Laserfiche WebLink
C AL Tali 1.-,ri\ iromental Laboratories <br />6X I 1 koscaan... A‘cnue. \ 90.7? I lc, <br />!eh:phone: (S62) 272-2700 I a\ 1 .,621272- iSI) <br />QA/QC Report <br />Method: 8260B <br />Matrix: Water <br />Date Analyzed: 4/10/06 <br />Date Extracted: 4/10/06 <br />Perimeters Conc. ug/L Spike <br />Added <br />Recovery % Control Limits RPD <br />MS MSD MS MSD Rec. RPD <br />1,1-Dichloroethene 48 50 50 96 100 70-130 20 4 <br />Benzene 52 51 50 104 102 70-130 20 2 <br />Trichloroethene 45 49 50 90 98 70-130 20 8 <br />-Foluene 46 45 50 92 90 70-130 20 2 <br />Chlorobenzene 47 49 50 94 98 70-130 20 4 <br />ni,p-Xylenes 98 101 100 98 101 70-130 20 3 <br />MS: Matrix Spike <br />MSD: Matrix Spike Duplicate <br />RPD: Relative Percent Difference of MS and MSD <br />Perimeters Method <br />Blank <br />Units Det. <br />Limit <br />1,1-Dichlornethene ND ug/L 1 <br />Benzene ND ug/L 0.5 <br />Trichloroethene ND ug/L 0.5 <br />Toluene ND ug/L 0.5 <br />Chlorobenzene ND ug/L 0.5 <br />imp-Xylenes ND ug/L 0.6 <br />MI BE ND ug/L 1 <br />Tt3A ND ug/L 10 <br />DIPE ND ug/L 1 <br />ETBE ND ug/L 1 <br />TAME ND ug/L 1 <br />1,2-Dichloroetilane ND ug/L 0.5 <br />EDB ND ug/L 0.5 <br />Ethylbenzene ND ug/L 0.5 <br />o-Xylene ND ug/L 0.6 <br />TCE ND ug/L 1 <br />PCE ND ug/L 1 <br />101,11.11.1)11)1(..111 ..1) I()(VSTON1FR SATISFACTION