Laserfiche WebLink
Underground Storage Tank <br />Secondary Containment Testing Report Form <br />8. SUMP/UDC TEST <br />Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br />Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br />Test Equipment Used: INCON TS1000-15 MIN. <br />Sump/UDC ID <br />87 <br />91 <br />DSL <br />1/2 <br />Sump Manufacturer <br />Unknown <br />Unknown <br />Unknown <br />Unknown <br />Sump depth (inches) <br />N/A <br />N/A <br />N/A <br />N/A <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />N/A <br />N/A <br />N/A <br />N/A <br />Test Start Time <br />10:48 <br />11:48 <br />12:21 <br />1:30 <br />Initial Reading <br />2.9755 <br />4.1212 <br />6.9702 <br />4.3163 <br />Test End Time <br />11:03 <br />12:03 <br />12:36 <br />1:45 <br />Final Reading <br />2.9742 <br />4.1208 <br />69706 <br />4.3153 - <br />Change in Reading <br />.0013 <br />.0004 <br />.0004 <br />.0010 <br />Pass/Fail Criteria <br />0.002 <br />0.002 <br />0.002 <br />0.002 <br />Tightness Test Results <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />Sump/UDC ID <br />3/4 <br />Sump Manufacturer <br />Unknown <br />Sump depth (inches) <br />N/A <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />N/A <br />Test Start Time <br />1:30 <br />Initial Reading <br />4.8895 <br />Test End Time <br />1:45 <br />Final Reading <br />4.8890 <br />Change in Reading <br />.0005 <br />Pass/Fail Criteria <br />0.002 <br />0.002 <br />0.002 <br />0.002 <br />Tightness Test Results <br />® Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Additional cooies of this ,cage may be attached. <br />Page 4 of 6 <br />