Laserfiche WebLink
March 23, 2021 Lab ID :STK2133009-001 <br /> San Joaquin Co. Environmental Health Dep Description : Wellhead <br /> Drinking Water Interpretation <br /> Summary: Your water has a failure for one or more items on this sample report. Please see <br /> the table below to determine which items failed. Following the table is a brief <br /> explanation describing the significance of the failure and whether treatment may <br /> be required. <br /> MCL <br /> CONSTITUENT RESULT UNITS MCL LESS OR EXCEED <br /> EQUAL <br /> Inorganic - Primar- <br /> Fluoride ND mg/L 2 Pass <br /> Nitrate+Nitrite as N 0.8 mg/L 10 Pass <br /> Nitrate as NO3 3.8 mg/L 45 Pass <br /> Nitrate Nitrogen 0.8 mg/L 10 Pass <br /> Nitrite as N ND m 1 Pass <br /> Inorganic- Secondary <br /> Chloride 580 mg/L 500 Fail <br /> Copper ND ug/L 1000 Pass <br /> Iron 60 ug/L 300 Pass <br /> Manganese 170 ug/L 50 Fail <br /> MBAS (foaming agents) ND mg/L 0.5 Pass <br /> Specific Conductance 2860 umhos/cm 1600 Fail <br /> Sulfate 385 mg/L 500 Pass <br /> Total.Dissolved Solids 1770 m 1000 Fail <br /> Other <br /> Copper ND ug/L 1300*" Pass <br /> ND=Non-Detected. I"Calitomia Title 22,Section 64672.3 <br /> Page 4 of 9 <br />