Laserfiche WebLink
_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2356744 Date: 5/12/2022 <br /> Site Name/ID: 7-ELEVEN 41342/41342 <br /> Address: 1233 E Dr. Martin Luther King Jr Blvd <br /> City: Stockton State: CA Zip: 95205 <br /> Tank ID T-1 RUL T-2 PUL Diesel <br /> Product REGULAR PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 11 11 3 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No. unreadable unreadable 21071525 <br /> Pump Operating Pressure(psi) 30.00 32.00 32.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 30.00 30.00 32.00 <br /> NIA for Electronic Lo's <br /> Resiliency(ml) 250.00 800.00 430.00 <br /> NIA for Electronic Lo's <br /> Metering PSI 17 18 20 <br /> NIA for Electronic Lo's <br /> Opening Time(sec) 4 10 4 <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jarrod Cooke Certification#: 2081 <br /> Technician Signature: Expire Date: 4/27/2023 <br /> Environmental Compliance for Petroleum Systems <br /> @2022 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />