<br /> ROOFTOP HVAC UNITS (GAS HEAT) AIR BALANCE
<br /> COOLING CAPACITY @ DESIGN CONDITIONS HEATING CAPACITY ® DESIGN CONDITIONS ELECTRICAL GHT SOURCE Architecture / Development
<br /> UNIT
<br /> ZONE/AREA
<br /> &NMO MODEL NO TONNAGE CFM HP RER NOMINAL OUTSIDE�AIR (OA) ESP SENSIBLE (NET) TOTAL (NET) INPUT OUTPUT % EFFICIENCY VOLT/PH/HZ M.C.A MOCP (@ ARI CONDITIONS WE GHT (LBS) WITH CURBT UNIT EI(INCHES) REMARKS EA OA SA RA
<br /> (INCH) KBTU/H KBTU/H )
<br /> 14901 Quorum Drive
<br /> 1,2,4,5,7-9,11-18,19,20 EF-1 RR KITCHEN 550 __ __ __ Suite 300
<br /> Al DINING CARRIER 48HC09 8.5 3400 2.81 1000 1.0 88.5 100.4 180.0 148.0 82 208/3/60 45.0 50 12.0 925 59.375 / Dallas Texas 75254
<br /> EF-2 ONION EXHAUST 250 -- -- -- Ph: (972)239-8884
<br /> 2 CARRIER 8.5 3400 2.81 1000 1.0 88.5 100.4 180.0 148.0 82 208/3/60 45.0 50 12.0 925 59.375 1,2,4,5,7-9,11-18,19,20 EF-3 FRYER HOOD 985 -- -- -- Fax: (972)239-5054
<br /> 2 DINING 48HC09 __ __ __
<br /> EF-4 GRIDDLE HOOD 585
<br /> AC CARRIER 20.0 8000 5.0 2000 1.0 177.0 223.6 220.0 178.0 81 208/3/60 98.4 125 12.0 2247 58.25 1,2,4,5,7-9,11-18,20 EF-5 GRIDDLE HOOD 585 -- -- --
<br /> ISSUE RECORD
<br /> 3 KITCHEN 48HC24 EF-6 GRIDDLE HOOD 585 -- -- -- DATE DESCRIPTION
<br /> REMARKS
<br /> AC-1 DINING ROOM -- 1000 3400 2000 URBAN DESIGN PROTOTYPE 1. NEW MFG MODEL UNIT W/R410A REFRIGERANT. 11. 100% ECONOMIZER-X W/ ENTHALPY CONTROL (HIGH LIMIT: Hon > 28 BTU/LB) AC-2 DINING ROOM -- 1000 3400 2000 7-10-2020 ISSUED FOR PERMIT
<br /> 2. 14" ROOF CURB 12. BAROMETRIC RELIEF DAMPER W/POWERED EXHAUST AC-3 KITCHEN -- 2000 8000 6000
<br /> 3. HAIL GUARDS 13. MERV 13 FILTERS TOTAL 3540 4000 14800 10000
<br /> 4. FACTORY INSTALLED DISCONNECT SWITCH. 14. MOTORIZED OUTSIDE AIR DAMPER (CLOSE UPON UNIT DEACTIVATION)
<br /> 5. UNIT MOUNTED WP/GFCI RECEPTACLE (NON-WIRED) 15. S/A DUCT SMOKE DETECTOR (SHALL BE UL 268A COMPLIANT AND INSTALLED PER NFPA 96). ACTUATION SHALL ZONE SUB-TOTAL: DINING ROOM: +2000 CFM
<br /> 6. PREMIUM EFFICIENCY MOTORS ACTIVATE VISIBLE AND AUDIBLE ALARM AT AN APPROVED LOCATION, IDENTIFIED AS AIR DUCT DETECTOR KITCHEN AREA: -1540 CFM (2000 - 3540)
<br /> 7. PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT-MODEL VENSTAR #T4800, PLACED IN OFFICE PER PLAN. TROUBLE OR CONNECTED TO THE BUILDING FIRE ALARM SYSTEM (IF AVAILABLE). PROVIDE WITH REMOTE BUILDING IS 460 CFM POSITIVE
<br /> 8. HUMIDITY CONTROL (HOT GAS REHEAT) TEST/RESET STATION WITH LED INDICATOR, CEILING MOUNTED.
<br /> 9. REMOTE, NON-ADJUSTABLE, TEMPERATURE, CO2 AND HUMIDITY (HUMIDITY CONTROL/HOT GAS REHEAT OPTION 16. ALL UNITS SHALL SHUT DOWN UPON DETECTION OF ANY SMOKE IN THE SUPPLY AIR DUCT. REFERENCE FAN
<br /> ONLY) SENSOR MODEL SENVA AQW. CONTROL SCHEMATIC ON SHEET E8.0
<br /> 10. DISCHARGE AIR TEMPERATURE CONTROL 17. GAS FLUE DEFLECTOR MINIMUM EXHAUST S C H E D U L E
<br /> 18. ALL RTU's SHALL BE AUTOMATICALLY ACTIVATED WHEN THE KITCHEN EXHAUST FANS ARE INITIATED. REVISION RECORD
<br /> 19. DEMAND CONTROL VENTILATION WITH CO2 SENSOR.
<br /> 20. ECONOMIZERS ARE TO INCLUDE FAULT DETECTION AND DIAGNOSTICS. AREA, Az EXHAUST RATE REQ. EXHAUST, CFM EXHAUST
<br /> AREA SERVED UNIT N0. SQ. FT. CFM/SQ. FT PER CMC** PROVIDED, CFM
<br /> EXHAUST FANS DRESSING ROOMS 151 0.25 38 100
<br /> RESTROOMS* EF-1 352 70 420 450
<br /> UNIT MANUFACTURER ZONE/AREA AIRFLOW ESP SPEED ELECTRICAL OPER. WT.
<br /> NO. & MODEL NO. SERVED LOCATION TYPE (CFM) (INCH) (RPM) VOLTS/PH/HZ HP (LBS) REMARKS EF-2
<br /> EF-3
<br /> EF COOK 100ACRUB ROOF RESTROOMS & CENTRIFUGAL 550 .5 1494 120/1/60 1/6 82 2,3,4,5,9,11,12,13 KITCHEN AREA EF-4 1740 - - 2990
<br /> 1 DRESSING ROOMS EF-5
<br /> EF COOK 100ACRUB ROOF ONION EXHAUST CENTRIFUGAL 250 .5 1494 120/1/60 1/6 82 1.4,9,11,12,13 EF-6
<br /> 2 * RATE CALCULATED PER FIXTURE
<br /> EF CENTRAL RE-12 ROOF FRYER HOOD CENTRIFUGAL 985 1.3 1878 208/3/60 1 240 1,4,6-14 ** CALCULATED PER 2019 CALIFORNIA MECHANICAL CODE, SECTION 403
<br /> 3
<br /> EF 4 CENTRAL RE-12 ROOF GRIDDLE HOOD CENTRIFUGAL 585 1.4 1676 208/3/60 1 240 1,4,6-13 MINIMUM OUTSIDE AIR SCHEDULE
<br /> :AL
<br /> EFAREA, Az CALCULATED REQ. OA, CFM OUTSIDE AIR
<br /> FSS/p
<br /> 5 CENTRAL RE-12 ROOF GRIDDLE HOOD CENTRIFUGAL 585 1.4 1676 208/3/60 1 240 1,4,6-13 AREA SERVED UNIT N0. SQ. FT. OCCUPANCY PER CMC* PROVIDED, CFM
<br /> �p R.
<br /> EF CENTRAL RE-12 ROOF GRIDDLE HOOD CENTRIFUGAL 585 1.4 1676 208/3/60 1 240 1,4,6-13AC-1 F z
<br /> 6 DINING ROOMS AC-2 1470 103 1036 2000 m
<br /> EF No. M29234 a
<br /> BROAN 506 TOWER TOWER WALL CENTRIFUGAL 470 .10 - 120/1/60 .083 20 12, 15 KITCHEN** AC-3 1587 32 525 2000 * Exp. 06/30/21
<br /> 7
<br /> REMARKS �TgTFOFHAA F N\0' \P
<br /> 1. FAN, ROOFCURB, AND WEATHER COVER FURNISHED BY KITCHEN EQUIPMENT SUPPLIER. 7. FANS PROVIDED WITH CAPACITOR ASSISTED MOTORS. * CALCULATED PER 2019 CALIFORNIA MECHANICAL CODE, SECTION 403 AND EQUATION 4-1 Vbz = RpPz + RQAz. 0/14/20
<br /> 2. CENTRIFUGAL FAN WITH BIRDSCREEN AND BACKDRAFT DAMPER PROVIDED BY CONTRACTOR. 8. FANS PROVIDED WITH GREASE RESERVOIR. ** THIS AMOUNT IS PROVIDED BY AC-3. TOTAL MAKE-UP AIR FOR KITCHEN IS PROVIDED VIA DIRECT OUTSIDE AIR (FROM AC-3) AND
<br /> 3. PROVIDE WITH ROOF CURB. 9. MAINTAIN 10' OF CLEARANCE BETWEEN EXHAUST DISCHARGE AND ANY OUTSIDE AIR INTAKE. TRANSFER FROM DINING ROOM (FROM AC-1 AND AC-2) AS REQUIRED TO REPLACE AIR EXHAUSTED BY EXHAUST FANS. SEE AIR BALANCE
<br /> 4. FURNISH NEMA 3R FACTORY DISCONNECT. REFERENCE SHEET E6.0 FOR MOUNTING/INSTALLATION. COORDINATE WITH 10. EXHAUST FANS SERVING TYPE 1 HOODS ARE DESIGNED TO AUTOMATICALLY ACTIVATE WHEN COOKING OPERATIONS ON THIS SHEET FOR DETAILS.
<br /> ELECTRICAL SCOPE. OCCUR.
<br /> 5. INTERLOCK WITH RESTROOM LIGHTS (REFERENCE ELECTRICAL PLANS). 11. REFERENCE E8.0 FOR FAN CONTROL SCHEMATIC(S).
<br /> 6. UL762 LISTED. 12. COORDINATE ELECTRICAL REQUIREMENTS INCLUDING CABLING AND CONDUIT WITH ELECTRICAL PLANS.
<br /> 13. REFERENCE AIR BALANCE SCHEDULE ON M2.0 FOR AIRFLOWS. kILr t M
<br /> 14. PROVIDE FAN WITH SIDE INLET CURB.
<br /> 15. REFERENCE SHEET E6.0 FOR WIRING DIAGRAM AND CONTROL. engineering consultants
<br /> 14901 Quorum Dr. #565 Dallas, TX 75254
<br /> rtmassociates.com 1972.387.3500
<br /> HEATER SCHEDULE 20.GHAA.027
<br /> PROTOTYPE VERSION
<br /> ELECTRICAL 16U.2.61
<br /> UNIT MANUFACTURER LOCATION DIMENSIONS HEAT OUTPUT OPER. WT. REMARKS
<br /> NO. & MODEL NO. (BTUH) VOLTS/PH/HZ AMPS (LBS) PROJECT NAME
<br /> MARKEL IN-N-OUT
<br /> WCH 6300 SERIES RISER ROOM 33X25X9-1/2 17,100 208/1/60* 25 99 1,2
<br /> 1 5KW HEATER I I I I I I IBURGER
<br /> 1. PROVIDE WITH THERMOSTAT. * COMES FIELD WIRED AS A 3-PHASE UNIT, CAN BE FIELD CONVERTED TO SINGLE PHASE
<br /> 2. PROVIDE ALL HARDWARE REQUIRED TO SAFELY MOUNT HEATER. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
<br /> STOCKTON
<br /> AIR CURTAIN SCHEDULE
<br /> CALIFORNIA
<br /> UNIT
<br /> NO &NMO MODELRER NO SOUND(dBA) ELECTRICAL OPER. WT. REMARKS
<br /> T. 5202 PACIFIC AVE
<br /> LOCATION DIMENSIONS
<br /> VOLTS/PH/HZ AMPS ( B
<br /> FAC SAVE-T REAR DOOR 10"H X 8.5"D X 48"W 53 208/230/1/60 5.0 130 1,3,4,5 STOCKTION, CA 95207
<br /> 1 IBD-2-48-1-SS
<br /> FAC SAVE-T PAY/PICK-UP 10"H X 8.5"D X 25"W 49 115/1/60 2.4 24 2,3,4,5
<br /> 2&3 IBD-2-25-1-SS WINDOWS
<br /> REMARKS 3. PROVIDE ALL HARDWARE AND ACCESSORIES NECESSARY FOR OPERATION.
