Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by p] Manufacturer Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ✓❑ Hydrostatic <br /> Test Equipment Used: Incon Sump Test System <br /> Sump/UDC ID UST Sump - Piping <br /> Sump Manufacturer Total Containment <br /> Sump Depth (inches) 43.5 <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 21 <br /> (inches) <br /> Test Start Time 08:09am <br /> Initial Reading 4.4614 <br /> Test End Time 08:24am <br /> Final Reading 4.4620 <br /> Change in Reading 0.0006 <br /> Pass/Fail Criteria 0.002 <br /> Tightness Test Results Pass <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> PasslFail Criteria <br /> Tightness Test Results <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />