Laserfiche WebLink
PETER MOHL JR., ANW. CHIEF <br /> Attrai of tri ire Pro&ctton jurict <br /> P. 0. BOX 244 <br /> LINDEN. CALIFORNIA 95236 <br /> DECEMBER 14,1 77 <br /> TO: San Joaquin Ccs my Local Health Dist. <br /> 1601 E.Hazelton Ave. <br /> Stockton, Calif. 95205 <br /> RE; Foothill Sanitary Landfill Permit. <br /> Gentlemen: <br /> Listed below are recommendations that we would like to have included in the <br /> proposed solid waste facility permit for the Foothill Sanitary Landfill at 6584 N.Waverly <br /> Rd. The below listed recommendations are basielly the same as the Calif. State Div. of <br /> Forestry's are . The Foothill Sanitary Landfill is within the boundries of the State Div. <br /> of Forestry's responsibility area and therefore the Linden-Peters Rural Fire District is <br /> mostly concerned with the Structural Protection along with personnel property and other <br /> improvements within and with out the Dump Site; <br /> 1. The operational area of the dump, outside the active dump site shall be maintained free <br /> and clear of all flammable vegetation and materials. <br /> 2. Install a 4-inch water main from the main water source to within 150 feet of the active <br /> dumping area. Install in the awter main, stand-pipes of 4" diameter, at intervals not to <br /> exceed 400 feet. These stand-pipes shall extend a minium of 24" above the Ground and will <br /> have a shut-off valve with male National Standard threads, each equipped with a cap. <br /> 3. Have a minium of 500 feet of 1 1/2" cotten jacketed fire hose in serviceable coedit n, <br /> with two nozzles. <br /> 4. Maintain a movable fence along the South side of the landfill with a mesh of no greater <br /> than 1" by I" of "hog wire or cyclone type"to a minuim of 10 feet vertical distance above <br /> the high point of the operating dump area. <br /> 5. Maintain around the South and East sides of the dump operating area, a minuim of 400 foot <br /> clearance of all flammable vegetation and other flammable material. <br /> 6. Maintain around the North and West sides of the dump operating area, a minuim of 150 foot <br /> clearnce of all flammable vegetation and other flammable material. <br /> 7. For the purpose of isolating possiable fires: <br /> (A) The active area will be broken up into cells no greater than 150 feet in length by 50 <br /> to 8 "feet in breadth and be separated by dikes of clean soil for a minium of 8 feet in <br /> width. At the end of each work day, that portion of any cell containing accumulated <br /> rubbish shall be covered with clear soil a minuim of 6 inches and compacted. <br /> 8. Equipment,consisting of the following: <br /> (A) A water tanker in 2211atable condition with a minuim of 2,000 gals and a pump capable <br /> of producing 100 pounds pressure at the 1 1/2" outlet and 100 feet of 1 1/2" pre-conn- <br /> ected cotten jacketed fire hose with a 1 1/2" nozzle <br /> (1) Con't) <br />