Laserfiche WebLink
Underground Storage Tank <br /> Overfill Prevention Equipment Inspection Report <br /> 6. OVERFILL PREVENTION EQUIPMENT DETAILS <br /> Tank ID (one OPE per column) T1 87 T3 e7 <br /> Are both vent and tank riser piping ✓ Yes /J Yes Yes Yes <br /> secondarily contained? <br /> lNo No No No <br /> OPE Model BBw Restricts <br /> What is the OPE response when activated? ✓ Shut off hut off Shut off Shut off <br /> (Check all that apply.) Flow Flow Flow Flow <br /> estricts L�estricts Restricts <br /> Flow Flow Flow Flow <br /> Audible Audible Audible Audible <br /> Alarm Alarm Alarm Alarm <br /> Visual Visual Visual Visual <br /> Alarm Alarm Alarm Alarm <br /> Are flow restrictors installed on vent piping Yes'` Yes* Yes* Yes* <br /> that may interfere with the OPE operation? No No _ No _ No <br /> At what level in the tank is the OPE set to <br /> activate? Inches from bottom of tank 76N 75 5 e• <br /> What is the percent capacity of the tank at 91.02% 90.65% <br /> which the OPE activates? <br /> Is the OPE in proper operating condition to Yes Zj Yes Yes Yes <br /> respond when the stored substance No No No No <br /> reaches the designated regulatory level? <br /> 7. SUMMARY OF TESTING RESULTS <br /> OPE Inspection Results v/ Pass �/ Pass Pass Pass <br /> Fail Fail HFail Fail <br /> $. COMMENTS <br /> Describe all results marked "Fail"and each proposed remedy. <br /> * Mark here if: <br /> Flow restrictors interfere with overfill prevention and equipment repairs required. <br /> Additional copies of this page may be attached. <br /> Attach tank chart(s), measurements, calculations, and In-Tank Setup report(s) <br /> Page 2 of 2 <br />