Laserfiche WebLink
CONDENSATE DRAIN - <br />SEE PLUMB. DRAWING <br />FACTORY ROOF CURB <br />JI <br />BY A/C CONTR. <br />SEE DETAIL <br />TRIS SHEET <br />(N)SA MANIFOLDS <br />NOTE: <br />INSTALL SMOKE DETECTORS IN S.A. <br />DUCT -ALL UNITS 2000 CFM OR <br />LARGER. <br />DUCT MTD.— <br />SMOKE DETECTOR <br />(N)RETURN AIR DUCT <br />NOTE: <br />1. AIR CONDITIONING UNIT SHOWN IS FOR <br />INFORMATION ONLY. VERIFY ALL UTILPTIES <br />WITH AIR CONDITIONING UNITS FURNISHED. <br />2. ACOUSTICALLY <br />LINE SA & RA PLENUM DROPS <br />FRESH AIR INTAKE <br />W/BACKDRAFT <br />DAMPER <br />(E) <br />AIR CONDITIONING UNIT (SIDE DISCHARGE) I N.T.S. I I <br />KEY <br />OMECH. <br />CONTR. <br />OELECT. <br />CONTR. <br />CWL <br />& WIRED BY <br />eFURNISHED <br />ELECT. CONTR.& INSTALLED <br />M <br />BY MECH. CONTR. <br />9:20 °" wpm= 75' <br />AIR DISTRIBUTION <br />p <br />m PedI <br />CWL <br />IL <br />WI <br />72 <br />— HEAT — — <br />17 <br />FACTORY OFF WHITE. OPPOSED BLADE DAMPER <br />— COOL — — <br />�. <br />CEILING DIFFUSER - HARD CEILING <br />GAN ON <br />Rh <br />HE T <br />24 VAC — <br />MADE <br />FAN MLMAY PROGRAM SET CLC <br />OVEINmP. <br />00 <br />0 0 <br />0 O <br />O <br />AIR CONDITIONING UNIT <br />(EXIST) <br />CONTROL <br />G <br />AIR DISTRIBUTION <br />— FAN — - <br />W2 <br />CEILING DIFFUSER <br />— HEAT — — <br />WI <br />TYPE: METALAIRE FACE FILLER PANEL: <br />— HEAT — — <br />Y2 <br />FACTORY OFF WHITE. OPPOSED BLADE DAMPER <br />— COOL — — <br />Y1 <br />CEILING DIFFUSER - HARD CEILING <br />— COOL I — — <br />Rh <br />TYPE METALAIRE FACE <br />24 VAC — <br />Rc <br />FACTORY OFF WHITE. OPPOSED BLADE DAMPER <br />24 VAC (COMMON) <br />ELECTRONIC WALL THERMOSTAT (NEW) <br />TOTAL LINE DEBONAIR MODEL 220 HEATING & COOLING THERMOSTAT <br />WITH SEVEN DAY TIME CLOCK, SOFT START, FOUR HOUR OVERRIDE, <br />PURGE MODE, DUAL DIGITAL SET POINTS & TEMPERATURE DEAD BAND. <br />VENTILATION AND PURGE CYCLE <br />AS REQUIRED BY CEC ALL VENTILATION SHALL MEET CEC GUIDELINES. A/C <br />UNITS SHALL START 1 HR. PRIOR TO OCCUPANCY AND CYCLE TO PROVIDE <br />PURGE CYCLE. <br />POWER <br />120V/11`11160 HZ <br />CONTROL POWER Q <br />I D/S I <br />014143"eR11 <br />TPANSFORMFR <br />UNIT <br />TERMINAL <br />STRIP <br />SUPPLY DUCT—/ <br />DUCT MOUNTED SMOKE DETECTOR <br />IN SUPPLY AIR DUCT. A/C UNITS <br />WITH SUPPLY CFM OF 2000 & HIGHER <br />AC226 <br />AIR CONDITIONING UNIT WIRING DIAGRAM I N.T.S. 1 21 <br />14"0 Si <br />EXHAI <br />HOOD CALCULATIONS <br />Q= 50(801106") =1,000 CFM <br />144 <br />DUCTRANGE <br />MIN—lm/2 m=0.4 SF <br />MAX.=10lfs=0.66SF <br />RECOM.=1"Xsw= 0.55 SF <br />CHECK 10" 0 DUCT <br />(5" ?x3.14 = 78.5 SI <br />78.5/144=.54 SF <br />CHECK VELOCITY <br />994CFM/0.54=1840 FPM <br />EF USE CFM (CAPTIVEAIRE FAN MFG.) <br />2 EXHAUST AIR <br />MODEL DR30HF,0.5" SP, 0.2511P, 994 CFM <br />SA MAKE-UP AIR <br />MODEL l-GIO, 0.5" SP, 0.25 HP 1000 CFM <br />] (ELECT:-120V/IPH) <br />(INTERLOCK EF -2 & SA -1) <br />0 EXHAUST <br />OSA <br />TYPE -II HOOD DETAIL I N.T.S. 13 <br />DUCT <br />AIR DISTRIBUTION <br />STANDARDS <br />I <br />— <br />CEILING DIFFUSER <br />2013 CMC <br />SECTIONS <br />TYPE: METALAIRE FACE FILLER PANEL: <br />YES <br />36,500 BTU/HR SENSIBLE COOLING <br />FACTORY OFF WHITE. OPPOSED BLADE DAMPER <br />NO <br />III I <br />CEILING DIFFUSER - HARD CEILING <br />DUCT MATERIAL <br />I� <br />TYPE METALAIRE FACE <br />1600 CFM SUPPLY AIR @ 0.5" ESP <br />INSTALLATION OF DUCTS <br />FACTORY OFF WHITE. OPPOSED BLADE DAMPER <br />YES <br />® <br />RETURN & EXHAUST AIR GRILLES/REGISTERS <br />FACTORY CURB, FACTORY FILTER RACK, <br />605 <br />TYPE METALAIRE SQUARE GRID24X12, 24X24, 24X48 <br />SMOKE, FIRE AND CEILING DAMPERS <br />UNIT TOTAL WT. = 490 LBS. <br />FACTORY OFF WHITE. OPPOSED BLADE DAMPER <br />NO <br />AUTOMATIC SHUT OFFS <br />LAY -IN TEE BAR. FOR HARD CEILINGS - USE FRAME <br />EF <br />BROAN-676 <br />& OPPOSED BLADE DAMPER. <br />AC240 <br />I <br />DUCT WORK <br />TOILET EXHAUST <br />HP = 50 WATTS RPM = 1550 <br />SHEET METAL (WHERE SHOWN) <br />120 VOLTS, I PHASE, 60 CYCLES <br />OUTSIDE AIR <br />GALVANIZED IRON FABRICATED & <br />DIAMETER ROUND DUCT <br />WT.= 15 LBS <br />INSTALLED AS PER 2016 CALIFORNIA MECHANICAL <br />F.D. - <br />FIRE DAMPER <br />CODE & 2016 CALIFORNIA TITLE 24 STANDARDS. <br />QUADRANT BALANCING DAMPER <br />B.D.D. - <br />SUPPLY & RETURN MAINS <br />M.V.D. - <br />MANUAL VOLUME DAMPER <br />1. RECTANGULAR OR ROUND, FABRICATED <br />CEILING DIFFUSER <br />C.R- - <br />& INSTALLED AS PER UMC CODE, & <br />E.P. - <br />EXTENDED PANEL <br />INSULATED PER INSULATION SCHEDULE. <br />RETURN AIR GRILLE <br />E.G. - <br />FINAL CONNECTORS TO AIR DEVICES <br />T.T.B. - <br />TRIM FLANGE TO FIT T -BAR GRID <br />L FLEXIBLE FIBERGLASS DUCT. <br />DOOR LOUVER <br />U/C - <br />MAXIMUM 7-0" LONG, 1 1/2" M <br />W.M.S. - <br />WIRE MESH SCREEN <br />HEAVY DENSITY FIBERGLASS WITH <br />CUBIC FEET PER MINUTE <br />OSA <br />LINER & VAPOR JACKET, CLASS <br />M.V.D. <br />MANUAL VOLUME DAMPER <br />I, STANDARD 181. <br />FLEX DUCT <br />DUCT <br />CONSTRUCTION <br />STANDARDS <br />ALL WORK SHALL CONFORM TO THE FOLLOWING <br />AC <br />2013 CMC <br />SECTIONS <br />48,000 BTU/HR TOTAL COOLING, I STAGE <br />TABLE <br />36,500 BTU/HR SENSIBLE COOLING <br />DESCRIPTION <br />CEDB = 95"F EWB = 67"17 <br />602 <br />100,000/80,000 BTU/HR HEATING INPUT/OUTPUT <br />DUCT MATERIAL <br />SEER= 14.0 EFF: -80"/" <br />603 <br />1600 CFM SUPPLY AIR @ 0.5" ESP <br />INSTALLATION OF DUCTS <br />208 VOLTS, 3 PHASE, 60 CYCLES <br />604 <br />UNIT FULL LOAD AMPS = 17.4, CKT, BRKR=30A <br />DUCT INSULATION <br />FACTORY CURB, FACTORY FILTER RACK, <br />605 <br />FACTORY OUTSIDE AIR HOOD <br />SMOKE, FIRE AND CEILING DAMPERS <br />UNIT TOTAL WT. = 490 LBS. <br />608 <br />UNIT HEIGHT (INCL. CURB) = 42" <br />AUTOMATIC SHUT OFFS <br />EXHAUST FANS (CLG. MTD.) <br />EF <br />BROAN-676 <br />RETURN AIR <br />AC240 <br />GENERAL NOTES <br />L POWER WIRING, CONDUIT, SWITCHES AND TIME <br />CLOCKS SHALL BE FURNISHED AND INSTALLED <br />BY ELECTRICAL CONTRACTOR. <br />2. LOW VOLTAGE WIRE AND CONDUIT SHALL BE <br />FURNISHED & INSTALLED BY ELECTRICAL CON- <br />TRACTOR. FINAL CONNECTIONS BY AIR CONDI- <br />TIONING CONTRACTOR. <br />3. CONDENSATE DRAIN PIPING (COPPER OR GALV.) <br />TO AN APPROVED RECEPTOR BY PLUMBING CON- <br />TRACTOR. CONDENSATE DRAIN TO BE TRAPPED. <br />SEE DETAIL. <br />4. GENERAL CONTRACTOR SHALL FURNISH AND /OR <br />INSTALL CUTTING, PATCHING, FRAMING, ROOF- <br />ING, PAINTING, EQUIPMENT SCREENING, CURBS, <br />OR PLATFORMS WITH THE REQUIREMENTS OF <br />THE AIR CONDITIONING SYSTEM. <br />5. EQUIPMENT, INSTALLATION AND OPERATION <br />SHALL BE IN ACCORDANCE WITH ALL <br />APPLICABLE CODES. <br />6. ALL A/C SYSTEMS SHALL BE TESTED AND BALANCED <br />IN ACCORDANCE WITH AA13C GUIDELINES. THE T & B <br />CONTRACTOR SHALL NOTIFY MECH. CONTRACTOR OF <br />ANY DEFICIENCY IN THE SYSTEMS AND HAVE THEM <br />CORRECTED PRIOR TO FINAL APPROVAL & START UP OF <br />A/C SYSTEMS. THE PROPER AMOUNT OF OSA SHALL <br />COMPLY WITH T-24 CALCULATIONS. <br />AC32 <br />TITLE 24 NOTES <br />TITLE 24 FOR AC ENERGY CONSERVATION <br />1, ALL DUCTWORK, INCLUDING INSULATION, SHALL <br />CONFORM TO CALIFORNIA ADMINISTRATIVE CODE, <br />2016 TITLE 24, AND THE CMC LOW VELOCITY DUCT <br />CONSTRUCTION STANDARDS, LATEST 2016 EDITION. <br />2, ALL EXHAUST FANS TO BE FURNISHED WITH BACK - <br />DRAFT DAMPERS. <br />3. ALL AC UNITS SHALL BE PROVIDED WITH A <br />THERMO- STAT FOR AUTOMATIC REGULATION OF <br />TEMPERATURE AND A FOUR HOUR OVERRIDE <br />TIMER.THERMOSTAT AND TIMER SHALL BE <br />READILY ACCESSIBLE AND BE MANUALLY <br />ADJUSTABLE. <br />4. ALL THERMOSTATS SHALL BE CAPABLE OF BEING SET <br />TO MAINTAIN SPACE TEMPERATURE SET POINTS FROM <br />55 DEGREES F. TO 85 DEGREES F. AND SHALL BE <br />CAPABLE OF OPERATING THE SYSTEM HEATING AND <br />COOLING SEQUENCE. <br />5, ALL THERMOSTATS SHALL BE ADJUSTABLE TO <br />PROVIDE A TEMPERATURE RANGE OF UP TO 5 DEGREES <br />F. BETWEEN FULL HEATING AND FULL COOLING AND <br />SHALL HAVE THE CAPABILITY OF TERMINATING ALL <br />HEATING AT A TEMPERATURE NO MORE THAN 70 <br />DEGREES F. AND OF TERMINATING ALL COOLING AT A <br />TEMPERATURE NOT LESS THAN 78 DEGREES F. <br />6. TRANSVERSE JOINTS FOR ALL AIR SUPPLY DUCTS <br />INSTALLED WHERE AIR LEAKAGE WOULD BE NON- <br />BENEFICIAL TO THE OCCUPIED AREA TEMPERATURE <br />REQUIREMENTS SHALL BE SEALED WITH APPROVED <br />MASTIC OR TAPE. <br />7, A MAINTENANCE LABEL SHALL BE AFFIXED TO <br />MECHANICAL EQUIPMENT AND A MAINTENANCE <br />MANUAL SHALL BE PROVIDED FOR THE OWNERS USE. <br />AC12 <br />Z <br />0 <br />W <br />�r <br />w a) <br />� C <br />N C 7 <br />E <br />00 U <br />fa) z c c <br />W g <br />ca <br />y <br />-�..+ N N p <br />.. 1p <br />J co 0) <br />06 O a) <br />CL r F, U C <br />C% NAV N <br />L 6 .m (L O <br />-a C CL <br />mI�cE <br />-aM CJS <br />C <br />2 00 <br />d CN <br />U N y <br />(D N N MC N <br />�... _J C O <br />00 c rn <br />r@ <br />C) �a aa)iUm <br />B <br />V) <br />J <br />W <br />Q <br />Q <br />Z <br />Q <br />W <br />O <br />Z <br />W <br />Q <br />W <br />i <br />WU <br />J <br />(Joe) <br />F <br />F <br />ui <br />Z <br />VJ <br />W <br />WC Of � <br />GF- <br />WCN <br />Lo <br />Q <br />ryryU <br />�OZ <br />-jO <br />zVU <br />wz0 <br />' <br />C/) <br />�M <br />W <br />`ZD`^ <br />VJ <br />C) <br />W <br />O <br />d <br />DATE: 02/02/2017 <br />JOB: PT -ST -05 <br />DWG BY: KS <br />CHK BY: APV <br />M1 <br />EQUIPMENT SCHEDULE <br />AIR CONDITIONING UNIT (NEW) <br />AC <br />GAS/ELECT. A/C <br />LINED DUCT - SIZE INDICATED IS <br />48,000 BTU/HR TOTAL COOLING, I STAGE <br />4.0 <br />36,500 BTU/HR