Laserfiche WebLink
CONDUIT SCHEDULE 100A MAIN LUG ONLY <br /> NAME DESCRIPTION CONDUIT SIZE QTY WIRE SIZE/ MFR# WIRE QTY E 1PH 3WIRE 208/120V <br /> SERVES: TENANT SPACE NEW PANELBOARD SERIES RATED cn <br /> STP POWER CONDUITS MUST BE RUN IN SEPARATE RACEWAY. LOCATION: STOCKROOM GROUND BAR ~ <br /> 101 DISPENSER POWER- NON DIESEL 3/4" 4 #10 THWN-2 1#10 HOT, 1#10 NEUT, 1#10 GR ENTIRE WIRING RUN MUST BE IN RIGID PVC COATED MOUNTING: SURFACE W <br /> GALVANIZED STEEL CONDUIT. USE ONLY ROB ROY CONDUIT CK LOAD SERVED WIRE BRKR PL PHASE C PHASE A PL BRKR WIRE LOAD SERVED CK 2i <br /> 102 DISPENSER SUMP SENSOR/FLOW METER 3/4" 5 BELDEN #88760 2 TYPES "PERMA-COAT", "PLASTI-BOND"OR"KORKAP" 2 <br /> DISPENSER 5 SUMP SENSOR/FLOW METER/ ELECTRICAL CONDUITS. NO PVC OR RNC CONDUIT ALLOWED. C 0 H H <br /> 102A 3/4" 1 BELDEN #88760 3 1 DISPENSER 1 10 20 1 1.08 1.08 1 20 10 DISPENSER 2 2 0 <br /> PRESSURE SENSOR .0 Z Z <br /> 2-WIRE TWISTED PAIR 6 PAIR USE ONLY ROB ROY CONDUIT TYPES"PERMA-COAT", 3 SWITCHED NEUTRAL -- -- - 0.00 0.00 - -- -- SWITCHED NEUTRAL 4 W W W <br /> 103 DISPENSER DATA* 3/4" 62 2 <br /> "PLASTI-BOND" OR"KORKAP" ELECTRICAL CONDUITS AT 5 DISPENSER 3 10 20 1 1.08 1.08 1 20 10 DISPENSER 4 6 <br /> CAT6 FEP/FEP (WCW7931AFEQ) 1 cn > 2E 2E <br /> FIBERGLASS TANK SUMPS OR WHERE BRAVO F-17-RR OR 7 SWITCHED NEUTRAL -- -- - 0.00 0.00 - -- -- SWITCHED NEUTRAL 8 a) LU O O <br /> 104 2HP STP POWER 3/4" 2 #8 THWN-2 3#8 HOTS, 1#8 GR F-10-RR ENTRY FITTINGS ARE CALLED OUT FOR FIRST 10' OF 9 DISPENSER #5 10 20 1 1.08 1.08 1 20 10 DISPENSER #6 10 U U <br /> RUN. TRANSITION TO RIGID NONMETALLIC CONDUIT(RNC) 11 SWITCHED NEUTRAL -- -- - 0.00 0.00 - -- -- SWITCHED NEUTRAL 12 W <br /> 105 RUL TANK ATG/SUMP SENSORS/INTERSTITIAL 3/4" 1 BELDEN #88760 7#88760 WHERE ALLOWED BY JURISDICTION. __ __ W <br /> VACUUM SENSOR 13 SPARE 20 1 0.00 0.00 1 20 SPARE 14 11 U U <br /> PUL/DSL TANK ATG/SUMP SENSORS/INTERSTITIAL RUN PVC COATED GALVANIZED STEEL FOR WIRING RUNS 15 SPARE -- 20 1 0.00 0.00 1 20 -- SPARE 16 O O <br /> 106 1" 1 BELDEN #88760 13#88760 <br /> VACUUM SENSOR EXPOSED TO THE WEATHER; FOR ENCLOSING MAIN 17 RUL STP 8 20 2 1.21 1.21 2 20 8 PUL STP 18 o N N N <br /> GROUNDING CONDUCTOR: WHERE REQUIRED FOR 19 ----- -- -- - 1.21 1.21 - -- -- ----- 20 <br /> 107 VENT/FILL SUMP SENSOR 3/4" 3 BELDEN #88760 1 MECHANICAL PROTECTION OR WHERE SPECIFICALLY 21 D-BOX CONTROLLER 12 20 1 0.11 1.09 2 20 8 DSL STP 22 C) \ \ <br /> OC) N <br /> O � O <br /> -- -- <br /> 108 STP SUMP SENSOR/ATG PROBE/VACUUM SENSOR 3/4" 3 BELDEN #88760 5 INDICATED. 