Laserfiche WebLink
190617 -698 <br /> EMERGENCY GENERATOR UNBURIED FUEL PIPING VISUAL INSPECTION § 25281 . 5 <br /> Y N INA <br /> Unburied fuel piping , fittings , and containment are free of water, leaks , and hazardous substance , ❑X 131 ❑ <br /> Sensors are capable of detecting a leak at the earliest possible opportunity . ❑X ❑ I ❑ <br /> Comments : <br /> On July 12 2019 there was a H - 1 Annular space sensor out alarm , H -2 Fill Sump Sensor out alarm , and <br /> H -5 Fuel Polisher sensor out alarm , ON 7/ 15/ 19 Atinesh Chandra responded to the alarm , he checked all <br /> sensors for tank and no sensors were out and reset the veeder root , the apparent cause for the alarms <br /> werre a power failure on 7/ 11 / 19 , on 7/23/ 19 1 went a head and inspected the piping sump and Fill sump <br /> and also the fuel polisher and all sensors are in the proper location and all sumps are clean and dry and <br /> all functions are currently normal on the veeder root . <br /> i <br /> i <br />