Laserfiche WebLink
JONES COVEY GROUP, INC, <br /> COMPLETE FUEL SYSTEM CONSTRUCTION Et MAINTENANCE SERVICES <br /> MECHANICAL / ELECTRONIC LEAK DETECTOR CERTIFICATION <br /> SITE: Pilot 1017 Lathrop DATE: 0 s 1 8 2 0 2 1 <br /> State Facility# CONTACT: Manager <br /> 1017 PHONE: (865) 588-7488 <br /> JOB#: 2138232-1-1 <br /> Tank # T1-T3 T5-T6 <br /> Product Diesel Diesel <br /> LD Manufacturer VMI VMI <br /> LD Model LD3000 LD3000 <br /> Sump Condition Good Good <br /> Operation Pressure 36 PSI 38 PSI <br /> PSI <br /> Opening Time(Sec) 5 Secs 6 Secs <br /> Metering Pressure 19 PSI 18 PSI <br /> (PSI) <br /> Functional Element 34 PSI 34 PSI <br /> Holding Pressure <br /> Leak Rate LD Detected 3.00 GPH 3.00 GPH <br /> (GPH) <br /> Does LD Detect 3 GPH Yes Yes <br /> Leak Rate? <br /> LD Serial 30001072 30001073 <br /> Comments: <br /> Technician Justin Zorn License Number VMI -4634 <br /> Signature - <br /> 9595 LUCAS RANCH ROAD, RANCHO CUCAMONGA, CA 91730- LICENSED IN 41 STATES <br /> California State License#804431 A, B, HAZ <br />