23 SPACE -- - 0.00 1.09 - -- ----- 24 <br /> 25 SPACE 0.00 0.36 1 20 12 OVERFILL ALARM 26 <br /> WITH THE EXCEPTION OF THE FIRST AND THE LAST 10'OF THE <br /> 27 LOW VOLTAGE DISC 12 20 1 0.36 0.00 SPACE 28 a) <br /> 109 INTERCOM 1" 2 BELDEN 8762 2 PAIR PER CALL BOX UNDERGROUND RUN AND ONLY WHERE AHJ ALLOWS, RIGID 29 SPACE 0.00 0.00 SPACE 30 <br /> NONMETALLIC CONDUIT(RNC) IS ALLOWED FOR TOTAL 10.46 3.87 KVA Proto 11-05-18 <br /> 110 DISPENSER POWER- DIESEL 3/4" 2 #10 THWN-2 1#10 HOT, 1#10 NEUT, 1#10 GR UNDERGROUND RUNS IF CONDUIT IS BURIED AT A MINIMUM <br /> OF 2'. 87.17 32.25 AMPS <br /> 111 1.5HP STP POWER 3/4" 1 #8 THWN-2 2#8 HOTS, 1#8 GR TOTAL LOAD 14.33 KVA 68.89 AMPS <br /> PER NEC ARTICLE 220 FEEDER LOAD 14.33 KVA 68.89 AMPS <br /> 112 AIR VAC MACHINE 3/4" 1 SEE BLDG ELECTRICAL SEE BLDG ELECTRICAL <br /> FUEL GC TO PROVIDE SINGLE PHASE POWER TO DEMAND LOAD 14.33 KVA 68.89 AMPS <br /> THE MAG-VFC. THREE PHASE POWER TO RUN M <br /> 113 CANOPY LIGHTING POWER 3/4" 2 SEE BLDG ELECTRICAL SEE BLDG ELECTRICAL FROM MAG-VFC TO 2HP VARIABLE SPEED STP'S. LOW <br /> W <br /> 114 CANOPY SIGN POWER 3/4" 1 SEE BLDG ELECTRICAL SEE BLDG ELECTRICAL ti 0 Z J <br /> 3 U) <br /> 115 VENT SUMP SENSOR 3/4" 1 BELDEN #88760 1 112 X N > W W <br /> 0 <br /> NOTE: DISPENSING DEVICES, REMOTE PUMPS,AND TANKS AIR VAC W LU Z <br /> SHALL COMPLY WITH TABLE 514.3(B)(1)AND TABLE MACHINE U (� J Lo = <br /> 116 OVERFILL ALARM 3/4" 1 #12 THWN-2 1 #12 HOT, 1 #12 NEUT, 1 #12 GR 514.3(8)(2), AND 2019 CALIFORNIA ELECTRICAL CODE. z (� N O U <br /> z � mrn Z U) <br /> 117 OVERFILL ALARM /ACKNOWLEDGMENT SWITCH 3/4" 1 #12 THWN-2 1#12 HOT, 1#12 NEUT > Q J <br /> Z � � < JW <br /> * REFERENCE GILBARCO FIELD WIRING DIAGRAM FOR COMPLETE SPECIFICATIONS 3 _ Z <br /> Uj J Q <br /> * CONTRACTOR TO UPSIZE CONDUCTORS FOR VOTLAGE DROP AS REQUIRED \ 0 w 2 0 Q <br /> Name or Item Tag Complete Luminaire Description Backlighting Rating Uplight Rating