Laserfiche WebLink
REVISIONS 0 <br /> DESCRIPTION DATE: W Z <br /> N <br /> Z E3 <br /> Demand Control Ventilation Hood Control Panel Specifications: Ln <br /> turndown <br /> Controls shall be listed by ETL (UL 508A) and shall comply with demand ventilation system 0 Ln .21 <br /> turndown requirements outlined in IECC 403.2.8 (2015). J W <br /> DUCT TEMPERATURE SENSOR <br /> The control enclosure shall be NEMA 1 rated and listed for installation inside of the <br /> exhaust hood utility cabinet. The control enclosure may be constructed of stainless steel �,, <br /> or painted steel. I� <br /> s <br /> Temperature probe(s) located in the exhaust duct riser(s) shall be constructed of <br /> stainless steel. 00 W <br /> Q <br /> lyA digital controller shall be provided to activate the hood exhaust fans dynamically based N �� <br /> on a fixed differential between the ambient and duct temperatures sensors. This functionU <br /> shall meet the requirements of IMC 507.1.1. <br /> o T_ O <br /> In O <br /> co <br /> A digital controller shall provide adjustable hysteresis settings to prevent cycling of the II I , U1 0 <br /> fans after the cooking appliances have been turned off and/or the heat in the exhaust m II c c <br /> system is reduced. CONTROL PANEL V I I I £ <br /> A digital controller shall provide an adjustable minimum fan run—time setting to prevent fanLCD <br /> I N <br /> cycling. INTERFACE 2 LL T <br /> ROOM TEMPERATURE <br /> — Variable Frequency Drives (VFDs) shall be provided for fans as required. The digital SENSOR Duct Temp Sensor to be w __J o <br /> controller shall modulate the VFDs between a minimum setpoint and a maximum setpoint on I o �.r' 10 <br /> demand. The duct temperature sensor input(s) to the digital controller shall be used to TYPICAL HOOD CONTROL PANEL INSTALLATION installed I n every exhaust riser. I 0') w <br /> a LU <br /> calculate the speed reference signal. <br /> All Duct Temp Sensors and I� <br /> N <br /> N <br /> — The VFD speed range of operation shall be from 0% to 100% for the system, with the actual Hood Lights to be wired back <br /> minimum speed set as required to meet minimum ventilation requirements. Sequence of Operations: a BUILDING DEPARTMENT <br /> The hood control panel is capable of operating in one or more of the following states at any t0 SC— EMS EIectricaI Control X Z <br /> — An internal algorithm to the digital controller shall modulate supply fan VFD speed given time: Box V � NAME: <br /> proportional to all exhaust fans that are located in the same fan group as the supply fan. — Automatic: The system operates based on the differential between room temperature and o � CITY OF STOCKTON <br /> the temperature at the hood cavity or exhaust duct collar. Fans activate at a DUCT THERMISTOR SENSOR INSTALLATION i N V <br /> — The system shall operate in PREP MODE during light cooking load or COOL DOWN MODE when configurable temperature differential threshold. Depending on the job configuration each fan NOTE, TherNstor has 2 wires that cawnect to control cabinet Room Override Thermostat = rn ADDRESS: <br /> sufficient heat remains underneath the hood system after cooking operations have zone can be configured as static or dynamic. These terms refer to whether a variable , d �, (n 425 N. ELDORADO ST. <br /> completed. Operation during either of these periods will disable the supply fans and provide motor such as EC Motors or VFD driven motors modulate with temperature. If the panel is V <br /> an exhaust fan speed that is equal to the minimum ventilation requirement. equipped with variable speed fans and the zone is defined as "dynamic", these will modulate ■ 3 5" STOCKTON, CA 95202 <br /> within a user—defined range based on the temperature differential. Panels equipped with I z <br /> — A digital controller shall disable the supply fan(s), activate the exhaust fan(s), activatevariable speed fans and a fan zone defined as "static", fans will run at a set speed �'> ` o PHONE: <br /> the appliance shunt trip, and disable an electric gas valve automatically when fire condition calculated for the drive. Demand control ventilation systems are capable of modulating ,�_,,,,�,,, ,,. „ I a 209-937-8561 <br /> is detected on a covered hood. exhaust and make up air fan speeds per