Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> CCUNT <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> ESCALON MINI MART 1097 YOSEMITE AVE, ESCALON December 06, 2022 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 118 CCR 2637.2(d&e), 2665(a&b) Failure to submit the"Overfill Prevention Equipment Inspection Report Form"within <br /> 30 days. <br /> OBSERVATION: Overfill Prevention Equipment testing was performed on 11/15/2021 and a test report was <br /> submitted on 2/24/2022, 3 months late. <br /> REGULATION GUIDANCE:A copy of the test report must be submitted within 30 days of the tests. <br /> CORRECTIVE ACTION: Take all necessary precautions to ensure testing and submittal of test reports are <br /> performed in a timely manner. <br /> This is a repeat violation, Class II. <br /> 308 CCR 2632(c), 2634(d), 2636(f) Failure of the leak detection equipment to have an audible and visual alarm. <br /> OBSERVATION: The 91 STP sump sensor failed to activate an audible and visual alarm when tested to ensure <br /> continuous monitoring of the tank system. <br /> REGULATION GUIDANCE:All monitoring equipment shall be maintained to activate an audible and visual alarm or <br /> stop the flow of product at the dispenser when it detects a leak. <br /> CORRECTIVE ACTION: Correct immediately by having a properly licensed,trained, and certified contractor replace <br /> the failed component with a functional component(LG 113-x listed, if applicable), and obtain a permit within one <br /> business day from the EHD, if needed. If the failed component can't be replaced immediately,there is a possibility <br /> that the 91 UST system may be red tagged to prevent fuel inputs. <br /> This is a repeat violation, Class Il. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 1/5/2023. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> ($156). To schedule an appointment, please call (209)468-3420. <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: December 06, 2022 Inspector: Inspector Phone: <br /> Printed Name and Title: KRISTINA SAETERN, EH Specialist (209)616-3045 <br /> E-mailed to Baban Kaur, Owner's daughter <br /> FA0000279 PR0231497 SCO01 12/06/2022 <br /> EHD 23-01 Rev.12/06/2021 Page 5 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />