Laserfiche WebLink
SAN J 0 A Q I I I Irl Environmental Health Department <br /> C O U N T AMENDED <br /> 5/26/2021 <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> ESTES TRUCKING 7611 S AIRPORT WAY, STOCKTON May 21, 2021 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 308 CCR 2632(c), 2634(d), 2636(f) Failure of the leak detection equipment to have an audible and visual alarm. <br /> OBSERVATION: The float and chain in the dispenser sump failed to stop the flow of product at the dispenser when <br /> tested. <br /> REGULATION GUIDANCE:All monitoring equipment shall be maintained to activate an audible and visual alarm or <br /> stop the flow of product at the dispenser when it detects a leak. <br /> CORRECTIVE ACTION: The service technician adjusted the float and chain and verified functionality. <br /> This was corrected on site. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> On site for the monitoring system certification. Looked inside all sumps and UDC. Verified proper sensor <br /> locations. Verified spill container 5 gallon capacity and one hour hydrostatic test- Passed. Witnessed leak <br /> detector testing. Paperwork inspection was conducted on 5/26/2021. <br /> An inspection checklist was provided to the facility operator on the day of inspection. A complete report was <br /> finished on 05-26-2021 and replaces the initial checklist. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, within 30 days of receiving the complete inspection report. <br /> Documents Provided: Schedule of Free CUPA Classes, Return to Compliance Certification form, Corrective <br /> Action Statement Worksheet <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: May 26, 2021 Inspector: Inspector Phone: <br /> Printed Name and Title: STACY RIVERA, Lead Senior REHS (209)616-3043 <br /> Emailed to Bill Wardell, Terminal Manager <br /> FA0003695 PR0231511 SCO01 05/21/2021 <br /> EHD 23-01 Rev.9/16/2020 Page 7 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />