Laserfiche WebLink
TAI T <br />11111Mf TO THE CNALLi Mk:r <br />p:714/560/8222 www.tait.com <br />701 N. Parkcenter Drive, Santa Ana, CA 92705 <br />Identification of Test Procedures for Secondary Containment Testing <br />To Whom It May Concern: <br />Tait Environmental Services, Inc., utilizes the following procedures when conducting Secondary <br />Containment Testing: <br />1) Containment Sumps, Transition Sumps, UDCs —Tait follows PEI-RP1200-17 Section 6.6 for the <br />accelerated test method. Tait uses the Incon TS -1000 hydrostatic test equipment following the <br />attached procedures. <br />2) Spill Buckets, Direct Bury & Contained in Sumps — Spill buckets contained in sumps are tested <br />per PEI -120047, Section 6.2, however Tait Pass/Fail threshold is 0" drop in one hour. Direct Bury <br />Spill Buckets are test the same as containment sumps per PEI -1200-17, Section 6.6. <br />3) Tank Annular Space — testing is conducted per PEI -1200-17, Section 4.2 <br />4) Piping Secondary Containment —Testing is conducted per PEI-RP1200-17, Section 5.3 <br />Please consider this letter as our Test Procedure utilized when conducting Secondary Containment <br />Testing in lieu of either parts or the whole RP1200 document due to copyright infringement. <br />SEP 11 <br />ENVIRONMENTAL NC A <br />�-�� <br />L0)V I_ TMFN`� <br />