SENSIBLE COOLING <br />(2) <br />CEDB = 95"F EWB = 67"17 <br />EXISTING <br />100,000/80,000 BTU/HR HEATING INPUT/OUTPUT <br />NOT IN THIS CONTRACT <br />SEER= 14.0 EFF: -80"/" <br />POINT OF CONNECTION <br />1600 CFM SUPPLY AIR @ 0.5" ESP <br />WITH <br />208 VOLTS, 3 PHASE, 60 CYCLES <br />WITH OUT <br />UNIT FULL LOAD AMPS = 17.4, CKT, BRKR=30A <br />GENERAL CONTRACTOR <br />FACTORY CURB, FACTORY FILTER RACK, <br />PLUMBING CONTRACTOR <br />FACTORY OUTSIDE AIR HOOD <br />ELECTRICAL CONTRACTOR <br />UNIT TOTAL WT. = 490 LBS. <br />MECHANICAL CONTRACTOR <br />UNIT HEIGHT (INCL. CURB) = 42" <br />CUBIC FEET PER MINUTE <br />EXHAUST FANS (CLG. MTD.) <br />EF <br />BROAN-676 <br />RETURN AIR <br />CENTRI. MATL ALUM. CLG. MTD. <br />I <br />CFM =50 TSP =0.25"WG <br />TOILET EXHAUST <br />HP = 50 WATTS RPM = 1550 <br />KITCHEN RANGE HOOD EXHAUST <br />120 VOLTS, I PHASE, 60 CYCLES <br />OUTSIDE AIR <br />BACKDRAFT DAMPER, INTAKE GRILLE <br />DIAMETER ROUND DUCT <br />WT.= 15 LBS <br />GENERAL NOTES <br />L POWER WIRING, CONDUIT, SWITCHES AND TIME <br />CLOCKS SHALL BE FURNISHED AND INSTALLED <br />BY ELECTRICAL CONTRACTOR. <br />2. LOW VOLTAGE WIRE AND CONDUIT SHALL BE <br />FURNISHED & INSTALLED BY ELECTRICAL CON- <br />TRACTOR. FINAL CONNECTIONS BY AIR CONDI- <br />TIONING CONTRACTOR. <br />3. CONDENSATE DRAIN PIPING (COPPER OR GALV.) <br />TO AN APPROVED RECEPTOR BY PLUMBING CON- <br />TRACTOR. CONDENSATE DRAIN TO BE TRAPPED. <br />SEE DETAIL. <br />4. GENERAL CONTRACTOR SHALL FURNISH AND /OR <br />INSTALL CUTTING, PATCHING, FRAMING, ROOF- <br />ING, PAINTING, EQUIPMENT SCREENING, CURBS, <br />OR PLATFORMS WITH THE REQUIREMENTS OF <br />THE AIR CONDITIONING SYSTEM. <br />5. EQUIPMENT, INSTALLATION AND OPERATION <br />SHALL BE IN ACCORDANCE WITH ALL <br />APPLICABLE CODES. <br />6. ALL A/C SYSTEMS SHALL BE TESTED AND BALANCED <br />IN ACCORDANCE WITH AA13C GUIDELINES. THE T & B <br />CONTRACTOR SHALL NOTIFY MECH. CONTRACTOR OF <br />ANY DEFICIENCY IN THE SYSTEMS AND HAVE THEM <br />CORRECTED PRIOR TO FINAL APPROVAL & START UP OF <br />A/C SYSTEMS. THE PROPER AMOUNT OF OSA SHALL <br />COMPLY WITH T-24 CALCULATIONS. <br />AC32 <br />TITLE 24 NOTES <br />TITLE 24 FOR AC ENERGY CONSERVATION <br />1, ALL DUCTWORK, INCLUDING INSULATION, SHALL <br />CONFORM TO CALIFORNIA ADMINISTRATIVE CODE, <br />2016 TITLE 24, AND THE CMC LOW VELOCITY DUCT <br />CONSTRUCTION STANDARDS, LATEST 2016 EDITION. <br />2, ALL