Laserfiche WebLink
T 3:DIESEL LEAK TEST METHODQ <br /> PRODUCT CODE 3 - - - - - - - - - -V OUTPUT RELAY SETUP O� <br /> THERMAL COEFF : .000450 TEST ON DATE : ALL TANK - - - - - - `� <br /> TANK DIAMETER 111 .00 OCT 1 , 2014 <br /> TANK PROFILE 1 PT START TIME : DISABLED R '1 :87 STP RELAY <br /> FULL VOL : 6000 TEST RATE :0.20.GAL/HR TYPE: <br /> DURATION 2 HOURS STANDARD ' <br /> NORMALLY CLOSED <br /> FLOAT'SIZE: 4.0 IN. TST EARLY STOP:DISABLED <br /> WATER MINIMUM : 0.000 TANK #: 1 <br /> WATER WARNING 2,0 LEAK TEST REPORT FORMAT <br /> HIGH WATER LIMIT: . 3.0 NORMAL. IN-TANK ALARMS <br /> WATER ALARM FILTER: LOW T 1 :LOW PRODUCT ALARM <br /> LIQUID SENSOR ALMS <br /> MAX OR LABEL L 1 :FUEL ALARM <br /> VOLUME : 6000 L 5:FUEL .ALARM <br /> L 6:FUEL ALARM <br /> HIGH PRODUCT L 7:FUEL ALARM <br /> % MAX : y5.0 L B:FUEL ALARM <br /> (GALLONS) : 5700 L 9:FUEL ALARM <br /> L10:FUEL ALARM <br /> OVERFILL LIMIT LIQUID SENSOR SETUP L 1 :SENSOR 'OUT ALARM <br /> % MAX 90.0 - - - - - - - - - - - - L 5:SENSOR OUT ALARM <br /> (GALLONS) 5400 L 6:SENSOR OUT ALARM <br /> L. 1 :87 STP SUMP L 7:SENSOR OUT ALARM <br /> DELIVERY LIMIT TRI-STATE (SINGLE FLOAT) L B:SENSOR OUT ALARM <br /> % MAX 10.0 CATEGORY : STP SUMP L 9:SENSOR OUT ALARM <br /> (GALLONS) Goo L10:SENSOR OUT ALARM <br /> L 1 :SHORt ALARM <br /> LOW PRODUCT L 2:91 STP SUMP L 5:SHORT ALARM <br /> VOLUME 300 TRI-STATE (SINGLE FLOAT) L 6:SHORT ALARM <br /> CATEGORY : STP SUMP L 7:SHORT ALARM <br /> LEAK ALARM. LIMIT: 99 L 8:SHORT ALARM <br /> SUDDEN LOSS LIMIT: 99 L 9:SHORT ALARM <br /> TANK TILT 0.00 L 3:DIESEL STP SUMP L10:SHORT ALARM <br /> PROBE OFFSET 0.00 TRI-STATE (SINGLE FLOAT) <br /> CATEGORY : STP SUMP ISD SITE ALARMS <br /> ' ISD GROSS PRES FAIL <br /> SIPHON MANIFOLDED TANKS ISD DEGRD PRES FAIL <br /> T#: NONE L 4:ANNULAR SPACE ISD VAPOR LEAK FAIL <br /> LINE MANIFOLDED TANKS TRI-STATE (SINGLE FLOAT)' ISD VP PRES FAIL <br /> T#: NONE CATEGORY : ANNULAR SPACE ISD HOSE ALARMS <br /> ALL:GROSS COLLECT FAIL <br /> _ <br /> LEAK MIN PERIODIC: % ALL:DEGRD COLLECT FHIL <br /> 0 L 5:1-2 UDC ALL:FLOW COLLECT FHIL <br /> PERIODIC TEST TYPE TRI-STATE (SINGLE FLOAT) <br /> STANDARD CATEGORY : DISPENSER PAN R 2:91 STP RELAY <br /> TYPE: <br /> PERIODIC TEST FAIL STANDARD. <br /> ALARM DISABLED NORMALLY CLOSED <br /> GROSS TEST FAIL L 6:3-4 UDCTRI-STATE (SINGLE FLOAT) TANK #: 2 <br /> ALARM DISABLED CATEGORY : DISPENSER PAN <br /> PER TEST AVERAGING: OFF IN-TANK ALARMS <br /> T 2:LOW PRODUCT ALARM <br /> TANK TEST NOTIFY: OFF L 7:5-6 UDC <br /> TRI-STATE (SINGLE FLOAT) LIQUID SENSOR ALMS <br /> TNK TST SIPHON BREAK.:OFF CATEGORY DISPENSER PAN L 2:FUEL ALARM <br /> L 5:FUEL ALARM <br /> DELIVERY DELAY 3 MIN L 6:FUEL ALARM <br /> PUMP THRESHOLD 10.00% L 7:FUEL ALARM <br /> L 8:7-8 UDC L 8:FUEL ALARM <br /> TRI-STATE (SINGLE FLOAT) L 9:FU2L ALARM <br /> CATEGORY : DISPENSER PAN L10:FUEL ALARM <br /> L 2:SENSOR OUT ALARM <br /> L 5:SENSOR OUT ALARM <br /> L '6:SENSOR OUT ALARM <br /> L 9:9-10 UDC L 7:SENSOR OUT ALARM <br /> TR'I-STATE (SINGLE FLOAT) L 8:SENSOR OUT ALARM <br /> CATEGORY DISPENSER PAN IL 9:SENSOR OUT ALARM <br /> L10:SENSOR OUT ALARM <br /> L 2:SHORT ALARM <br /> L 5:SHORT ALARM <br /> L10:11-12 UDC: L 6:SHORT ALARM <br /> TRI-STATE (SINGLE FLOAT) L 7:SHORT ALARM <br /> CATEGORY DISPENSER PAN L B:SHORT ALARM <br />