Underground Storage Tank <br />Overfill Prevention Equipment Inspection Report <br />6. OVERFILL PREVENTION EQUIPMENT DETAILS <br />Tank ID (one OPE per column) <br />87 OCTANE <br />91 OCTANfj <br />DIESEL # 2 <br />Are both vent and tank riser piping <br />❑ Yes <br />❑ Yes <br />❑ Yes <br />❑ Yes <br />secondarily contained? <br />❑✓ No <br />❑ No <br />❑✓ No <br />✓❑ No <br />OPE Model <br />61 S O <br />61 SO <br />EMCO A1100 <br />What is the OPE response when activated? <br />p Shut off <br />❑ Shut off <br />❑✓ Shut off <br />❑✓ Shut off <br />(Check all that apply.) <br />Flow <br />Flow <br />Flow <br />Flow <br />❑ Restricts <br />❑ Restricts <br />❑ Restricts <br />❑ Restricts <br />Flow <br />Flow <br />Flow <br />Flow <br />❑ Audible <br />❑ Audible <br />❑ Audible <br />❑ Audible <br />Alarm <br />Alarm <br />Alarm <br />Alarm <br />❑ Visual <br />❑ Visual <br />❑ Visual <br />❑ Visual <br />Alarm <br />Alarm <br />Alarm <br />Alarm <br />Are flow restrictors installed on vent piping <br />❑ Yes* <br />❑ Yes* <br />❑ Yes* <br />❑ Yes* <br />that may interfere with the OPE operation? <br />p No <br />❑ No <br />❑✓ No <br />❑✓ No <br />At what level in the tank is the OPE set to <br />82.011 <br />81.5511 <br />961/411 <br />activate? Inches from bottom of tank <br />What is the percent capacity of the tank at <br />94.5% <br />94.1 % <br />> 100 <br />which the OPE activates? <br />Is the OPE in proper operating condition to <br />p Yes <br />❑ Yes <br />❑✓ Yes <br />❑ Yes <br />respond when the stored substance <br />❑ No <br />❑ No <br />❑ No <br />❑✓ No <br />reaches the designated regulatory level? <br />7. SUMMARY OF TESTING RESULTS <br />p Pass <br />❑ Pass <br />p Pass <br />❑ Pass <br />OPE Inspection Results <br />❑ Fail <br />❑ Fail <br />❑ Fail <br />p Fail <br />8. COMMENTS <br />Describe all results marked "Fail" and each proposed remedy. <br />DSL EMCO set too high, needs replacement. Donlee to R&R DIE Drop tube <br />* Mark here if: <br />❑ Flow restrictors interfere with overfill prevention and equipment repairs required. <br />Additional copies of this page may be attached. <br />Attach tank chart(s), measurements, calculations, and In -Tank Setup report(s) <br />Page 2 of 2 <br />