<br /> 1. PROVIDE DOOR LIMIT SWITCH AND MOTOR CONTROL PANEL. MOUNT SWITCH TO TURN AIR CURTAIN ON AS DOOR OPENS. 4. INSTALL UNITS WITHOUT OBSTRUCTION TO AIRFLOW.
<br /> 2. PROVIDE WITH NORMALLY CLOSED LIMIT SWITCH. MOUNT SWITCH TO TURN AIR CURTAIN ON AS WINDOW BEGINS TO OPEN. 5. AIR CURTAINS ARE SUPPLIED BY KITCHEN SUPPLIER FOR INSTALLATION BY CONTRACTOR.
<br /> NoNmOUT
<br /> FAN COIL UNITS 11LBURGER®
<br /> GOD BLESS AMERICA
<br /> UNIT DESIGN CONDITIONS ELECTRICAL
<br /> ZONE/AREA MANUFACTURER LOCATION AIRFLOW (CFM) SOUND DIMENSIONS CAPACITY S.E.E.R OPER.
<br /> N0. SERVED & MODEL NO. LO-MID-HI (DBA) WxDxH (INCHES) COOLING KBTU/H KBTU/H HEATING VOLT/PH/HZ M.C.A MOCP (© ARI CONDITIONS) WEIGHT (LBS) REMARKS
<br /> FC MIS DAIKIN MIS 39x11-5 8x10-3 8 24.0 25.2 * * * 15.0 27 2,3,5,6 PROJECT NUMBER
<br /> 1 ROOM FTX24NMVJU ROOM 491-579-713 39-45-51 / /
<br /> (91
<br /> MIs 190955
<br /> DAIKIN ROOF 2609 59 37-9/16x14-1/4x28-15/16 N/A N/A 208/1/60 18.3 20 N/A 97 1,3,4,5,6
<br /> ROOM RX24NMVJU
<br /> SHEET TITLE
<br /> REMARKS * INDOOR UNITS RECEIVE POWER FROM OUTDOOR UNITS THROUGH
<br /> 1 . PROVIDE SEACOAST PROTECTION (OPTION BS) ON OUTSIDE UNITS LOCATED WITHIN 2 MILES OF A COAST. FIELD-SUPPLIED INTERCONNECTED WIRING. MECHANICAL
<br /> 2. PROVIDE WALL-MOUNTED TEMPERATURE DISPLAY AND TEMPERATURE CONTROLLER. EQUIPMENT
<br /> 3. SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATIONS.
<br /> N 4. PROVIDE LOW AMBIENT KIT IN CLIMATES WITH 99.6% ASHRAE DESIGN HEATING TEMPERATURE BELOW 40°F. SCHEDULES
<br /> Z1 5. PROVIDE ALL HARDWARE AND ACCESSORIES NECESSARY FOR PROPER INSTALLATION.
<br /> w o 6. PIPING INSTALLATION: REFRIGERANT PIPING MATERIAL: FACTORY CLEANED AND CHARGED, ACR COPPER TUBING (TYPE L) WITH
<br /> w N ENDS CAPPED TO PROTECT CLEANLINESS OF INTERIOR, CONFORMING TO ASTM B 280. FITTINGS: WROUGHT-COPPER JOINTS
<br /> w MAY BE FLARED UNLESS PROHIBITED BY AHJ. IF NOT PERMITTED, USE BRAZED JOINTS. BRAZING FILLER METALS: AWS A5.8, SHEET NUMBER
<br /> C:) SUITABLE FOR ACR PIPING. SUPPORT PIPING PER MSS STANDARD SP-69. PROVIDE ADDITIONAL SUPPORT AT ELBOWS AND FITTINGS.
<br /> m INSULATE WITH 3/4" ARMSTRONG "ARMAFLEX" CLOSED CELL, ELASTOMERIC INSULATION. PROTECT INSULATION AT HANGER SUPPORTS
<br /> 0 o WITH SHIELDS.