Laserfiche WebLink
The following is an itemized list of aboveground petroleum storage act violations that <br /> have not been addressed for A L POWELL TRUCKING as of December 13, 2021. <br /> Open violations from October 04, 2021 inspection <br /> Violation#105-Failed to properly close tanks under the definition of"Permanently Closed". <br /> OBSERVATION: 250 gallon kerosene and 100 gallon fuel tank(on the side of the shop)is not in use but has not <br /> been properly closed. Tanks are empty and do not have a sign that stated "permanently closed"and with a date. <br /> REGULATION GUIDANCE: When a tank is not in use, it must be permanently closed by meeting the following <br /> conditions: <br /> -remove all liquid and sludge from each container and connecting line <br /> -disconnect and blank off all connecting lines and piping have from the tank/container <br /> -close and lock all valves <br /> -post a sign conspicuously stating that it is a permanently closed container and denoting the date of closure. <br /> CORRECTIVE ACTION: Tanks that are not being used or are not addressed in the Spill Prevention, Control, and <br /> Countermeasure(SPCC)Plan must either be included in your plan or meet the permanent closure requirements <br /> noted above. Provide verification to the EHD of proper closure of the tanks. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> Page 1 of 6 <br />