Laserfiche WebLink
August 25, 2021 Lab ID :STK2150747-001 <br /> San Joaquin Co. Environmental Health Dep Description : Wellhead <br /> Drinking Water Interpretation <br /> Summary: Your water has a failure for one or more items on this sample report. Please see <br /> the table below to determine which items failed. Following the table is a brief <br /> explanation describing the significance of the failure and whether treatment may <br /> be required. <br /> MCL <br /> CONSTITUENT RESULT UNITS MCL LESS OR EXCEED <br /> EQUAL <br /> Inorganic - Primary <br /> Fluoride ND mg/L 2 Pass <br /> Nitrate +Nitrite as N 3.0 mg/L 10 Pass <br /> Nitrate as NO3 13.3 mg/L 45 Pass <br /> Nitrate Nitrogen 3.0 mg/L 10 Pass <br /> Nitrite as N ND mg/L 1 Pass <br /> Inorganic - Secondary <br /> Chloride 29 mg/L 500 Pass <br /> Copper 120 ug/L 1000 Pass <br /> Iron 3370 ug/L 300 Fail <br /> Manganese 600 ug/L 50 Fail <br /> MBAS (foaming agents) ND mg/L 0.5 Pass <br /> Specific Conductance 491 umhos/cm 1600 Pass <br /> Sulfate 12.6 mg/L 500 Pass <br /> Total Dissolved Solids 330 mg/L 1000 Pass <br /> Other <br /> Copper 120 ug/L 1300** Pass <br /> ND=Non-Detected.**California Title 22,Section 64672.3 <br /> Page 4 of 9 <br />