Laserfiche WebLink
_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2348912 Date: 12/15/2021 <br /> Site Name/ID: 7-ELEVEN#20632, MKT 2368/20632 <br /> Address: 4627 DA VINCI DR @ MARCH LN <br /> City: STOCKTON State: CA Zip: 95207 <br /> Tank ID 3 4 5 <br /> Product REGULAR PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 4 4 4 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. 20091498 20091500 20091499 <br /> Pump Operating Pressure(psi) 34.00 35.00 35.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 30.00 35.00 35.00 <br /> N/A for Electronic LD's <br /> Resiliency(ml) 120.00 100.00 120.00 <br /> N/A for Electronic LD's <br /> Metering PSI 21 22 22 <br /> N/A for Electronic LD's <br /> Opening Time(sec) 2 3 3 <br /> N/A for Electronic LD's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Landon Zamora Certification#: 162837 <br /> Technician Signature: Expire Date: 6/11/2023 <br /> Environmental Compliance for Petroleum Systems <br /> ©2021 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />