ELECTRICAL SPECIFICATIONS ELECTRICAL SPECIFICATIONS (CONT.) <br /> GENERAL NOTES: <br /> 1. ELECTRICAL INSTALLATION SHALL COMPLY WITH TITLE 24, CALIFORNIA GROUNDING: <br /> CODE OF REGULATIONS, INCLUDING THE FOLLOWING: <br /> TITLE 24, CCR, PART 2, 2013 CBC 1 . GROUND AND BOND ALL EQUIPMENT AS REQUIRED BY GOVERNING CODES AND <br /> TITLE 24, CCR, PART 3, 2013 CEC SPECIFICALLY INCLUDING SWITCHBOARD, PANELBOARDS, MOTOR CASES, ETC. <br /> TITLE 24, CCR, PART 4, 2013 CMCA�, <br /> BENJAMIN HOLT DRIVE <br /> TITLE 24, CCR, PART 9, 2013 CFC WORKING CLEARANCES FOR PANELS & SWITCHBOARDS <br /> ALL APPLICABLE LOCAL CODES. 1 . COORDINATE WITH OTHER TRADES TO ENSURE CODE REQUIRED WORKING I APEX <br /> 2. ELECTRICAL CONTRACTOR SHALL PROCURE AND PAY FOR ALL LICENSES, <br /> CLEARANCES, ACCESS, ETC. FOR PANELS AND SWITCHBOARDS PER C.E.C. I ARCHITECTURE ETC. REQUIRED TO CARRY ON AND COMPLETE THE WORK. PERMIT BY OWNER. SECTIONS 110-16 AND 384-4. I <br /> PANELBOARDS: 1325 EI Pinal Drive, Suite D4 <br /> 3. PROVIDE ALL LABOR, MATERIALS, TOOLS, PLANT EQUIPMENT, - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - <br /> TRANSPORTATION AND PERFORM ALL OPERATIONS NECESSARY FOR ANY REASONABLE UNITS SHALL BE FLUSH OR SURFACE MOUNTED AS INDICATED ON THE PANEL I Stockton, CA. 95205 <br /> INCIDENTAL TO PROPER EXECUTION AND COMPLETION OF ALL "ELECTRICAL WORK" SCHEDULE, WITH THE NUMBER AND SIZE OF BREAKERS INDICATED ON THE (209) 662-4874 <br /> PANEL SCHEDULE. SINGLE POLE, TWO POLE AND THREE POLE BREAKERS SHALL I <br /> WHETHER SPECIFICALLY MENTIONED OR NOT; ALL AS INDICATED, SPECIFIED � (e) SIGN TO apexplanning@hotmail.com <br /> HEREIN, AND/OR IMPLIED THEREBY TO CARRY OUT THE APPARENT INTENT BE BOLT-ON TYPE. THE PANEL DOORS SHALL HAVE FLUSH TYPE LOCKS, ALL I REMAIN <br /> THEREOF. LOCKS SHALL BE KEYED ALIKE AND HAVE TYPEWRITTEN DIRECTORIES INDICATING <br /> FIXTURES, EQUIPMENT, OR OUTLETS SERVICED BY EACH BREAKER. ALL BUSSING REMAIN SIGN TO <br /> N <br /> SHALL BE COPPER. REMAII Steven Anthony4. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED WITH THE Torres II <br /> UNDERWRITERS' LABORATORIES, INC., SHALL MEET THEIR REQUIREMENTS AND TESTING: Architect # C32553 <br /> SHALL BEAR THEIR LABEL WHEREVER STANDARDS HAVE BEEN ESTABLISHED AND <br /> LABEL SERVICE IS REGULARLY FURNISHED BY THAT AGENCY. <br /> 1 . THE ENTIRE ELECTRICAL INSTALLATION SHALL BE FREE FROM SHORT CIRCUITS <br /> TEST ALL WIRING AND CONNECTIONS FOR CONTINUITY <br /> 5. ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH THE AND IMPROPER GROUNDS. I � �� ❑ ❑ � � <br /> AND GROUNDS BEFORE ANY FIXTURES OR EQUIPMENT ARE CONNECTED AND WHETHER SUCH <br /> SIZE AND LOCATIONS OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER POSSIBLE, TESTS INDICATE FAULTY INSULATION OR OTHER DEFECTS, THEY SHALL BE LOCATED, ' <br /> CONTRACTOR SHALL MAKE USE OF ALL DATA IN ALL CONTRACT DOCUMENTS AND REPAIRED AND RETESTED AT THE CONTRACTOR'S EXPENSE. I � � PROPERTY OWNER <br /> VERIFY THIS INFORMATION AT THE SITE. CONTRACTOR SHALL BE RESPONSIBLE I <br /> FOR LAYING OUT AND INSTALLING HIS WORK TO AVOID INTERFERENCE WITH 2. DEMONSTRATE TO THE OWNER AND THE ARCHITECT, THAT THE ENTIRE I I LAWRENCE WIGHT <br /> OTHER TRADES. <br /> INSTALLATION IS COMPLETE, IN PROPER OPERATING CONDITION AND THAT THE <br /> CONTRACT HAS BEEN PROPERLY AND FULLY EXECUTED. PROVIDE ALL INSTRUMENTS <br /> 6. CONDUCTORS SHALL BE COPPER CONDUCTORS TYPE THWN UNLESS OTHERWISE TO MAKE SUCH TESTS. <br /> NOTED OR REQUIRED BY CODE. <br /> 7. ALL LUMINAIRES AND BALLASTS SHALL BE CERTIFIED BY THE MANUFACTURER <br /> TO THE CALIFORNIA ENERGY COMMISSION. ALL FLUORESCENT FIXTURES TO BE <br /> LAMPED WITH F032, T8, 3500K LAMPS OR APPROVED EQUAL, AND HAVE AN ENERGY I CONTRACTOR <br /> SAVING "A" SOUND RATING ELECTRONIC BALLAST OR APPROVED EQUAL UNLESS <br /> OTHERWISE SHOWN. ALL H.I.D. LIGHT FIXTURES SHALL HAVE HIGH POWER FACTOR - ---------------- I <br /> � BOB LEONARD AND ASSOC. <br /> BALLASTS. I o I I 1325 EL PINAL DRIVE, SUI D-4 <br /> 8. FLASH AND COUNTER FLASH ALL ITEMS PASSING THROUGH THE ROOF. I I I ❑ ❑ STOCKTON, CA. 95205 <br /> ANY ROOF PENETRATIONS WILL BE APPROVED BY THE OWNER. ROOFING MFG. I <br /> HAS SPECS. AS TO NOT VOID 20 YEAR WARRANTED. I o I I <br /> I <br /> 9. WORK SHOWN ON THE DRAWINGS TO BE INSTALLED UNDERGROUND SHALL BE I <br /> INSTALLED AT LEAST 24" BELOW GRADE. BACKFILL IN 6" THICK, PROPERLY I <br /> MOISTENED LAYERS, SOLIDLY PACKED AND IRON TAMPED TO A DENSITY NOT I o <br /> LESS THAN THAT OF ADJACENT, UNDISTURBED EARTH. RESTORE SURFACES, I <br /> ROADWAYS, WALKS, CURBS, WALLS, EXISTING UNDERGROUND INSTALLATIONS TO I <br /> ORIGINAL CONDITION IN AN ACCEPTABLE MANNER. I I I I IMPROVEMENT UNDER <br /> 10. THE OWNER RESERVES THE RIGHT TO RELOCATE ALL LIGHTING, OUTLETS AND I I I THIS PROJECT <br /> i o i <br /> SWITCHES BEFORE THEY ARE ROUGHED IN AT NO EXTRA COST. I <br /> 11 . ALL EXIT SIGNS TO BE UNSWITCHED. PI IPO I o ° --- -! -- --- --------+- I <br /> NAMEPLATES & IDENTIFICATION: I Fu� RAS F1 <br /> INSTALL ENGRAVED NAMEPLATES FOR EACH PANELBOARD, CABINET, DISCONNECT, � 11, 00 ARCO CONVENIENCE� I I COORDINATE W/ PG&E TO <br /> ETC. NAMEPLATES SHALL BE SECURELY FASTENED TO THE EQUIPMENT WITH I I I I I UPGRADE TRANSFORMER. I STORE REMODEL <br /> #4 PHILLIPS ROUND HEAD CADMIUM PLATED SELF-TAPPING SCREWS, BRASS <br /> BOLT, OR WITH A PLASTIC RESIN ADHESIVE GLUE, GOODYEAR "PLIEBOND" OR EQUAL. i i I EXISTING I El 2908 Benjamin Holt Drive <br /> BUILDING TO I Q Stockton, CA. 95207 <br /> HVAC UNIT DISCONNECTS: I I I REMAIN = <br /> — I D <br /> 1. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL CONTRACTOR I PROVIDE A RENTAL o <br /> FOR EXACT LOCATIONS OF ALL HVAC UNITS, DISCONNECTS AND DEVICES IN FIELD. I I I o I - GENERATOR TO POWER } <br /> VERIFY AND CONFIRM THE ACTUAL MOUNTING LOCATION ON THE HVAC UNIT FOR THE I I I I _- - PANELS A,B,C DURING <br /> DISCONNECT. I I o SERVICE REPLACEMENT TO I <br /> I I I O I KEEP STATION OPERATIONAL. <br /> 2. THE RATING OF THE DISCONNECT SHALL BE SUCH AS TO ENABLE THE LARGEST >004 <br /> I <br /> FUSE SIZE ON THE UNIT NAMEPLATE TO BE INSTALLED IN THE DISCONNECT. PROVIDE I I I RELOCAT� O I <br /> FUSES OF THIS RATING. XXX <br /> VAPOR I >004I <br /> 3. FURNISH AND INSTALL ALL LINE VOLTAGE AND LOW VOLTAGE CONDUITS AND i i I SYSTEM o I /001 ❑ <br /> LINE VOLTAGE WIRING (LOW VOLTAGE WIRING BY OTHERS) TO HVAC EQUIPMENT ANDI I WALK IN COOLER I <br /> ASSOCIATED CONTROLS AND DEVICES AS SHOWN ON THE ELECTRICAL AND MECHANICAL <br /> PLANS, UNLESS OTHERWISE NOTED. I I INTERCEPT FUTURE VACCUM T <br /> I I <br /> WIRING METHODS: I o I CIRCUITEXTENNEW <br /> I i �— � I 1—:17 ❑ <br /> 1. ALL WIRING SHALL BE INSTALLED IN STEEL CONDUITS, CONCEALED IN WALL ���� �� VAPOR SYSTEM LOCATION <br /> AND CEILING U.O.N. I o I o o AIR I NEW MAIN SERVICE 3)5"C I <br /> II LPL WATER PL <br /> 2. MINIMUM CONDUIT SIZE SHALL BE 1/2". MINIMUM ACCEPTABLE CONDUITS i (STUB FOR FUTURE­0­[—i—�— — ——— —— — ——— — ,—— — ——————— J 1200A-120/208V, 30, 4W <br /> ARE I <br /> A. GALVANIZED RIGID STEEL. I o <br /> B. GALVANIZED STEEL EMT. I I 2)4"C0 1"C 1"C ELECTRICAL SITE PLAN o <br /> C. LIQUID TIGHT STEEL FLEX - FOR FINAL CONNECTION TO OUTDOORI I F _ _ _ _ _ _ _ _ _ - - - - - 2 <br /> EQUIPMENT. \ 3/4"C– 2#12+1#12 GND <br /> D. FLEXIBLE STEEL CONDUIT - FOR INDOOR FINAL CONNECTIONS TO I <br /> MECHANICAL EQUIPMENT (NOT TO EXCEED 36"). I I i ; ;-RECONNECT TO ORIGINAL `� �i a <br /> \ i -CIRCUIT. �\ ,, � i � <br /> E. PVC CONDUIT SCHEDULE 40, UNDERGROUND. I I FUTURE , o <br /> �;- - - - - - - - <br /> 3. MC CABLING SYSTEM IS ALLOWED IN THIS BUILDING. - - - - - - - - - - - - - - - - - - - - - - - <br /> Q <br /> 0) <br /> I I Q <br /> WIRING DEVICES: I <br /> l i ;� � � i � I i �SEA RC / o <br /> UNITS SHALL BE EQUAL TO THE DEVICES SET FORTH HEREIN, IN STANDARD I I �, A <br /> COLORS (BROWN, WHITE, GREY, BEIGE OR IVORY) AS SELECTED BY THE i I `i- _ _ _ _ _ _ - _ _ _ _ _ _ I ��, �� To�p o <br /> ARCHITECT: -FUTURE� � - - - - - - - - - - - - - - - - - - - - - - - - - - - - - � � <v� ``� O� 75 <br /> A. WIRING DEVICES LEVITON # HUBBELL # P & S # I I I I CAR WASH ENTRY ; -_ <br /> SINGLE POLE SWITCH 1221 1221 20AC1 I I I I - - - - - * LIC# C 32553 � <br /> 3 <br /> THREE WAY SWITCH 1223 1223 20AC3 i I 9T <br /> REN. 3-31-17 <br /> DUPLEX CONV. OUT. 15A 5262 5262 5262 �0 \F <br /> DUPLEX GFI CONV. OUT. GF5262 I ( ,,- - - - - - - - - - - - - - - - - - - - - F CA\- i <br /> DEVICE PLATES: \ <br /> 1. ALL DEVICE PLATES FOR INDOOR USE SHALL BE SMOOTH NYLON OR APPROVED I \� - ' ' ,'' N <br /> EQUAL UNLESS OTHERWISE NOTED. ALL DEVICE PLATES FOR OUTDOOR USE SHALL I \ ( - - -- ��- - - - - - - - - - - - - - - - - - - - - REV.# DATE ISSUED DESCRIPTION <br /> BE RAISED METAL. I \ - - I N <br /> 1 7/2/2019 OWNER CHANGES 0 <br /> 2. DEVICE COVERS FOR SURFACE MOUNTED BOXES SHALL BE 1/2" RAISED STEEL <br /> PLATES. WEATHERPROOF COVERS TO BE SNAP TYPE COVERS. I �� <br /> 3. DEVICE PLATES FOR TELEPHONE AND COMPUTER OUTLETS TO BE PROVIDED I � <br /> < <br /> BY OWNER'S VENDOR. ALL TELEPHONE AND COMPUTER SYSTEM WIRING BY OWNER'S <br /> VENDOR. <br /> _ c <br /> SUPPORTS: <br /> APEX PROJECT 15-11 x <br /> 1 . FURNISH ALL NECESSARY FOUNDATIONS, SUPPORTS, BACKING, ETC., FORo- <br /> ALL ELECTRICAL ENCLOSURES, CONDUITS AND EQUIPMENT. <br /> 2. ATTACH ALL BOXES, CABINETS, ETC. TO WOOD WITH WOOD OR LAG SCREWS, __- _ NORTH DUMPSTER DATE: 7-2-2019 M <br /> TO METAL WITH MACHINE SCREWS OR BOLTS AND TO CONCRETE WITH EXPANSION o <br /> ANCHORS AND MACHINE SCREWS OR BOLTS. j <br /> ELECTRICAL SITE PLAN <br /> 0 <br /> SCALE: 1"=10'-O" �OFESs� Y <br /> ° C. 5 � HCS ENGINEERING INC. El <br /> No. E14303 CONSULTING ELECTRICAL ENGINEERS `` <br /> * <br /> Exp. 6-30-21 * 4512 FEATHER RIVER DRIVE, SUITE F <br /> s�F� N STOCKTON, CA 95219 (209)478-8270 <br /> CTRX9TFOF CA E-MAIL ADDRESS - richard®hcs-eng.com Copyright APEX <br /> PROJ.-- 2016.171--DES.--BA -ENG.- RCS - <br />