Laserfiche WebLink
CONDUIT SCHEDULE <br /> NAME DESCRIPTION CONDUIT SIZE QTY WIRE SIZE/MFR# <br /> 101 DISPENSER POWER-NON DIESEL 3/4" 4 #10 THWN-2 <br /> 102 DISPENSER SUMP SENSOR/FLOW METER 3/4" 5 BELDEN #88760 <br /> 102A DISPENSER 5 SUMP SENSOR/FLOW METER/ 3/4" 1 BELDEN #88760 <br /> PRESSURE SENSOR <br /> 103 DISPENSER DATA* 3/4" 6 2-WIRE TWISTED PAIR <br /> CAT6 FEP/FEP (WCW7931AFEQ) <br /> 104 2HP STP POWER 3/4" 2 #8 THWN-2 <br /> 105 RUL TANK ATG/SUMP SENSORS/INTERSTITIAL 3/4" 1 BELDEN#88760 <br /> VACUUM SENSOR <br /> 106 PUL/DSL TANK ATG/SUMP SENSORS/INTERSTITIAL 1" 1 BELDEN #88760 <br /> VACUUM SENSOR <br /> 107 VENT/FILL SUMP SENSOR 3/4" 3 BELDEN#88760 <br /> 108 STP SUMP SENSOR/ATG PROBE/VACUUM SENSOR 3/4" 3 BELDEN#88760 <br /> 109 INTERCOM 1" 2 BELDEN 8762 <br /> 110 DISPENSER POWER-DIESEL 3/4" 2 #10 THWN-2 <br /> 111 1.5HP STP POWER 3/4" 1 #8 THWN-2 <br /> 112 AIR VAC MACHINE 3/4" 1 SEE BLDG ELECTRICAL <br /> 113 CANOPY LIGHTING POWER 3/4" 2 SEE BLDG ELECTRICAL <br /> 114 CANOPY SIGN POWER 3/4" 1 SEE BLDG ELECTRICAL <br /> 115 VENT SUMP SENSOR 3/4" 1 BELDEN#88760 <br /> 116 OVERFILL ALARM 3/4" 1 #12 THWN-2 <br /> 117 OVERFILL ALARM/ACKNOWLEDGMENT SWITCH 3/4" 1 #12 THWN-2 <br /> REFERENCE GILBARCO FIELD WIRING DIAGRAM FOR COMPLETE SPECIFICATIONS <br /> * CONTRACTOR TO UPSIZE CONDUCTORS FOR VOTLAGE DROP AS REQUIRED <br /> COORDINATE PANEL F AND FUELING AREA CIRCUIT LOAD <br /> INFORMATION WITH STORE MEP'S. STORE CONTRACTOR TO <br /> SUPPLY AND INSTALL NEW PANELS AND VERIFY ELECTRIC <br />