Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for PACIFIC SERVICE STATION as of October12 , 2021 . <br /> Open violations from August 112021 inspection <br /> ❑ This violation was corrected efr�This violation will be corrected by (date) . y <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation : <br /> `cakes , <br /> e ko lEct tTAL1 <br /> iolation #319 - Failure to comply with overfill prevention equipment requirements . <br /> OBSERVATION: The mechanical flapper used as the overfill prevention system is not currently functional on the 87 <br /> grade UST. <br /> REGULATION GUIDANCE: All UST systems must be equipped with an approved , functional overfill prevention <br /> device at all times during delivery operations . <br /> CORRECTIVE ACTION : Immediately discontinue deposition of petroleum into this tank until the component is <br /> repaired or replaced by a properly licensed , trained , and certified contractor under permit and inspection of the EHD . <br /> If the failed component can ' t be replaced immediately, there is a possibility that the 87 UST system may be red <br /> tagged to prevent fuel inputs . <br /> ❑ This violation was corrected Plehis violation will be corrected by (date) : ✓ _ <br /> ❑ Supporting documents included _ <br /> Describe actions taken or will be taken to correct violation : / 2.. �� r i AA 1 E:0,0, <br /> �--� 1It 6LJ <br /> A1 <br /> bes (Ali) IA) ► i S <br /> i <br /> i <br /> I <br /> 4 <br /> Page 5 of 5 <br /> t <br />