SECTION 230000 - HVAC GENERAL CONDITIONS covers and suitable weather-proof covering. For extended outdoor storage, remove 2.03 SEISMIC RESTRAINTS c. Summary of outdoor and exhaust flows to indicate amount of building
<br /> motors from equipment and store separately. A. Type: Non-directional and double acting unit consisting of interlocking steel pressurization
<br /> RT 1 GENERAL 1.10 WARRANTY AND GUARANTEE members restrained by neoprene elements. d. Nomenclature used throughout report and test conditions.
<br /> A. Submit manufacturer's warranty and ensure forms have been filled out in Owner's B. Elements: Replaceable neoprene, minimum of 0.75 inch thick with minimum 1/8 inch B. Electric Motors and drives: ,►
<br /> 1.01 APPLICABILITY name and registered with manufacturer. air gap. 1. Manufacturer; Model/Frame; HP/BHP; Phase, voltage, amperage; nameplate,
<br /> A. This section supplements all sections of the Specifications for Division 23 and B. Provide one year manufacturer warranty for pumps. C. Capacity: 4 times load assigned to mount groupings at 0.4 inch deflection. actual , no load; RPM; Service factor; Sheave Make/Size/Bore.
<br /> shall apply to all phases of work hereinafter specified, shown on the Drawings, or C. Provide three year manufacturer s warranty for solid state ignition modules. D. Attachment Points and Fasteners: Capable of withstanding 3 times rated load 2. V-Belt Drives: Identification/location; Required driven RPM; Driven sheave,
<br /> required to provide a complete installation of approved HVAC systems. D. Provide five year manufacturer's warranty for compressors, heat exchangers, capacity of seismic snubber. diameter and RPM; Belt, size and quantity; ..
<br /> 1.02 DEFINITIONS condensing units, and electronic air cleaners. C. Cooling and Heating Coils: Vr
<br /> A. "Work" is hereby defined as, "The construction and services required by the PART 3 EXECUTION 1. Identification/number; Manufacturer
<br /> Contract Documents whether completed or partially completed and includes all labor, PART 2 PRODUCTS 2. Air flow, design and actual
<br /> materials, equipment, and services provided or to be provided by the Contractor to 3.01 INSTALLATION 3. Air pressure drop, design and actual
<br /> fulfill the Contractor's obligations. The work may constitute the whole or a part 2.01 SUBSTITUTIONS A. Install in accordance with manufacturer's instructions. 4. Entering and leaving air DB and WB temperature, design and actual
<br /> of the project." A. The manufacturers listed are listed to set minimum standards for quality, design, B. On closed spring isolators, adjust so side stabilizers are clear under normal 5. Water flow, design and actual (if applicable)
<br /> B. "Furnish" is hereby defined as, "To supply and deliver, unload, and inspect for and functionality. The products of other manufacturers may be submitted, at the operating conditions. 6. Water pressure drop, design and actual (if applicable)
<br /> damage." Contractor's option, during shop drawing review unless indicated otherwise. The C. Prior to making piping connections to equipment with operating weights 7. Entering and leaving water temperature, design and actual (if applicable)
<br /> C. "Install" is hereby defined as, "To unpack, assemble, erect, apply, place, finish, products of other manufacturers shall meet or exceed all requirements of the substantially different from installed weights, block up equipment with temporary D. Air Moving Equipment: 0
<br /> cure, protect, clean, connect, and place into operation into the work." Contract Documents. The Contractor accepts all responsibility for costs and shims to final height. When full load is applied, adjust isolators to load to 1. Manufacturer; Model number; Serial number; Arrangement/Class/Discharge
<br /> D. "Provide" is hereby defined as, "To furnish and install ." coordination issues arising out of the substitution of materials or equipment, and allow shim removal . 2. Air flow, specified and actual O 2020 STARBUCKS COFFEE COMPANY
<br /> E. "Connect" is hereby defined as, "To bring service to the equipment and make final the coordination of such substitutions with all other contractors and D. Support piping connections to equipment mounted on isolators using isolators or 3. Inlet; Discharge; Total static pressure (total external ), specified and "KS -
