Laserfiche WebLink
Underground Storage Tank <br /> Overfill Prevention Equipment Inspection Report <br /> 6 . OVERFILL PREVENTION EQUIPMENT DETAILS <br /> Tank ID (one OPE per column) DSL- 1 DSL-2 87 <br /> Are both vent and tank riser piping ❑ Yes ❑ Yes ❑ Yes ❑ Yes <br /> secondarily contained ? ❑✓ No ❑✓ No ❑✓ No ❑ No <br /> OPE Model oPW 71 SO oPW 71 SO oPW 71 SO <br /> What is the OPE response when activated ? ✓❑ Shut off ❑✓ Shut off ❑✓ Shut off ❑ Shut off <br /> (Check all that apply. ) Flow Flow Flow Flow <br /> El Restricts ❑ Restricts ❑ Restricts ❑ Restricts <br /> Flow Flow Flow Flow <br /> ❑ Audible ❑ Audible ❑ Audible ❑ Audible <br /> Alarm Alarm Alarm Alarm <br /> ❑ Visual ❑ Visual ❑ Visual ❑ Visual <br /> Alarm Alarm Alarm Alarm <br /> Are flow restrictors installed on vent piping ❑ Yes * ❑ Yes * ❑ Yes * ❑ Yes * <br /> that may interfere with the OPE operation ? ❑✓ No ❑✓ No ❑✓ No ❑ No <br /> At what level in the tank is the OPE set to 105 107 77 <br /> activate ? Inches from bottom of tank <br /> What is the percent capacity of the tank at 93 . 2 94 . 6 90 . 3 <br /> which the OPE activates ? <br /> Is the OPE in proper operating condition to ❑✓ Yes ❑✓ Yes ❑✓ Yes ❑ Yes <br /> respond when the stored substance ❑ No ❑ No ❑ No ❑ No <br /> reaches the designated regulatory level ? <br /> 7 . SUMMARY OF TESTING RESULTS <br /> [D Pass ZPass [D Pass ElPass <br /> OPE Inspection Results ❑ Fail ❑ Fail ❑ Fail ❑ Fail <br /> 8 . COMMENTS <br /> Describe all results marked "Fail' and each proposed remedy. <br /> * Mark here if: <br /> ❑ Flow restrictors interfere with overfill prevention and equipment repairs required . <br /> Additional copies of this page may be attached. <br /> Attach tank chart(s), measurements, calculations, and In - Tank Setup reports) <br /> Page 2 of 2 <br />