the requirements outlined in IECC 403.2.8. aakWW—) 2 0 <br /> BUILDING OWNER <br /> A digital controller shall allow for external BMS fan control via Dry Contact (external — Manual: The system operates based on human input from an HMI. h.r.FWT.mr•«r. m �• <br /> Y P P �T4, Provides room override based on temperature Q <br /> control shall not override fan operation logic as required by code). differential between the room and duct. NAME: <br /> Schedule: A weekly schedule can be set to run fans for a specified period throughout the `•32-M Installed by electrician on a wall, 5'-6' off the E BECK PROPERTIES <br /> An LCD interface shall be provided with the following features: da There are three occu ied times er da to allow for the user to set u a time that is finished floor, in the space but not directly c w <br /> a. On Off push button fan & light switch activation y P P y P under the hood or close to an appliance � <br /> / P 9 suitable to their needs. Any time that is within the defined occupied time, the system will run MV (including the electrical control box) so the Z ADDRESS: <br /> b. Integrated gas valve reset for electronic gas valves (no reset relay required) at modulation mode and follow the fan procedure algorithm based on temperature during this w reading is accurate for space. m <br /> c. VFD Fault display with audible & visual alarm notification time. During unoccupied time, the system will have an extra offset to prevent unintended O 3114 W. HAMMER LN. <br /> d. Duct temperature sensor failure detection with audible & visual alarm notification activation of the system during a time where the system is not being occupied. v STOCKTON, CA 95209 <br /> e. Mis—wired duct temperature sensor detection with audible & visual alarm notification rZ <br /> f. A single low voltage Cat-5 RJ45 wiring connection — Other: The system operates based on the input from an external source (DDC, BMS or CZ PHONE: <br /> g. An energy savings indicator that utilizes measured kWh from the VFDs hard—wired interlock) < (209) 957-0331 <br /> TENANT <br /> NAME: <br /> Z YUMMY DONUTS <br /> Z <br /> Q ADDRESS: <br /> Z <br /> LLJ 3221 W. HAMMER LN. <br /> STOCKTON, CA 95209 <br /> PHONE: <br /> (209) 636-8909 <br /> LIC, <br /> O 0 NAME: <br /> UT.B.D. <br /> U W Q <br /> O Z O-) < ADDRESS: <br /> � Q <br /> O <br /> N Z <br /> LO M O <br /> W 0PHONE: <br /> Q <br /> DEMONSTRATIONS ARE AVAILABLE AT THE Q U �o QROFE A/pNq� <br /> CALIFORNIA BAY AREA DISPLAY CENTER _ ����,r�,W <br /> System Design Verification (SDV) FOR PRICES AND QUESTIONS, CALL z LMrJ � a <br /> DANNY NG <br /> z <br /> REFERENCE JOB# 3787274 w No. C74034 <br /> If ordered, CAS Service will perform a System Design Verification (SDV) once all equipment has had a REG91©CAPTIVEAIRE.COM Z EXP, <br /> complete start up per the Operation and Installation Manual. Typically, the SDV will be performed after all PHONE: (415) 956-2200 FAX: (919) 227-5940 N U z ��qTF CIV1�Eo��� <br /> inspections are complete. N 0 LU of CA�-� <br /> � <br /> Any field related discrepancies that are discovered during the SDV will be brought to the � U) PHONE:209-263-1382 <br /> attention of the general contractor and corresponding trades on site. These issues DATE: 4/9/2019 <br /> will be documented and forwarded to the appropriate sales office. If CAS Service has to LE U) CONSTRUCTION SITE <br /> resolve a discrepancy that is a field issue, the general contractor will be notified and DWG.#: J <br /> billed for the work. Should a return trip be required due to any field related discrepancy that cannot be 3787274 SITE ADDRESS: <br /> Q 3221 W. HAMMER LN. STE.A&B <br /> resolved during the SDV, there will be additional trip charges. I.-_ <br /> DRAWN W STOCKTON, CA 95209 <br /> BY: Q <br /> During the SDV, CAS Service will address any discrepancy that is the fault of the manufacturer. Should a 0 SITE APN: <br /> return trip be required, the general contractor and appropriate sales office will be notified. There will be CO 3/4,CALE: -0 O 82-220-03 <br /> no additional charges for manufacturer discrepancies. DRAWING INFORMATION <br /> MASTER DRAWING REVISION DATE <br /> LLJ 4-25-19 <br /> J FILE NAME: <br /> 19-0311 —YUMMY—DONUTS <br /> SHEET NO. (n DRAWING SCALE: <br /> N.T.S. <br /> 6 <br /> M8 <br />