<br /> attachment including necessary ductwork, piping, wiring, etc. subcontractors. resilient hangers to nearest flexible pipe connector. actual S I A K B U C0
<br /> F. "Concealed" is hereby defined as, "Hidden from sight in chases, furred spaces, B. The Contractor may use any of the following ductwork, piping or insulation E. Provide flexible connections on all piping and ductwork connections to equipment. E. Air Distribution Tests:
<br /> shafts, hung ceilings, embedded in construction, in crawl spaces, or buried." materials at his option, provided the selected material meets with the approval of Refer to other sections of this Specification for the acceptable types of flexible 1. Air terminal number 2401 UTAH AVENUE SOUTH
<br /> G. "Exposed" is hereby defined as, "Not installed underground nor concealed as defined all State, local authorities and any utility company requirements. Verification of connectors to be used. 2. Room number/location
<br /> F. 3. SEATTLE, WASHINGTON 98134
<br /> by the Specifications." compliance of the selected material is the sole responsibility of the installing Selection of type, thickness and deflection of vibration isolation shall be by the Terminal type
<br /> H. "Drawings" is hereby defined as, "All plans, details, equipment schedules, Contractor. vibration control manufacturer based on the specific equipment type and size, as 4. Terminal size (206) 318-1575
<br /> diagrams, sketches, etc. issued for the construction of the work." scheduled on the Drawings and indicated below. 5. Area factor
<br /> 1.03 CODES AND STANDARDS PART 3 EXECUTION 3.02 SCHEDULES 6. Design ve I oc i ty THESE DRAWINGS AND THE PROJECT MANUAL
<br /> A. Perform work in accordance with the applicable Building Code, Electrical Code, Fire A. Equipment Isolation Schedule: (Minimum deflection as sized by the isolation 7. Design air flow
<br /> Code, Mechan i ca I Code, P I umb i ng Code, Energy Code, and a I I other app I i cab I e codes, 3.01 COORDINATION OF WORK equipment manufacturer.) 8. Test final ve I oc i ty ARE CONFIDENTIAL AND SHALL REMAIN THE
<br /> amendments, and ordinances. A Iso perform a I I work i n accordance w i th the Americans
<br /> A. Examine the Contract Documents as a who I e for the work of other trades. Coordinate 1. Packaged roof top equipment. 9. Test � i na I � a i r f I ow SOLE PROPERTY OF STARBUCKS
<br /> with Di sob i I i t i es Act (ADA) and the Authority Having Jurisdiction (AHJ) i nc I ud i ng a I I work accord i ng I y. a. Above grade roof structures: 10. Percent of design a i r f I ow CORPORATION,WHICH IS THE OWNER OF THE
<br /> Fire Marsha I(s). B. Prompt I y report to the Architect any de I ay or d i f f i cu I t i es encountered i n the 1. Base: Roof Curb. COPYRIGHT IN THIS WORK. THEY SHALL NOT BE
<br /> B. Perform work i n accordance with Land I ord requirements, i nc I ud i ng any Tenant i nsta I I at i on of the work, which m i ght prevent prompt and proper i nsta I I at i on, or 2. Isolation: Fu I I perimeter Neoprene Pad between curb and units. END OF SECTION REPRODUCED(IN WHOLE OR IN PART), SHARED
<br /> Cr i ter i a Manua I s and Lease Exhibits, where app I i cab I e. make i t unsu i tab I e to connect w i th or receive the work of others. Fa i I ure to so Provide restrained spring v i brat i on i so I at i on curbs when WITH THIRD PARTIES OR USED IN ANY MANNER
<br /> C. Perform work i n accordance with the app I i cab I e ut i I i ty companies serving the report sha I I constitute an acceptance of the work of other trades as being f i t and i nd i Gated on the Drawings. ON OTHER PROJECTS OR EXTENSIONS TO THIS
<br /> project. Make all arrangements with the utility companies for proper coordination proper for the execution of this work.
<br /> of the work.
<br /> C. P Ian, I ay out, and coordinate the work w i th a I I trades we I I enough i n advance so END OF SECTION SECTION 230713 - DUCT INSULATION PROJECT WITHOUT THE PRIOR WRITTEN
<br /> D. Recognized Standards: Design, manufacture, testing and method of i nsta I I at i on of that i t proceeds w i th a m i n i mum of i nterf erence to work that has not been comp I eted CONSENT OF STARBUCKS CORPORATION.
<br /> a I I apparatus and mater i a I s furnished under the requirements of these and work that i s i n progress. Inform a I I trades of openings required for the work PART 1 GENERAL THESE DRAWINGS AND SPECIFICATIONS ARE
<br /> Specifications sha I I conform to the I atest pub I i cat i ons or standard ru I es of and provide a I I spec i a I frames, s I eeves, and anchor bo I is required. The HVAC SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC INTENDED TO EXPRESS DESIGN INTENT FOR A
<br /> Underwriters Laboratories, Inc. (U.L.), American Society for Testing and Mater i a I s system I ayout may be a I tered to su i t the conditions w i th engineer approva I , prior 1.01 SECTION INCLUDES PROTOTYPICAL STARBUCKS STORE(WHICH IS
<br /> (ASTM), American Nat i ona I Standards Institute (ANSI), and Nat i ona I E I ectr i ca I Code to the i nsta I I at i on of any work and w i thout add i t i ona I cost to the Owner. PART 1 GENERAL A. Duct i nsu I at i on. SUBJECT TO CHANGE AT ANYTIME AND DO NOT
<br /> (NEC), National Fire Protection Association (NEPA), American Society of Heating, Conflicts arising from lack of coordination shall be this Contractor's B. Duct liner. )
<br /> Refrigerating and A i r-Conditioning Engineers C. Insu I at i on j ackets. REFLECT ACTUAL SITE CONDITIONS. NEITHER
<br /> Conditioning Contractors' National Association (SMACNA). D. Perform all work in conformity with the Contract Documents and afford other trades A. Testing, adjustment, and balancing of air systems. D. Supply, return or exhaust ducts in ceiling spaces. PARTY SHALL HAVE ANY OBLIGATION NOR
<br /> E. The Contract Documents shall take precedence where the Contract Documents exceed reasonable opportunity for the execution of their work. Properly connect and 1. Air handling units; Packaged heating and/or cooling equipment; Fans. (Exhaust E. Supply, return or exhaust ducts in interior unconditioned areas. LIABILITY TO THE OTHER(EXCEPT STATED
<br /> code, Landlord, utility, or recognized standards requirements. coordinate this work with the work of other trades at such time and in such a and supply); Coils; Terminal equipment; Air inlets and outlets. (Diffusers, F. Supply, return or exhaust ducts in exposed locations. ABOVE) UNTIL A WRITTEN AGREEMENT IS FULLY
<br /> 1.04 PERMITS AND FEES manner as not to de I ay or i nterf ere w i th the i r work.
<br /> grilles, louvers, etc.) 1.02 FIELD CONDITIONS EXECUTED BY BOTH PARTIES.
<br /> A. Permits, licenses, fees, inspections and arrangements required for the work under E. All roofing penetrations shall be flashed and weather sealed by the roofing B. Measurement of final operating condition of HVAC systems. A. Maintain ambient temperatures and conditions required by manufacturers of
<br /> this Contract shall be obtained by the Contractor at his expense, unless otherwise manufacturer's authorized roofing contractor at this Contractor's expense. This C. Independent agency requirements. adhesives, mastics, and insulation cements. STARBUCKS TEMPLATE VE RSION: i2020-01-31.1
<br /> indicated. Contractor shall contract with the factory authorized roofing contractor for the 1.02 SUBMITTALS B. Maintain temperature during and after installation for minimum period of 24 hours.
<br /> 1.05 CONTRACT DRAWINGS specific roofing system applicable to this Project. The use of an unauthorized A. Qualifications: Submit name of adjusting and balancing agency and TAB supervisor
<br /> A. The Contractor is responsible to obtain, fully understand, and coordinate the work roofing contractor may result in removal and replacement of the penetration systems for approval within 30 days after award of Contract. Provide TAB Agency PART 2 PRODUCTS ARCHITECT OF RECORD
<br /> with the complete set of Contract Documents. Any required corrections, including at this Contractor's expense. qualifications.
<br /> all associated costs, arising from issues caused by the Contractor's failure to F. All temperature control wiring, thermostat wiring, damper interlock wiring, control B. Final Report: Indicate deficiencies in systems that would prevent proper testing, 2.01 REQUIREMENTS FOR ALL PRODUCTS OF THIS SECTION
<br /> understand and/or coordinate the work with the complete set of Contract Documents panel interlock wiring and miscellaneous low voltage wiring associated with the adjusting, and balancing of systems and equipment to achieve specified A. Surface Burning Characteristics: Flame spread/Smoke developed index of 25/50, Za ; z
<br /> are the Contractor's sole responsibility. equipment furnished or installed under this contract shall be furnished and performance. maximum, when tested in accordance with ASTM E 84, NEPA 255, or UL 723. Cc CD o
<br /> B. Work under these sections is diagrammatic unless indicated otherwise and is installed by the mechanical contractor or his sub-contractor. All wiring installed 1. Submit to the Construction Manager within two weeks after completion of B. Manufacturer: Knauf Fiber Glass; Johns Manville Corporation; Owens Corning Corp.; LL_E5
<br /> intended to convey the scope of work and indicate the general arrangement of under this contract shall be in full compliance with the National Electrical Code, testing, adjusting, and balancing. CertainTeed Corporation. cc
<br /> ductwork, piping, equipment, and accessories. Follow these drawings in laying out all State and local codes and requirements of the Electrical Specifications for Cn
<br /> 2. Provide reports in bound manuals, complete with index page and indexing tabs, 2.02 GLASS FIBER, FLEXIBLE
<br /> the work and verify spaces for the installation of these materials and equipment. this project. with cover identification at front and side. Include set of reduced drawings A. Insulation: ASTM C 553; flexible, noncombustible blanket.
<br /> Wherever a question exists as to the exact intended location of ductwork, piping, 3.02 EXAMINATION with air outlets and equipment identified to correspond with data sheets, and 1. 'K' value: 0.31 at 75 degrees F, when tested in accordance with ASTM C 518.
<br /> or equipment, obtain instructions from the Architect before proceeding with the A. Verify field measurements are as indicated on the Drawings. indicating thermostat and equipment locations. 2. Maximum Service Temperature: 450 degrees F. 4micga Pitecure
<br /> work. B. Verify a I I equipment I ocat i ons prior to rough-i n. Ma i nta i n adequate equipment 3. Inc I ude actua I i nstrument I i st, w i th manufacturer name, ser i a I number, and 3. Maximum Water Vapor Sorption: 5.0 percent by weight. 15635 Alton Parkway,Suite 100, Irvine,CA 92618
<br /> C. Notify the Architect for resolution if a discrepancy is discovered within the service clearance per manufacturer and code. date of calibration. B. Vapor Barrier Jacket: P:949.553.1117 F:949.474.7056
<br /> Contract Documents. Failure of the Contractor to notify the Architect of C. Verify routing of all ductwork and piping in field prior to fabrication or 4. Form of Test Reports: Where the TAB standard being followed recommends a 1. Kraft paper with glass fiber yarn and bonded to aluminized film.
<br /> discrepancies shall result in the resolution becoming the Contractor's installation. Verify adequate clearance with structure, light fixtures, and report format use that; otherwise, follow ASHRAE Std 111. 2. Moisture Vapor Permeability: 0.029 ng/Pa s m (0.02 perm inch), when tested
<br /> responsibility and subject to the Architect's review and possible rejection. ceiling heights. 5. Include the following on the title page of each report: in accordance with ASTM E 96/E 96M. ARCHITECT STAMP
<br /> Should the Architect reject a discrepancy resolution of which they were not D. Verify that proper fuel and power supply is available for connection. a. Name, address and telephone number of Testing, Adjusting, and Balancing 3. Secure with pressure sensitive tape. IL
<br /> C.
<br /> notified, the Contractor is fully responsible to correct the installation, 3.03 INTERFACE WITH OTHER PRODUCTS Agency. C. Vapor Barrier Tape:
<br /> including all associated costs, until approval of the installation is given by the A. Install all ductwork, pipe, equipment, and accessories to preserve fire resistance b. Project: Name; location; Engineer; Contractor, Report date. 1. kraft paper reinforced with glass fiber yarn and bonded to aluminized film, Q•PJG
<br /> Architect. rating of partitions and other elements, using materials and methods specified. 1.03 WARRANTY with pressure sensitive rubber based adhesive. ����
<br /> 1.06 EXISTING CONDITIONS 3.04 FIELD QUALITY CONTROL A. The Balancing Contractor shall be prepared to return to the site at no additional D. Outdoor Vapor Barrier Mastic: Q•�
<br /> A. Verify all existing conditions prior to beginning work. A. Provide tests as necessary to establish the adequacy, quality, safety, completed cost to re-adjust air quantities as required to provide uniform temperatures, 1. Vinyl emulsion type acrylic or mastic, compatible with insulation, black �Q'O
<br /> B. Any existing conditions indicated in the Contract Documents are based on status, and suitable operation of each system. Tests shall be conducted under the eliminate drafts and objectionable noises during the first year of occupancy, color.
<br /> information drawings provided by others and possibly limited field verification. supervision of the Architect. including one full heating and one full cooling season, after the acceptance of the E. Tie Wire: Annealed steel , 16 gage. �v�QQ`
<br /> The Contractor shall adjust for actual field conditions at no additional expense to 3.05 CLEANING AND REPAIR final balancing report. 2.03 DUCT LINER
<br /> the Owner. A. Clean fire suppression parts to remove harmful materials. A. Insulation: Incombustible glass fiber complying with ASTM C 1071; flexible Q�O�
<br /> C. The Contractor shall visit the project site, review existing conditions against the B. Clean exposed surfaces of all ductwork pipe, equipment, and accessories of all PART 2 PRODUCTS - NOT USED blanket, rigid board, and preformed round liner board; impregnated surface and 11-19-21
<br /> Contract Documents, and familiarize himself with the work prior to bidding and dirt, debris, splatter, and other deleterious materials. Follow the manufacturer's edges coated with acrylic polymer shown to be fungus and bacteria resistant by
<br /> start of the work. By signing the Contract, the Contractor acknowledges the site recommendations for cleaning as applicable. PART 3 EXECUTION testing to ASTM G 21.
<br /> visit has been completed and the existing conditions are accepted. C. Repair or replace damaged ductwork, pipe, equipment, and accessories, as directed 1. Apparent Thermal Conductivity: Maximum of 0.31 at 75 degrees F.
<br /> D. The Contractor shall notify the Architect of major discrepancies in writing so the by and to the satisfaction of the Architect, where marring or disfigurement has 3.01 GENERAL REQUIREMENTS 2. Service Temperature: Up to 250 degrees F.
<br /> appropriate modifications to the design can be made without delay to the project. occurred. All pipe, equipment, and accessories shall be new. A. Perform total system balance in accordance with one of the following: 3. Rated Velocity on Coated Air Side for Air Erosion: 5,000 fpm, minimum.
<br /> The Contractor assumes full responsibility of adjusting for discrepancies of which 3.06 PROJECT CLOSEOUT 1. AABC MN-1, AABC National Standards for Total System Balance. 4. Minimum Noise Reduction Coefficients:
<br /> the Architect is not informed. A. Project Record Documents: At project closeout, provide one printed copy and one 2. ASHRAE Std 111, Practices for Measurement, Testing, Adjusting and Balancing a. 1/2 inch Thickness: 0.30.
<br /> 1.07 SUBMITTALS electronic copy of the project record documents to the Owner. Record documents of Building Heating, Ventilation, Air-Conditioning, and Refrigeration b. 1 inch Thickness: 0.45.
<br /> A. Shop Drawings: will not be reviewed by the Engineer. Systems. C. 1-1/2 inches Thickness: 0.60.
<br /> 1. Furnish the following submittals to the Architect for review by the Engineer: B. Record Drawings: Information contained on project record drawings shall include, 3. NEBB Procedural Standards for Testing Adjusting Balancing of Environmental d. 2 inch Thickness: 0.70.
<br /> a. Provide product data and shop drawings for vibration isolation. as a minimum: Systems. B. Adhesive: Waterproof, fire-retardant type.
<br /> b. Provide balancing firm qualifications and final test report for 1. Actual locations of all equipment, ductwork, air inlets/outlets, accessories, 4. SMACNA HVAC Systems Testing, Adjusting, and Balancing. C. Liner Fasteners: Galvanized steel , self-adhesive pad or impact applied with
<br /> Testing, Adjusting, and Balancing. etc. B. Begin work after completion of systems to be tested, adjusted, or balanced and integral , or press-on head.
<br /> C. Provide product data for duct insulation. 2. Actual routing of ductwork with sizes and elevations. complete work prior to Substantial Completion of the Project.
<br /> d. Provide product data for grease duct fireproofing (if specified). 3. Actual locations of control devices including valves and volume dampers. C. Where HVAC systems and/or components interface with life safety systems, including PART 3 EXECUTION
<br /> e. Provide product data for HVAC piping insulation. C. Operation and Maintenance Data: Provide descriptive literature, maintenance and fire and smoke detection, alarm, and control , coordinate scheduling and testing and -#--a L_
<br /> f. Provide product data and shop drawings for HVAC ductwork. operation data for all hvac equipment, control systems, accessories, and materials inspection procedures with the authorities having jurisdiction. 3.01 INSTALLATION
<br /> g. Provide product data for air duct accessories. used. Include maintenance procedures, intervals, and parts list of each item D. TAB Agency Qualifications: A. Install in accordance with manufacturer's instructions and NAIMA National O 0
<br /> h. Provide product data and shop drawings for HVAC power ventilators. installed under this contract. Include all manufacturer's guarantees and 1. Company specializing in the testing, adjusting, and balancing of systems Insulation Standards. ♦-#
<br /> i . Provide product data and shop drawings for air outlets and inlets. warranties. specified in this Section with a minimum of five years' experience. B. Insulated ducts conveying air below ambient temperature: 0
<br /> j. Provide product data and shop drawings for packaged rooftop units. D. Maintenance Materials: At project closeout, furnish to the Owner the following: 2. Certified by one of the following: 1. Provide insulation with vapor barrier jackets.
<br /> 2. Submittals other than those listed above will not be reviewed and will be 1. One set of replacement filters for all hvac equipment. a. AABC, Associated Air Balance Council; upon completion submit AABC 2. Finish with tape and vapor barrier jacket. C: _ M
<br /> returned stating as such. 2. The maintenance contract for the hvac system, if applicable. National Performance Guaranty. 3. Continue insulation through walls, sleeves, hangers, and other duct r
<br /> 3. Shop drawings shall be prepared by a manufacturer's representative, and shall E. Test Reports: Submit to the Owner all testing reports. b. NEBB, National Environmental Balancing Bureau. penetrations. C CSI
<br /> contain names of the manufacturer and cut sheets of equipment to be used on
<br /> C. TABB, The Testing, Adjusting, and Balancing Bureau of National Energy 4. Insulate entire system including fittings, joints, flanges, fire dampers, E. .
<br /> �E LC}
<br /> the project. Use manufacturer's specification sheets identified by number END OF SECTION Management Institute. flexible connections, and expansion joints. LO
<br /> indicated on drawings or schedules. Indicate catalog number on the cut 3. The TAB Agency must be a completely independent, third party balancing C. Insulated ducts conveying air above ambient temperature: "CU U .M
<br /> sheets. As applicable, provide construction data, weight and dimensional contractor with no financial , common owners or other ties to the installing 1. Provide with or without standard vapor barrier jacket. W C Q
<br /> data, voltage ratings, performance data, listing data, pump curves, fan contractors. 2. Insulate fittings and joints. Where service access is required, bevel and W C: OfU
<br /> curves and sound data as part of the shop drawing submittal . SECTION 230548 - VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT E. TAB Supervisor and Technician Qualifications: Certified by same organization as seal ends of insulation. 2 (D ❑
<br /> 4. Submittals are reviewed only for general compliance with the Contract TAB agency. D. External Duct Insulation Application: Q ❑ m
<br /> Documents. Dimensions, quantities and details are not checked during PART 1 GENERAL 3.02 ADJUSTMENT TOLERANCES 1. Secure insulation with vapor barrier with wires and seal jacket joints with Z M Q C
<br /> submittal review. Review of the submittals does not relieve the Contractor A. Air Handling Systems; Air Outlets and Inlets; Hydronic Systems: Adjust to within vapor barrier adhesive or tape to match jacket. U06 F- 0
<br /> of the responsibility for providing all materials, equipment and accessories 1.01 SECTION INCLUDES plus or minus 15 percent of design. 2. Secure insulation without vapor barrier with staples, tape, or wires.
<br /> necessary for a complete and operational system meeting the requirements of A. Vibration isolators. 3.03 RECORDING AND ADJUSTING 3. Install without sag on underside of duct. Use adhesive or mechanical W W r V
<br /> . . . . . . . . . . . . . .
<br /> the project and the intent of the Contract Documents. The responsibility for B. Seismic restraints. A. Permanently mark settings of valves, dampers, and other adjustment devices allowing fasteners where necessary to prevent sagging. Lift duct off trapeze hangers O O r O
<br /> coordination of substituted materials and equipment lies solely with the C. Equipment: settings to be restored. Set and lock memory stops. and insert spacers. � O },
<br /> substituting Contractor. 1. Packaged roof top equipment B. Mark on the Drawings the locations where traverse and other critical measurements 4. Seal vapor barrier penetrations by mechanical fasteners with vapor barrier o � � co
<br /> 5. Electrical Characteristics: Verify that proper power supply is available 1.02 SUBMITTALS were taken and cross reference the location in the final report. adhesive.
