Laserfiche WebLink
SAN J 0 A Q I I I Irl Environmental Health Department <br /> CCUNr <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> SMK CHEVRON T25651 N HWY 99 , ACAMPO May 18, 2021 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 208 CCR 2716(a-e) Failure to comply with the designated operator inspection requirements. <br /> OBSERVATION: The designated operator failed to check and note all required items on the visual inspection <br /> reports.The incorrect and missing information included the following from the inspection reports: <br /> -The incorrect overfill test date <br /> -The incorrect designated operator report was used for the 10/17/2020 report <br /> REGULATION GUIDANCE: During the visual inspection,the designated operator shall check that all required <br /> testing and maintenance for the UST system have been completed and shall check all required items on the report. <br /> CORRECTIVE ACTION: Ensure that designated operators performing visual inspections at this facility are including <br /> all of the required information on the reports. <br /> This is a repeat violation, Class II. <br /> 304 CCR 2631(a); HSC 25290.1(c) Failure to construct, operate, and maintain primary containment as product-tight. <br /> OBSERVATION: Dispensers 5/6 and 9/10 were observed to have liquid seeping from the shear valve area (87 <br /> product piping)and the bottom of the UDCs were wet indicating a leak in the primary containment. <br /> REGULATION GUIDANCE:All primary containment for the UST system must be product tight. <br /> CORRECTIVE ACTION: Immediately have a properly licensed,trained, and certified contractor repair or replace the <br /> failed component(s), under permit and inspection of the EHD if necessary. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by June 17, 2021. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> ($152). To schedule an appointment, please call (209)468-3420. The report was emailed to the owner, Tony <br /> Singh, at<bigts1@aol.com>. <br /> Documents provided during inspection: List of free training classes <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: May 18, 2021 Inspector: Inspector Phone: <br /> Printed Name and Title: JOHN ALANIZ, Senior REHS (209)616-3053 <br /> Report emailed to,Tony Singh <br /> FA0003835 PR0231628 SCO01 05/18/2021 <br /> EHD 23-01 Rev.9/16/2020 Page 5 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />