Laserfiche WebLink
JJWTP — HMBP — Response to Violations <br />chemicals ( Sodium Hypochlorite, Phosphoric Acid, Oxygen, <br />and Mineral Oi)I. The maps list Sodium Hydroxide. The <br />facility is no longer is using/storing Sodium Hydroxide. The site <br />maps list Aluminum Sulfate as ALUM. The maps do <br />not list the emergency response equipment, and emergency <br />shut offs. The site maps are not numbered, and 2 out <br />of 4 do not contain North Orientation. <br />REGULATION GUIDANCE: A site map shall contain a north <br />orientation, loading areas, internal roads, adjacent <br />streets, storm and sewer drains, access and exit points, <br />emergency shutoffs, evacuation staging areas, hazardous <br />material handling and storage areas, and emergency response <br />equipment. <br />If a site map element is not applicable for your facility then list it <br />on the map and label as "NA". <br />CORRECTIVE ACTION: Immediately log into the California <br />Environmental Reporting System (CERS) at <br />http://cers,calepa,ca.gov/, upload the correct or updated <br />information, and submit to the END for approval. Any <br />abbreviations and symbols on the site map need to be <br />addressed within the site map. Submit statement to EHD <br />stating that the business plan will be submitted to EHD Annually <br />by the due date, January 15. <br />This is a repeat violation, Class II. <br />7 <br />HSC 25505(a)(3) Failed to electronically submit an adequate <br />An emergency response plan <br />ER procedures for a release or threatened release. <br />has been updated to include <br />OBSERVATION: The Emergency Action Plan (EAP)/Emergency <br />equipment list, ammonia <br />Response and Training Plan was not submitted <br />alarm, maps, & coordination <br />annually as a part of the business plan for years 2019 and <br />With first responders (Fire / <br />2020. Dale Klever, David Carter,and Bill Tapia have not <br />been working for this facility for longer than 30 days and the <br />PD/ Hospital). <br />emergency contact and notification list with the EAP <br />has not been updated. The EAP does not list the emergency <br />A copy of the ER and annual <br />response equipment at this facility. <br />REGULATION GUIDANCE: The business owner/operator shall <br />notice are provided, <br />annually review and certify that the business plan is <br />complete, accurate, up-to-date and in compliance with Section <br />11022 of Title 42 of the United States Code. An <br />annual electronic submittal satisfies these requirements. The <br />annual business plan shall be submitted/certified by <br />January 15 of each calendar year and may be submitted <br />beginning November 1 of the previous year. <br />A business plan shall include the following emergency response <br />procedures for a release or threatened release of <br />hazardous materials, including, but not limited to, the following: <br />- immediate notification of local emergency personnel and the <br />Environmental Health Department (EHD) <br />- procedures for the mitigation of a release or threatened <br />release to minimize any potential harm or damage to <br />persons, property, or the environment <br />- evacuation plans and procedures, including immediate notice, <br />for the site <br />CORRECTIVE ACTION: Immediately log into the CERS at <br />http://cers.calepa.ca.gov/, review and submit/certify the <br />current and complete information. Submit statement to EHD <br />stating that the business plan will be submitted to EHD <br />Annually by the due date, January 15. <br />This is a Class II violation. <br />g <br />HSC 25505(a)(4) Failed to establish and electronically <br />Employee training plan is <br />submit a reasonable or an adequate training program, <br />included as part of the ER. <br />