Glare Rating(Lumens) W Of \ O Y () C) <br /> COORDINATE PANEL F AND FUELING AREA CIRCUIT LOAD 3 / Z <br /> INFORMATION WITH STORE MEP'S. STORE CONTRACTOR TO Max allowable Backlight Rating Max Allowable Uptight Rating Max Allowable Glare Rating J >- W H U <br /> SUPPLY AND INSTALL NEW PANELS AND VERIFY ELECTRIC Mounting Height Lighting Type Mounting Height FEEDER AND BRANCH CIRCUIT VOLTAGE DROP CALCULATIONS w � J O U Q <br /> Backlight Rating Per Design Uptight Rating Per Design Glare Rating Per Design � W W � � W <br /> PANEL CAN MEET LOAD REQUIREMENTS. <br /> M15 CPY250 B-DM F B UL 57K-WH HZ m Q <br /> Status of Devgn Date Prepared:03-16-2020 � ' LI..I J <br /> All other outdoor W <br /> 2 MH from 2 MH from property Cu Al Load Cu cr 1L AL Raemrac Circuit f 1 M `/^/ <br /> No Limit 63 lighting,including U3 UO G3 G1 Voltage Voltage Voltage Voltage Voltage Load Voltage Load Wire Sim Resistance Reactance Resistance Reactance Type Length V (� <br /> property line line TQ N Q <br /> decorative Drop Drop Drop at Load at Source (Amperes) Drop Pmrer (ANGor (Ohmsper (Ohmsper (Ohmsper (Ohmsper (RGS (One Nat- = f/1 <br /> 3#12, 3/4"C T_ UJ - <br /> FOR PANEL INFORMATION (Percent) (colts) (colts) (colts) (colts) Farrar Factor kcmil) 1000 LF) 1000LF) 1000LF� 1110 LF) or PVC) Feel) C) Q <br /> REF STORE ELECTRICAL DRAWINGS Description (2 or 1.732) N <br /> Panel F to Di pens 2.63 321 530 116.79 120.00 9.00 1.7321 0.85 10 1.200 0.050 2 000 0.050 PVC 197 co <br /> ONE-LINE DIAGRAM IS FOR REFERENCE Panel FtoSTP 286 533 055 20167 208.00 zo_n 321 0 8 3 o_7so 0.052 0.052 0.052 PVC 221 <br /> PANEL ONLY. FUEL CONTRACTOR TO VERIFY Panel Lto Iirvac 0.43 ass 0.03 119.42 120.00 13.00 x2 0.85 1 2.000 0.054 0.054 0.054 PVC 15 <br /> FEEDER LOADS TO BE PLACED ON PANELS. <br /> PANEL F <br /> LIGHTING SUPPLIED BY 7-ELEVEN, INC AND <br /> INSTALLED BY FUEL CONTRACTOR. NOTE: PVC CONDUIT(WHERE ALLOWED BY AHJ), MAY BE USED. STORE SIDE NOTE: ROUTE ALL CONDUITS UNDERGROUND TO C-STORE ELEC <br /> SEE SPECIFICATION SHEET G16.0, SECTION 2.3.1 FOR ROOM. DATA/COM CABLE EXCESS TO BE COILED IN ELEC RM <br /> CIRCUITS REQUIRED FOR THE FUELING AREA/ FOR ROUTING ABOVE CEILING IN C-STORE TO FINAL <br /> 3 POLE, 100 AMP LOCATIONS WHERE PVC CONDUIT