Laserfiche WebLink
Storage Tank Inspection Check List <br /> Equipment#: Emergency Generator C Fuel Tank <br /> Item Inspection Task Y N N/A Comments &Observations <br /> 1.3( a) Inspect for signs of settlement where rain <br /> Asphalt runoff may be directed under the tank instead X <br /> of away. <br /> 1.3 b <br /> ( ) Inspect for exposed rock filler indicating <br /> product leeching. X <br /> 1.4 (a) Inspect for signs of settlement where rain <br /> Sand/Dirt runoff may be directed under the tank instead X <br /> of away. <br /> 1.4(b) Inspect for exposed rock filler indicating <br /> product leeching. X <br /> 1.5 Inspect anchor bolts and check for excessive <br /> Anchors cracking of the concrete structures to which X <br /> they are embedded. <br /> 1.6 Inspect annular plate and weldments for <br /> Annular Ring cracks and general corrosion/erosion. X <br /> Record annular plate thickness and assess. <br /> Visually inspect 100%of the bottom and <br /> 1.7(a) annular plates for evidence of settlement and <br /> Internal Bottom corrosion. Hammer test the bottom plates for X <br /> evidence of external corrosion. Report any low <br /> areas that do not drain properly. <br /> Measure, record, and assess internal and <br /> 1.7(b) external pitting of floor plates by FL, UT,VT, X <br /> or ET methods. <br /> 1.7 c <br /> ( ) Vacuum test bottom lap welds and shell to <br /> annular welds. X <br />