EXHAUST FANS TO BE FURNISHED WITH BACK - <br />DRAFT DAMPERS. <br />3. ALL AC UNITS SHALL BE PROVIDED WITH A <br />THERMO- STAT FOR AUTOMATIC REGULATION OF <br />TEMPERATURE AND A FOUR HOUR OVERRIDE <br />TIMER.THERMOSTAT AND TIMER SHALL BE <br />READILY ACCESSIBLE AND BE MANUALLY <br />ADJUSTABLE. <br />4. ALL THERMOSTATS SHALL BE CAPABLE OF BEING SET <br />TO MAINTAIN SPACE TEMPERATURE SET POINTS FROM <br />55 DEGREES F. TO 85 DEGREES F. AND SHALL BE <br />CAPABLE OF OPERATING THE SYSTEM HEATING AND <br />COOLING SEQUENCE. <br />5, ALL THERMOSTATS SHALL BE ADJUSTABLE TO <br />PROVIDE A TEMPERATURE RANGE OF UP TO 5 DEGREES <br />F. BETWEEN FULL HEATING AND FULL COOLING AND <br />SHALL HAVE THE CAPABILITY OF TERMINATING ALL <br />HEATING AT A TEMPERATURE NO MORE THAN 70 <br />DEGREES F. AND OF TERMINATING ALL COOLING AT A <br />TEMPERATURE NOT LESS THAN 78 DEGREES F. <br />6. TRANSVERSE JOINTS FOR ALL AIR SUPPLY DUCTS <br />INSTALLED WHERE AIR LEAKAGE WOULD BE NON- <br />BENEFICIAL TO THE OCCUPIED AREA TEMPERATURE <br />REQUIREMENTS SHALL BE SEALED WITH APPROVED <br />MASTIC OR TAPE. <br />7, A MAINTENANCE LABEL SHALL BE AFFIXED TO <br />MECHANICAL EQUIPMENT AND A MAINTENANCE <br />MANUAL SHALL BE PROVIDED FOR THE OWNERS USE. <br />AC12 <br />Z <br />0 <br />W <br />�r <br />w a) <br />� C <br />N C 7 <br />E <br />00 U <br />fa) z c c <br />W g <br />ca <br />y <br />-�..+ N N p <br />.. 1p <br />J co 0) <br />06 O a) <br />CL r F, U C <br />C% NAV N <br />L 6 .m (L O <br />-a C CL <br />mI�cE <br />-aM CJS <br />C <br />2 00 <br />d CN <br />U N y <br />(D N N MC N <br />�... _J C O <br />00 c rn <br />r@ <br />C) �a aa)iUm <br />B <br />V) <br />J <br />W <br />Q <br />Q <br />Z <br />Q <br />W <br />O <br />Z <br />W <br />Q <br />W <br />i <br />WU <br />J <br />(Joe) <br />F <br />F <br />ui <br />Z <br />VJ <br />W <br />WC Of � <br />GF- <br />WCN <br />Lo <br />Q <br />ryryU <br />�OZ <br />-jO <br />zVU <br />wz0 <br />' <br />C/) <br />�M <br />W <br />`ZD`^ <br />VJ <br />C) <br />W <br />O <br />d <br />DATE: 02/02/2017 <br />JOB: PT -ST -05 <br />DWG BY: KS <br />CHK BY: APV <br />M1 <br />LEGEND <br />AC105 <br />SYMBOL- DESCRIPTION <br />(L) - <br />LINED DUCT - SIZE INDICATED IS <br />SHEET METAL DIMENSION <br />UTR - <br />UP THRU ROOF <br />DTR - <br />DOWN THRU ROOF <br />MC - <br />NOT IN THIS CONTRACT <br />P.O.C. - <br />POINT OF CONNECTION <br />W/ - <br />WITH <br />W/O - <br />WITH OUT <br />G.C. - <br />GENERAL CONTRACTOR <br />P.C. - <br />PLUMBING CONTRACTOR <br />E.C. - <br />ELECTRICAL CONTRACTOR <br />M.C. - <br />MECHANICAL CONTRACTOR <br />CFM - <br />CUBIC FEET PER MINUTE <br />S.A. - <br />SUPPLY AIR <br />R.A. - <br />RETURN AIR <br />E.A. - <br />EXHAUST AIR <br />T.X. - <br />TOILET EXHAUST <br />KRHX - <br />KITCHEN RANGE HOOD EXHAUST <br />OSA - <br />OUTSIDE AIR <br />DIAMETER ROUND DUCT <br />T - <br />THERMOSTAT <br />F.D. - <br />FIRE DAMPER <br />Q.B.D. - <br />QUADRANT BALANCING DAMPER <br />B.D.D. - <br />BACKDRAFT DAMPER <br />M.V.D. - <br />MANUAL VOLUME DAMPER <br />C.D. - <br />CEILING DIFFUSER <br />C.R- - <br />CEILING REGISTER <br />E.P. - <br />EXTENDED PANEL <br />RAG. - <br />RETURN AIR GRILLE <br />E.G. - <br />EXHAUST GRILLE <br />T.T.B. - <br />TRIM FLANGE TO FIT T -BAR GRID <br />D/L - <br />DOOR LOUVER <br />U/C - <br />UNDERCUT DOOR <br />W.M.S. - <br />WIRE MESH SCREEN <br />CFM <br />CUBIC FEET PER MINUTE <br />OSA <br />OUTSIDE (STANDARD) AIR <br />M.V.D. <br />MANUAL VOLUME DAMPER <br />HOiii" <br />FLEX DUCT <br />® <br />CEILING DIFFUSER <br />CEILING REGISTER <br />-A---ISWG <br />SIDEWALL GRILLE <br />O <br />THERMOSTAT <br />N.I.C. <br />NOT IN THIS CONTRACT <br />® <br />DUCT MOUNTED SMOKE DETECTOR <br />GENERAL NOTES <br />L POWER WIRING, CONDUIT, SWITCHES AND TIME <br />CLOCKS SHALL BE FURNISHED AND INSTALLED <br />BY ELECTRICAL CONTRACTOR. <br />2. LOW VOLTAGE WIRE AND CONDUIT SHALL BE <br />FURNISHED & INSTALLED BY ELECTRICAL CON- <br />TRACTOR. FINAL CONNECTIONS BY AIR CONDI- <br />TIONING CONTRACTOR. <br />3. CONDENSATE DRAIN PIPING (COPPER OR GALV.) <br />TO AN APPROVED RECEPTOR BY PLUMBING CON- <br />TRACTOR. CONDENSATE DRAIN TO BE TRAPPED. <br />SEE DETAIL. <br />4. GENERAL CONTRACTOR SHALL FURNISH AND /OR <br />INSTALL CUTTING, PATCHING, FRAMING, ROOF- <br />ING, PAINTING, EQUIPMENT SCREENING, CURBS, <br />OR PLATFORMS WITH THE REQUIREMENTS OF <br />THE AIR CONDITIONING SYSTEM. <br />5. EQUIPMENT, INSTALLATION AND OPERATION <br />SHALL BE IN ACCORDANCE WITH ALL <br />APPLICABLE CODES. <br />6. ALL A/C SYSTEMS SHALL BE TESTED AND BALANCED <br />IN ACCORDANCE WITH AA13C GUIDELINES. THE T & B <br />CONTRACTOR SHALL NOTIFY MECH. CONTRACTOR OF <br />ANY DEFICIENCY IN THE SYSTEMS AND HAVE THEM <br />CORRECTED PRIOR TO FINAL APPROVAL & START UP OF <br />A/C SYSTEMS. THE PROPER AMOUNT OF OSA SHALL <br />COMPLY WITH T-24 