Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer D Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum 0 Hydrostatic <br /> Test Equipment Used: Incon Tester <br /> Sump/UDC ID UDC 1/2 UDC 3/4 87 STP <br /> Sump Manufacturer oPw oPw Fiberglass <br /> Sump Depth (inches) 31" 31" 68" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 18" 18" 26" <br /> (inches) <br /> Test Start Time 8:54 am 8:29 am 11:16 am <br /> Initial Reading 4.7306 5.1204 5.7781 <br /> Test End Time 9:09 am 8:45 am 11:31 am <br /> Final Reading 4.7306 5.1199 5.7785 <br /> Change in Reading 0.0000 0.0005 0.0004 <br /> Pass/Fail Criteria 0.002 0.002 0.002 <br /> Tightness Test Results p Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />