Underground Storage Tank <br /> Overfill Prevention Equipment Inspection Report <br /> 6. OVERFILL PREVENTION EQUIPMENT DETAILS <br /> Tank ID (one OPE per column) T1 Diesel West T2 Diesel East T3 New Oil T4 Waste Oil <br /> Are both vent and tank riser piping ❑x Yes ❑x Yesx❑ Yesx❑ Yes <br /> secondarily contained? ❑ No ❑ No ❑ No ❑ No <br /> OPE Model _ OPW 71 So OPW 61 SO OPW 61 SO Veeder-Root <br /> What is the OPE response when ❑x Shut off ❑x Shut off ❑x Shut off ❑ Shut off <br /> activated? Flow Flow Flow Flaw <br /> (Check all that apply.) ❑x Restricts ❑x Restricts ❑x Restricts ❑ Restricts <br /> Flow Flow Flow Flow <br /> ❑ Audible ❑ Audible ❑ Audible ❑x Audible <br /> Alarm Alarm Alarm Alarm <br /> ❑ Visual ❑ Visual ❑ Visual ❑x Visual <br /> Alarm Alarm Alarm Alarm <br /> Are flow restrictors installed on vent piping ❑ Yes* Yes* ❑ Yes* ❑ Yes* <br /> that may interfere with the OPE operation? ❑x No Q No x❑ No ❑x No <br /> At what level in the tank is the OPE set to 86.5" 81" 83.5" 54" <br /> activate? Inches from bottom of tank <br /> What is the percent capacity of the tank at 94.8 90% 92.3% 90% <br /> which the OPE activates? <br /> Is the OPE in proper operating condition to ❑x Yes Q Yes* ❑x Yes* ❑x Yes* <br /> respond when the stored substance ❑ No ❑ No ❑ No ❑ No <br /> reaches the designated regulatory level? <br /> 7. SUMMARY OF TESTING RESULTS <br /> OPE Inspection Results Z Pass [9 Pass 0 Pass ❑x Pass <br /> El Fail El Fail ❑ Fail El Fail <br /> 8. COMMENTS _ <br /> Describe all answers marked "No"or"Fail"and proposed remedy. <br /> List all monitoring equipment either replaced or repaired. <br /> * Mark here if: <br /> ❑ Flow restrictors interfere with overfill prevention and equipment repairs required. <br /> Additional copies of this page may be attached. <br /> Attach tank chart(s), measurements, calculations, and In-Tank Setup report(s) <br /> Page 2 of 2 <br />