MAY BE USED. <br /> CANOPY LIGHTING AND MISCELLANEOUS EQUIPMENT CONTACTOR TERMINATION POINT. <br /> ARE: (2) EMERGENCY GASOLINE W <br /> SHUT-OFF SWITCH REF 2-G10.0. STORE CONTRACTOR: <br /> CANOPY LIGHTS 864 VA 20 A BREAKER EXTENTS OF N.E.C. CLASSIFIED INSTALL CONDUIT FROM THE ELECTRICAL <br /> CANOPY LIGHTS 864 VA 20 A BREAKER NOTE: AREA TYPICAL ALL DISPENSERS ROOM TO 10'-0" PAST BUILDING SLAB. SEE W <br /> CANOPY SIGNS 600 VA 20 A BREAKER 3 SPECIFICATION SHEET G16.0, SECTION VII, <br /> AIR-VAC MACHINE 1560 VA 20 A BREAKER (1) GENERAL CONTRACTOR TO INSTALL PANELS CIRCUIT BREAKERS AND CONDUIT. .2.3.1 FOR CONDUIT TYPES. W <br /> CONT/EMERG SHUTOFF 40 VA 20 A BREAKER (2) FUEL CONTRACTOR SHALL INSTALL WIRING (FROM CIRCUIT BREAKERS TO <br /> EQUIPMENT), RELAYS, ETC. MAKE ALL CONNECTIONS AND COMPLETE SEAL OFF. ROUTE OVERHEAD TO ROUTE OVERHEAD TO FUELING CONTRACTOR: <br /> REF STORE MEP PANEL SCHEDULES FOR LOCATION REMAINING COLUMNS REMAINING COLUMNS EXTEND CONDUITS FROM 10'-0" PAST THE <br /> ELECTRICALONE - LINE DIAGRAM 20'01, ry0 S BUILDING SLAB TO FINAL TERMINATION <br /> POINT . SEE SPECIFICATION SHEET G16.0, <br /> N.T.S. - _E�;T ---1 191 T!:;9� <br /> 109 _ 109 SECTION VII, 2.3.1 FOR CONDUIT TYPES. z Z <br /> 0 0 0 0 0 0 W <br /> WP J-BOXES WITH WIRE COILED - LU <br /> 103 DATA - _ 103 DATA _ 103 DATA <br /> co <br /> STORE SIDE 101 F-9,11 101 F-5,7 101 <br /> FOR FUTURE USE (4 LOC) CONNECT F-1,3 w <br /> TO BUILDING PANEL- L FOR E SIDE 1 SIDE 1 a SIDE 1 w <br /> SIGNAGE POWER 99'-8" O-T-O CANOPY 02 102 102 REMOTE VENT (D <br /> -�- SENSOR - �- SENSOR �- SENSOR Z g <br /> DISP 5 DISP 3 DISP 1 W J <br /> 0 0 0 0 0 0 W a w o 3 <br /> Z o 3 <br /> JWP W P J 0 N. <br /> 20;0„ ° W <br /> 1 of 4 SIGN <br /> ( ) ti 115 O <br /> SIGN (2 of 4) 9 <br /> CANOPY EACH INTERCOM m ix " �� <br /> LIGHTING SPEAKER/CALL SWITCH HAS CLEAN AIR ° _ Uj <N <br /> J <br /> POWER TWO PAIRED CIRCUITS ~ r-~ <br /> SEPARATOR <br /> FROM LIGHTS LIGHTS CANOPY SIGN <br /> ROUTED TO CONSOLE-TYP <br /> 113 BUILDING POWER FROM 114 Q <br /> 113 PANEL L - - - - - - - _ BUILDING PANEL L -- -- A <br /> 0 0 0 0 0 0 <br /> i 0 0 0 0 0 0 M O 04 < <br /> _ _ _ <br /> 102 102 102 W 00 <br /> SENSOR SENSOR SENSOR 7"1 <br /> 0 Y <br /> SIDE 1 SIDE 1 no SIDE 1P ENCLOSURE Z ti <br /> DATA O <br /> DISP 5 DISP 3 DISP 1 103 DATA 103 DATA 103 (� <br /> 0 0 0 0 0 0 DISP 6 110 F-10,12 DISP 4 101 F-6,8 DISP 2 110 F-2,4 Q m <br /> 0 0 F-26 116 0 0 0 0 <br /> CD N o_ 117 m U <br /> a� <br /> N O OVERFILL ALARM NOTE: OUTDOOR LIGHTING CALCULATIONS FOR <br /> C3 Q I REF 4-G6.0 FOR THE CANOPY ARE INCLUDED IN THE STORE O U <br /> U ELECTRICAL DRAWINGS ON SHEET E4.1. <br /> 6i O MS MS MS 0 (n D D <br /> l � 0C20Ccn - C (6 � cn <br /> o ~ _0 ° �mo � � <br /> EE ca_ 42" CONTAINMENT MANWAY 0 0 Q E w L o o <br /> L WITH PRODUCT FILL AND <br /> DIESEL VENT CONNECTION -0° °r 0 c ° �o ami c <br /> �Rz0 0 0 0 0 0 / REF 2-G4.1 -M CL � 01 M c. <br /> Q-° j�Q=1 45 0 0 <br /> oo \ \ / \ / / 42" CONTAINMENT MANWAY 0 - - <br /> DISP 6 DISP 4 v DISP 2 WITH SUBMERGED PUMP 42" CONTAINMENT MANWAY Q o a 0 a) U L E- <br /> = AND TANK PROBE m to m ° m 0 0 E <br /> �J 107 105 �: Cn C v m N <br /> �, / / \ / AND TANK PROBE 0 C 4 �Q 0>1 (n w� o <br /> N cn C <br /> REF 2-G4.0 <br /> REF 1-GLLJ4.0 E2LvUQ-t= 0._ 0 <br /> Q ' ANNULAR SPACE RESERVOIR 0 m >'a0i Q �� o W <br /> _ co <br /> o � o o � o o � o o � � REF4-G3.0 7 p•E o �-2o=�� � � <br /> 0 ca <br /> i i i o0 107 RUL TANK <br /> COWDSL TANK <br /> PUL TANK Fl 0-81 <br /> FOR STP POWER CONDUITS, USE ONLY ROB ROY Q�oFESS/ <br /> LLJ CONDUIT TYPES"PERMA-COAT", "PLASTI-BOND" <br /> OR"KORKAP"WHERE BRAVO FITTINGS ARE USED <br /> w 111 F-18,20 AND NO PVC CONDUIT IS PERMITTED. ROUTE �, m <br /> CD F-22,24 F-17,19 104 CONDUITS IN SEPERATE RACEWAY. w. m <br /> z SIGN 104 35558 <br /> SIGN WP <br /> OJ (4 of 4) WP <br /> 3 of 4)91 <br /> �9�FCHAN�GP <br /> LLJ <br /> MS MOTION SENSOR M1 42" CONTAINMENT MANWAY 42" CONTAINMENT MANWAY OF CA��FO <br /> W REF G7.1 FOR PART NUMBER STREET SIDE WITH SUBMERGED PUMP WITH PRODUCT FILL AND ANNULAR SPACE RESERVOIR 42" CONTAINMENT MANWAY <br /> LED RECESSED FUELING CANOPY REF 4-G3.0 WITH PRODUCT FILL AND <br /> LIGHTING AND TANK PROBE VAPOR CONNECTION STREET SIDE VAPOR CONNECTION 03/23/21 <br /> o REF 1-G4.0 REF 1-G4.1 <br /> U W <br /> �z CDN N REF 1-G4.1 SHEET: <br /> mz CA OPY CO DU T SCH EM AT C UNDERGROUND CO DU T SCHEMATIC <br /> G9 . 0 <br /> z ¢ <br /> io <br /> FUELING - USA CA <br />