 2872 2872 2801 2801 920 920 6593 6593 9TF �FCTR ICP <br /> OTHER CONTINUOUS: 125% 2100 2625 2820 3525 2600 3250 7520 9400 TOTAL: 12832 13657 11901 12906 10959 12113 35692 38676 OF CAFE <br /> OTHER NONCONTINUOUS: 100% 1460 1460 0 0 3540 3540 5000 5000 EQUIVALENT AMPS: 107 114 100 108 92 101 100 108 <br /> WATER HEATING: 100% 0 0 840 840 0 0 840 840 PHASE BALANCE: 5.93% 0.11% -6.04% j Date. 01/24/2020 <br /> KITCHEN: 65% 26218 17042 21986 14291 23796 15468 72000 46800 <br /> MOTOR: 100% 13700 13700 15000 15000 12904 12904 41604 41604 <br /> ADD 25% OF LARGEST MOTOR: 100% 1000 1000 1000 1000 1000 1000 3000 3000 <br /> TOTAL: 48550 40199 45647 38957 47075 39976 141272 119131 <br /> EQUIVALENT AMPS: 405 335 381 325 393 334 393 331 <br /> PHASE BALANCE: 1.23% -1.90% 0.67% <br /> EXISTING PAD MOUNT Q 0 <br /> TRANSFORMER N <br /> EXISTING LO <br /> TRANSFORMER <br /> PAD EXISTING MAIN SWITCHBOARD "MSB", 208/120 VOLT, 3 PHASE, w <br /> 4 WIRE, 600 AMP BUS, BRACED FOR 42KAIC <br /> PRIMARYNG -RY GPS DISTRIBUTION SECTION C/) <br /> CONDUIT w <br /> CTs � � 0 <_ z <br /> EXISTING 600/3 Q = O <br /> EXISTING PRIMARY Z Q U <br /> UTILITY FEEDERS FEEDERS METER M FOR FUTURE SOLAR r , <br /> v • <br /> SOCKET � 400/3 3: � 1 <br /> W °6 W O <br /> EXISTING G.E.C. 0 0 <br /> 4 — #500kcrn il, <br /> #1 GROUND U) <br /> IN 4" <br /> CONDUIT <br /> STORE #: TBD <br /> ALL EQUIPMENT EXISTING BY LANDLORD, SHOWN FOR REFERENCE ONLY. PROJECT#: 85426-001 <br /> PANEL <br /> "A" CASEWORK CONCEPT: CORE <br /> ISSUE DATE: <br /> FTL <br /> PROGRAM MANAGER: <br /> 4 - #500kcrn iI, STORE DESIGNER: S. BLEVINS <br /> #1 GROUND <br /> IN 4" LEED®AP: N/A <br /> CONDUIT CHECKED BY: <br /> FTL MCG PROJECT#: 19236 <br /> PANEL MCG PROJ. MANAGER: C. LEE <br /> MCG PROJ. SPECIALIST: <br /> Revision Schedule <br /> D1ONE-LINE DIAGRAM Rev Date By Description <br /> Scale:NOT TO SCALE <br /> SHEET TITLE: <br /> PANEL SCHEDULES AND <br /> ONE-LINE DIAGRAM <br /> LEGEND hn k l SCALE:AS SHOWN <br /> ����� Sc ac e <br /> EX/ST/NG NewY�a�heaLw�ksa H ,du® SHEET NUMBER: <br /> NEW WORK 800-581-0963 www uhnackeLoom <br /> NEW TO EX/STING CONNECT/ON 80 South Lake Avenue, Suite 640 Pasadena, CA 91101 E-6001 <br /> SE JOW: 190728 <br />