CALCULATIONS. <br />AC32 <br />TITLE 24 NOTES <br />TITLE 24 FOR AC ENERGY CONSERVATION <br />1, ALL DUCTWORK, INCLUDING INSULATION, SHALL <br />CONFORM TO CALIFORNIA ADMINISTRATIVE CODE, <br />2016 TITLE 24, AND THE CMC LOW VELOCITY DUCT <br />CONSTRUCTION STANDARDS, LATEST 2016 EDITION. <br />2, ALL EXHAUST FANS TO BE FURNISHED WITH BACK - <br />DRAFT DAMPERS. <br />3. ALL AC UNITS SHALL BE PROVIDED WITH A <br />THERMO- STAT FOR AUTOMATIC REGULATION OF <br />TEMPERATURE AND A FOUR HOUR OVERRIDE <br />TIMER.THERMOSTAT AND TIMER SHALL BE <br />READILY ACCESSIBLE AND BE MANUALLY <br />ADJUSTABLE. <br />4. ALL THERMOSTATS SHALL BE CAPABLE OF BEING SET <br />TO MAINTAIN SPACE TEMPERATURE SET POINTS FROM <br />55 DEGREES F. TO 85 DEGREES F. AND SHALL BE <br />CAPABLE OF OPERATING THE SYSTEM HEATING AND <br />COOLING SEQUENCE. <br />5, ALL THERMOSTATS SHALL BE ADJUSTABLE TO <br />PROVIDE A TEMPERATURE RANGE OF UP TO 5 DEGREES <br />F. BETWEEN FULL HEATING AND FULL COOLING AND <br />SHALL HAVE THE CAPABILITY OF TERMINATING ALL <br />HEATING AT A TEMPERATURE NO MORE THAN 70 <br />DEGREES F. AND OF TERMINATING ALL COOLING AT A <br />TEMPERATURE NOT LESS THAN 78 DEGREES F. <br />6. TRANSVERSE JOINTS FOR ALL AIR SUPPLY DUCTS <br />INSTALLED WHERE AIR LEAKAGE WOULD BE NON- <br />BENEFICIAL TO THE OCCUPIED AREA TEMPERATURE <br />REQUIREMENTS SHALL BE SEALED WITH APPROVED <br />MASTIC OR TAPE. <br />7, A MAINTENANCE LABEL SHALL BE AFFIXED TO <br />MECHANICAL EQUIPMENT AND A MAINTENANCE <br />MANUAL SHALL BE PROVIDED FOR THE OWNERS USE. <br />AC12 <br />Z <br />0 <br />W <br />�r <br />w a) <br />� C <br />N C 7 <br />E <br />00 U <br />fa) z c c <br />W g <br />ca <br />y <br />-�..+ N N p <br />.. 1p <br />J co 0) <br />06 O a) <br />CL r F, U C <br />C% NAV N <br />L 6 .m (L O <br />-a C CL <br />mI�cE <br />-aM CJS <br />C <br />2 00 <br />d CN <br />U N y <br />(D N N MC N <br />�... _J C O <br />00 c rn <br />r@ <br />C) �a aa)iUm <br />B <br />V) <br />J <br />W <br />Q <br />Q <br />Z <br />Q <br />W <br />O <br />Z <br />W <br />Q <br />W <br />i <br />WU <br />J <br />(Joe) <br />F <br />F <br />ui <br />Z <br />VJ <br />W <br />WC Of � <br />GF- <br />WCN <br />Lo <br />Q <br />ryryU <br />�OZ <br />-jO <br />zVU <br />wz0 <br />' <br />C/) <br />�M <br />W <br />`ZD`^ <br />VJ <br />C) <br />W <br />O <br />d <br />DATE: 02/02/2017 <br />JOB: PT -ST -05 <br />DWG BY: KS <br />CHK BY: APV <br />M1 <br />