Site Address: 14900 W Highway 12, Lodi Record ID#PR0516677 <br /> Date of inspection: 7/6/2021 Program: APSA <br /> Photo 2: High level monitoring devices for each fixed above ground storage tanks were not discussed in the SPCC plan dated 4/11/2020. <br /> $'Z•7 Neatin Coils(40 CFR 112.8fc)17)] <br /> This setteon is not applicable for the facility. <br /> 5280, r71 and Other Prevention Systems[40 CFR 112.8(c)18)] <br /> Fuel levels for each fuel are monitored daily,and shall be measured and adjusted if necessaryin <br /> the event of a discrepancy. <br /> $-2.9 E luenY Treatment Facilitfes[40 CFR 112.8(c)(9)] <br /> This section is not applicable for the facility since there are no effluent treatment facilities <br /> located at this facility, <br /> 5.1.10 Visible Drschar es[40 CFR 112-8(c)(10)] <br /> Visible discharges from any container or appurtenance—inciuding seams,gaskets,piping,pu <br /> valves,rivets,and bolts—are quickly corrected upon discovery. <br /> 5-2.21 Mobile and Portable Containers[40 CFR 112.8(c)(11)] <br /> Secondary containment is provided for the 55 gallons by being storing the drums inside the <br /> hazardous material enclosure. This enclosure has a secondary containment floor base. A spill <br /> Pallet provides secondary containment for AST 7,the portable tank that stores waste vegetable <br /> Oil. See Section 5.2.2 for recommended secondary containment for AST 7. <br /> During business hours a potential spill from a portable tank will be cleaned up by personnel. Ani <br /> discharged material is quickly contained and cleaned-up by use of sorbent pads and uthe <br /> appropriate cleaning products. <br /> Any empty containers should be labeled as such. <br /> 5.3 Transfer Operations,Pumping,and In-Plant Processes[40 CFR 112.8(d)] <br /> Transfer operations at this facility include: <br /> • The transfer of oil into or from tanker trucks at the loading/unloading areas. <br /> ■ All products being pumped into or out of all tanks at this facility loading area <br /> accomplished by way of connection hoses from the tank truck to the remote <br /> ground level fill connection. The system is manually operated with a handheld <br /> emergency shutoff device held by the user. This device will shut off any pump in <br /> operation during product exchange. <br /> 53.1 BY fed Piping[40 CFR 112.8(d)(1)] <br /> As noted by the code buried piping that is installed or replaced on or after August 16,2002, <br /> have a protective wrapping and coating. It appears that the underground fuel pipe const <br /> double-wa[i fiberglass pipe. <br /> Shewit Woldearegay, EHS Page 2 of 2 <br />