<br /> prior to ordering equipment. Verify proper voltage, phase and current rating A. Product Data: Provide schedule of vibration isolator type with location and load 3.04 AIR SYSTEM PROCEDURE 5. Stop and point insulation around access doors and damper operators to allow
<br /> of power supply and inform Engineer of any deviations prior to order, on each. A. Adjust air handling and distribution systems to provide required or design supply, operation without disturbing wrapping. STORE #: 20685
<br /> connection of equipment or start-up. Responsibility for verification of return, and exhaust air quantities. E. Duct and Plenum Liner Application:
<br /> proper power supply voltage and any product returns or damage resulting from PART 2 PRODUCTS B. Make air quantity measurements in ducts by Pitot tube traverse of entire cross 1. Adhere insulation with adhesive for 90 percent coverage. PROJECT#: 59335-039
<br /> incorrect connections shall rest with this Contractor. sectional area of duct. 2. Secure insulation with mechanical liner fasteners. Refer to SMACNA HVAC Duct
<br /> B. Test Reports: Provide Testing, Adjusting, and Balancing (TAB) and Commissioning 2.01 MANUFACTURERS C. Measure air quantities at air inlets and outlets. Construction Standards - Metal and Flexible for spacing. ISSUE DATE: CH ECKSET
<br /> reports to the Architect for review by the Engineer. All other reports shall be A. Isolation Technology, Inc.; Kinetics Noise Control , Inc.; Mason Industries. D. Adjust distribution system to obtain uniform space temperatures free from 3. Seal and smooth joints. Seal and coat transverse joints.
<br /> provided to the Owner. 2.02 VIBRATION ISOLATORS objectionable drafts and noise. 4. Seal liner surface penetrations with adhesive. DESIGN MANAGER: J.RAMOS
<br /> 1.08 QUALITY ASSURANCE A. Restrained Open Spring Isolators: E. Use volume control devices to regulate air quantities only to extend that 5. Duct dimensions indicated are net inside dimensions required for air flow. PRODUCTION DESIGNER:
<br /> A. Manufacturer Qualifications: Company specializing in manufacturing the Products 1. Springs: Minimum horizontal stiffness equal to 75 percent vertical adjustments do not create objectionable air motion or sound levels. Effect volume Increase duct size to allow for insulation thickness.
<br /> CHECKED BY: GRS
<br /> specified in this section with minimum five years experience. stiffness, with working deflection between 0.3 and 0.6 of maximum deflection. control by duct internal devices such as dampers and splitters. Do not use 3.02 SCHEDULES
<br /> B. Installer Qualifications: Company specializing in performing the work of this Color code springs for load carrying capacity. diffuser, grille or register integral dampers for balancing adjustments unless the A. The Contractor may use any of the following insulating materials, at his option,
<br /> section, with minimum five years experience. 2. Spring Mounts: Provide with leveling devices, minimum 0.25 inch thick plans do not indicate duct mounted devices. provided the selected material meets with the approval of all State, local MCG PROJECT#: 21324
<br /> C. Products: neoprene sound pads, and zinc chromate plated hardware. F. Vary total system air quantities by adjustment of fan speeds. Provide drive authorities and utility company requirements. Verification of compliance of the MCG P ROJ. MANAGER: J.S PE NCER
<br /> 1. Listed and classified by Underwriters Laboratories Inc. as suitable for the 3. Sound Pads: Size for minimum deflection of 0.05 inch; meet requirements for changes required at no additional expense to the Owner. Vary branch air quantities selected insulating material and thickness with all State and local codes and MCG P ROJ. SPECIALIST:
<br /> purpose specified and indicated. neoprene pad isolators. by damper regulation. utility company requirements is the sole responsibility of the installing
<br /> D. All equipment and components shall be free of all rust/corrosion or any visible 4. Restraint: Provide heavy mounting frame and limit stops. G. Measure static air pressure conditions on air supply units, including filter and Contractor.
