Laserfiche WebLink
March 23, 2021 Lab ID : STK2133006 <br /> San Joaquin Co.Environmental Health Dep Customer : 3-17919 <br /> Quality Control -Inorganic <br /> Constituent Method Date/ID Type Units Conc. Q('Data DQO Note <br /> Wet Chem <br /> Nitrate 300.0 (VI2141617-001) MSD mg/L 40.00 34.4% 85-119 435 <br /> MSRPD mg/L 10.00 15.6% <19 <br /> 300.0 03/04/21:203298MCA ICB mg/L 0.000 0.5 <br /> ICV mg/L 20.00 103% 90-110 <br /> CCB mg/L 0.078 0.5 <br /> CCV m 20.00 104% 90-110 <br /> Nitrate+Nitrite as N 300.0 03/04/21:202410MCA Blank mg/L ND <0.1 <br /> Nitrate Nitrogen 300.0 03/04/21:202410MCA Blank m9fL ND <0.1 <br /> Nitrite 300.0 03/04/21:202410MCA Blank mg/L ND <0.5 <br /> LCS mg/L 15.00 103% 90-110 <br /> MS mg/L 30.00 104% 74-126 <br /> (CH 2171418-001) MSD mg/L 30.00 102% 74-126 <br /> MSRPD mg/L 10.00 2.3% <20 <br /> MS mg/L 30.00 103% 74-126 <br /> (VI 2141617-001) MSD mg/L 30.00 103% 74-126 <br /> MSRPD m--/l. 10.00 0.05% 520 <br /> 300.0 03/04/21:203298MCA ICB mg/L 0.000 0.5 <br /> ICV mg/L 15.00 103% 90-110 <br /> CCB mg/L 0.000 0.5 <br /> CCV mg/L 15.00 104% 90-110 <br /> Nitrite Nitrogen 300.0 03/04/21:202410MCA Blank mgfL ND <0.2 <br /> Sulfate 300.0 03/04/21:202410MCA Blank mg/L ND <0.5 <br /> LCS mg/L 50.00 104% 90-110 <br /> MS mg/L 100.0 104% 82-124 <br /> (CH 2171418-001) MSD mg/L 100.0 102% 82-124 <br /> MSRPD mg/L 10.00 1.6% 523 <br /> MS mg/L 100.0 94.6% 82-124 <br /> (VI 2141617-001) MSD mg/L 100.0 95.1% 82-124 <br /> MSRPD mg/L 10.00 0.3% 523 <br /> 300.0 03/04/21:203298MCA ICB mg/L 0.219 0.5 <br /> ICV mg/L 50.00 102% 90-110 <br /> CCB mg/L 0.408 0.5 <br /> CCV mg/L 50.00 106% 90-110 <br /> BAS 5540C 03/04/21:203395jba CCB mg/L -0.0393 0.25 <br /> CCV mg/L 1.000 94.1% 90-110 <br /> CCB mg/L -0.0393 0.25 <br /> CCV I m I- 1.000 93.6% 1 90-110 <br /> BAS Extraction 5540C 03/04/21:202526jba Blank mg/L ND <0.1 <br /> LCS mg/L 0.5000 93.6% 86-114 <br /> BS mg/L 0.5000 90.5% 86-114 <br /> BSD mg/L 0.5000 91.3% 86-114 <br /> BSRPD mg/L 0.5000 0.0042 <0.1 <br /> Definition <br /> ICV :Initial Calibration Verification-Analyzed to verify the instrument calibration is within criteria. <br /> ICB :Initial Calibration Blank-Analyzed to verify the instrument baseline is within criteria. <br /> CCV :Continuing Calibration Verification-Analyzed to verify the instrument calibration is within criteria. <br /> CCB :Continuing Calibration Blank-Analyzed to verify the instrument baseline is within criteria. <br /> Blank :Method Blank-Prepared to verify that the preparation process is not contributing contamination to the samples. <br /> LCS :Laboratory Control Standard/Sample-Prepared to verify that the preparation process is not affecting analyte recovery. <br /> MS Matrix Spikes-A random sample is spiked with a known amount of analyte.The recoveries are an indication of how that sample <br /> matrix affects analyte recovery. <br /> MSD :Matrix Spike Duplicate of MS/MSD pair-A random sample duplicate is spiked with a known amount of analyte.The recoveries <br /> are an indication of how that sample matrix affects analyte recovery. <br /> BS :Blank Spikes-A blank is spiked with a known amount of analyte.It is prepared to verify that the preparation process is not <br /> affecting analyte recovery. <br /> Page 8 of 9 <br />