Laserfiche WebLink
I the spill container empty. <br /> 2 pp. Defendants shall install all underground piping that is in contact with <br /> 3 hazardous substances, under normal operating conditions, within a secondary containment system as <br /> 4 required by California Code of Regulations, title 23, section 2636(c)(1). <br /> 5 qq. Defendants shall at all times (other than when the secondary containment <br /> 6 is being tested) ensure that boots at turbine sumps, transition sumps and piping sumps are properly <br /> 7 placed so that piping drains to a monitored sump as required by California Code of Regulations, title <br /> 8 23, sections 2631 and 2636. <br /> 9 rr. Defendants shall install and maintain automatic line leak detectors on all <br /> 10 underground pressurized piping as required by California Code of Regulations, title 23, section <br /> 11 2636(f)(2). <br /> 12 ss. Defendants shall have a means for monitoring water intrusion by <br /> 13 precipitation or infiltration into the secondary containment as required by California Code of <br /> 14 Regulations, title 23, section 2630(d) and Health and Safety Code section 25291(e). <br /> 15 tt. Upon discovery, Defendants shall remove any liquid or debris that has <br /> 16 accumulated in spill buckets and secondary containment systems pursuant to the maintenance and <br /> 17 operating requirements contained in California Code of Regulations, title 23, sections 2630(4), <br /> 18 2631(d)(4),2632(d)(2) and 2635(c)(6). <br /> 19 uu. Defendants shall institute a program for the regular inspection and <br /> 20 maintenance of spill containment structures("spilI buckets") and under-dispenser containment areas <br /> 21 ("spill boxes"). The program shall require documented inspections at least monthly, and that any <br /> 22 accumulation of liquid or debris discovered during these inspections is promptly removed and the <br /> 23 source of liquid or debris addressed. Defendants shall ensure that their employees comply with the <br /> 24 spill bucket and spill box inspection and maintenance once instituted. <br /> 25 w. Defendants shall insure that each container, receptacle, pump, dispenser <br /> 26 and inlet end of the fill pipe of each underground storage tank is properly labeled with the name of <br /> 27 the product, the brand, the trademark, the trade name, and the grade and brand name at any location <br /> 28 where Defendants sells fuel, pursuant to the requirements of Business and Professions Code 13480. <br /> to <br /> Hassan &Sons,Inc.,et al. [Proposedl Final Judgment and Permanent Injunction <br />