Laserfiche WebLink
imGFrrtER-RYAN INC. FORM 1 GR Jab # 22204981 <br /> SUMMARY OF SOURCE TEST DATA <br /> SOURCE INFORMATION FACILITY PARAMETERS <br /> GDF Name and Address GDF Representative and Title PHASE II SYSTEM TYPE <br /> Area 6080 Vince Caluag (Check One) <br /> 85 E. Louise Ave. <br /> Lathrop, CA 95330 GDF Phone No. Balance <br /> 916-858-9907 Hirt <br /> Permit Conditions Source,GOF Vapor Recovery system Red Jacket <br /> CCVp Hasstech <br /> Healy <br /> GOF# Other <br /> A/C 0 Manifolded7 Yes No <br /> Operating Parameters <br /> Number of Nozzles Served by Tank#1 8 Number of Nozzles Served by Tank#3 <br /> Number of Nozzles Served by Tank#2 a Number of Nozzles Served by Tank#4 <br /> Applicable Regulations: VR-203-1 and VR-204-1 VN Recommended <br /> Source Test Results and Comments <br /> Tank#: 1 2 3 4 <br /> 1. Product Grade <br /> 87 91 <br /> 2. Actual Tank Capacity,gallons 19951 11873 <br /> 3. Gasoline Volume Total 9863 6031 <br /> 4. Ullage,gallons (#2-#3) 15930 10088 5842 <br /> 5. Initial Pressure, inches H2O 2.00 <br /> 6. Pressure After 1 Minute, inches H2O 2.00 <br /> 7. Pressure After 2 Minutes, inches H2O 1.99 <br /> 8. Pressure After 3 Minutes, inches H2O 1.99 <br /> 9. Pressure After 4 Minutes, inches H2O 1.98 <br /> 10. Final Pressure After 5 Minutes,inches H2O 1.98 <br /> 11. Allowable Final Pressure 1.90 <br /> Test Conducted by: Test Company: Date of Test: <br /> Darnell smith Gettler-Ryan Inc. 10/12/2022 <br /> California Air Resource Board March 17, 1.999 <br /> TP-201.3, Page 14 <br />