Laserfiche WebLink
_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2353595 Date: 2/16/2022 <br /> Site Name/ID. CHEVRON#208117/208117 <br /> Address: 755 S.TRACY BLVD <br /> City: TRACY State: CA Zip: 95376 <br /> Tank ID T2 T 1 <br /> Product REGULAR PREMIUM <br /> Product Line 1 1 <br /> Tested From 9 9 <br /> Existing/New Existing Existing <br /> Mechanical/Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD <br /> Serial No. 235887 015583 <br /> Pump Operating Pressure(psi) 40.00 40.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 <br /> Holding PSI <br /> NIA for Electronic Lo's <br /> Resiliency(ml) <br /> NIA for Electronic Lo's <br /> Metering PSI <br /> NIA for Electronic Lo's <br /> Opening Time(sec) <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus S�/aldivar Certification#: 115237 <br /> Technician Signature: /-1 1�� Expire Date: 11/7/2024 <br /> Environmental Compliance for Petroleum Systems <br /> @2022 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />