Laserfiche WebLink
Underground Storage, I"ank <br />eco Wary Containment ,� estil�c� Report Form <br />8. SUMP/UDC TEST <br />Test Method Developed by ❑ Manufacturer ❑ Industry Standard N Professional Engineer <br />Test Type ❑ Pressure ❑ vacuum N Hydrostatic <br />Test Equipment Used: INCON TS1000-15 MIN. <br />Sump/UDC ID <br />E�85 <br />7/8 <br />9/10 <br />Sump Manufacturer <br />Unknown <br />Unknown <br />Unknown <br />Sump depth (inches) <br />N/A <br />N/A <br />N/A <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />N/A <br />N/A <br />N/A <br />Test Start Time <br />12:48 <br />10:08 <br />11:25 <br />Initial Reading <br />2.2041 <br />2.1878 <br />400783 <br />Test End Time <br />1:03 <br />10:24 <br />11:41 <br />Final Reading <br />2.2041 <br />2.1875 <br />4.0781 <br />Change in Reading <br />0 <br />.0003 <br />.0002 <br />Pass/Fail Criteria <br />0.002 <br />0.002 <br />0.002 <br />0,002 <br />Tightness Test Results <br />® Pass ❑ Fail <br />N Pass ❑ Fall <br />N Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Sump/UDC ID <br />Sump Manufacturer <br />Sump depth (inches) <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />Test Start Time <br />Initial Reading <br />Test End Time <br />Final Reading <br />Change in Reading <br />Pass/Fail Criteria <br />0.002 <br />0.002 <br />0.002 <br />0.002 <br />Tightness Test Results <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Additions/ capias of this page may be attached. <br />Page 4 of 6 <br />