Laserfiche WebLink
Overfill Prevention Equipment Inspection <br /> .1114Tanknology OPW 61 and 71 Series Overfill Prevention Device Inspection <br /> Date: 7/13/2021 <br /> Customer Name: CHEVRON PRODUCTS USA <br /> Location#: Chevron 212470 <br /> Location Address: 3400 N MacArthur Drive ,Tracy,CA, 95376 <br /> OPW Model Number: 71so <br /> 87 <br /> PART 1)Proper height setting calculation <br /> Maximum Tank Volume per:Tank Chart Agallons 19703.000 <br /> Max shut off requirement for Flapper is 95% a 95% 0.95 0.95 0.95 0.95 <br /> Multiply Maximum tank volume by 95% c gallons 18717.850 <br /> Use tank chart to determine height of calculated volume D inches 105.375 <br /> Measure top of fill riser threads,or face seal adapter when used,to tank top E inches 27.500 <br /> Tank diameter From Chart Finches 117.750 <br /> Upper Tube in tank(G) F-D=G G inches 12.375 <br /> Subtract 2 inches from upper tube in tank G-2"=H H inches 10.375 <br /> Calculated minimum upper tube length(1)H+E=I i inches 37.875 <br /> Actual measured upper tube length (Without fill <br /> J inches 43.375 <br /> adapter)(J) <br /> PART 2)Device certification criteria evaluation <br /> Criteria 1 Yes <br /> Does the overfill prevention device meet the 95%requirement? <br /> Criteria 1 a If the final shutoff volume is installed greater than 95%,is there at <br /> least 250 gallons of ullage above the overfill device activation point NA <br /> to ensure that none of the tank top fittings are exposed to product, <br /> meeting the criteria established in EPA 280.20iic and per OPW <br /> installation guidelines. <br /> Criteria 2 Is the Actual measured upper tube length 6.5 inches Yes <br /> or more than the fill riser?(J must be 6.5"or more <br /> than E) <br /> Criteria 3 Does the overfill prevention device function as <br /> required?(Inspect the device for damage, Yes <br /> contamination,freedom of movement, <br /> weakening due to wear and corrosion) <br /> PART 3)Device Certification PASS/FAIL <br /> Pass <br /> Technician certifies that the device is operationally <br /> compliant. <br /> Comments: <br /> Signature of <br /> t <br /> Technician: Date: 7/13/2021 <br /> Tim Elebeck <br /> WO: NW1-2352476 <br />