Laserfiche WebLink
Lancaster <br /> Laboratories Analysis Report <br /> 2425 New Holland Pike,PO Box 12425,Lancaster,PA 17605-2425-717-656-2300 Fax:717-656-2681•www.larcasterIabs.com <br /> Page 3 of 3 <br /> Quality Control Summary <br /> Client Name: Chevron Environmental Mgt. Co. Group Number: 1001992 <br /> Reported: 09/01/06 at 11:26 AM <br /> Surrogate Quality Control <br /> Nitrobenzene-d5 2-Fluorobiphenyl Terphenyl-d14 <br /> 4843973 89 109 92 <br /> 4843974 101 117* 106 <br /> 4843975 94 112 105 <br /> 4843976 91 107 101 <br /> 4843977 87 109 96 <br /> 4843978 86 107 98 <br /> Blank 99 125* 105 <br /> LCS 103 115 105 <br /> MS 94 112 105 <br /> MSD 91 107 101 <br /> Limits: 57-137 60-115 64-123 <br /> Analysis Name: TPH-DRO (C10-C25) Water <br /> Batch number: 062340009A <br /> Orthoterphenyl <br /> 4843973 115 <br /> 4843974 125 <br /> 4843975 109 <br /> 4843976 145* <br /> 4843977 105 <br /> 4843978 111 <br /> Blank 115 <br /> LCS 111 <br /> MS 109 <br /> MSD 145* <br /> Limits: 59-131 <br /> Analysis Name: TPH-DRO(C10-C25)Water w/ SiGel <br /> Batch number: 062400032A <br /> Orthoterphenyl <br /> 4843974 67 <br /> 4843975 69 <br /> 4843976 80 <br /> 4843977 79 <br /> Blank 83 <br /> LCS 72 <br /> MS 69 <br /> MSD 80 <br /> Limits: 59-131 <br /> *-Outside of specification <br /> (1) The result for one or both determinations was less than five times the LOQ. <br /> (2) The background result was more than four times the spike added. <br />