<br /> damage. All items not complying with this requirement shall be replaced without 5. For Exterior and Humid Areas: Hot dipped galvanized housings and neoprene coil pressure drops, and total pressure across the fan. Make allowances for 50 B. Supply air ducts in ceiling spaces: Revision Schedule
<br /> any change in the Contract amount. coated springs. percent loading of filters. 1. Flexible Glass Fiber Duct Insulation: 1-1/2 inches thick.
<br /> E. Equipment performance and accessories shall be as scheduled on the Drawings and B. Spring Hanger: H. Adjust outside air automatic dampers, outside air, return air, and exhaust dampers 2. Flexible Glass Fiber Duct Liner Insulation: 1 inches thick.
<br /> specified herein. Inclusion in both locations is not a prerequisite to inclusion 1. Springs: Minimum horizontal stiffness equal to 75 percent vertical for design conditions in all operating modes as indicated in the sequence of C. Supply, return or exhaust air ducts in crawl spaces, attics or other unconditioned Rev Date By Description
<br /> in the Contract. Equipment and accessories specified in either location shall be stiffness, with working deflection between 0.3 and 0.6 of maximum deflection. control . areas:
<br /> included in the Contract. Provide all necessary accessories and connections as Color code springs for load carrying capacity. I. Measure temperature conditions across outside air, return air, and exhaust dampers 1. Flexible Glass Fiber Duct Insulation: 3 inches thick.
<br /> required for a complete, functional system, including all required components 2. Housings: Incorporate neoprene isolation pad meeting requirements for to check leakage. D. Supply air ducts exposed in finished areas:
<br /> reasonably inferred to as necessary although such components may or may not be neoprene pad isolators or rubber hanger with threaded insert. J. Where modulating dampers are provided, take measurements and balance at extreme 1. Flexible Glass Fiber Duct Liner Insulation: 1 inches thick.
<br /> specifically indicated in the Contract Documents. 3. Misalignment: Capable of 20 degree hanger rod misalignment. conditions and at all intermediate operating conditions specified in the sequence E. Return or exhaust air ducts exposed in finished areas: None.
<br /> F. Code or utility company requirements shall supersede any conflicting requirements 4. For Exterior and Humid Areas: Hot dipped galvanized housings and neoprene of control . Balance variable volume systems at maximum air flow rate, full
<br /> of this section. coated springs. cooling, and at minimum air flow rate, full heating. END OF SECTION
<br /> 1.09 DELIVERY, STORAGE, AND HANDLING C. Neoprene Pad Isolators: 3.05 SCOPE
<br /> A. Rooftop Equipment: Protect units from physical damage by storing off site until 1. Rubber or neoprene waffle pads. A. Equipment Requiring Testing, Adjusting, and Balancing (if present on the project): SHEET TITLE:
<br /> roof mounting curbs are in place, ready for immediate installation of units. a. Hardness: 30 durometer. 1. HVAC Pumps; Boilers; All Air Handling Equipment; All Packaged Heating and/or MECHANICAL
<br /> B. Protect insulation from weather and construction traffic, dirt, water, chemical , b. Thickness: Minimum 1/2 inch. Cooling Equipment; All Coil; All Heat Exchangers; Terminal Heat Transfer SECTION 233100 - HVAC DUCTS AND CASINGS
<br /> and mechanical damage, by storing in original wrapping.
<br /> C. Maximum Loading: 50 psi . Units; Air Terminal Units; Air Inlets and Outlets
<br /> C. d. Rib Height: Maximum 0.7 times width. ED SPECIFICATIONS
<br /> Protect dampers and accessories from damage to operating linkages, blades and 3.06 MINIMUM DATA TO BE REPORTPART 1 GENERAL
<br /> finishes. 2. Configuration: S i ng I e I oyer. A. Report (as app I i cab I e to the project): SCALE:AS SHOWN
<br /> D. Provide temporary end caps and closures on piping and fittings. Maintain in place D. Rubber Mount or Hanger: Molded rubber designed for 0.4 inch deflection with 1. Summary Comments: 1.01 SECTION INCLUDES
<br /> until installation. threaded insert. a. Design versus final performance A. Metal ductwork.
<br /> E. Protect motors stored on site from weather and moisture by maintaining factory E. Glass Fiber Pads: Neoprene jacketed pre-compressed molded glass fiber. b. Notable characteristics of system B. Nonmetal ductwork. SHEET NUMBER:
<br /> M-0001
<br />
|