Laserfiche WebLink
Fire alarm? <br />Does the FACP display read "NORMAL"? Verify annual service through service records kept in the document box on the FACP. Is signage in place identifying <br />the FACP location? <br />Status: Approved <br />Notes: Inside of pump house. <br />Fire Sprinklers? <br />Confirm fire sprinklers have current annual and 5 year certification tags on each riser. <br />Status: Approved <br />Notes: Fire sprinklers ok <br />EXTINGUISHERS <br />Additional fire extinguishers required: Class 2A:10-BC rated fire extinguisher(s) shall be provided for each 3,000 square feet of <br />light hazard fuel load or for each 1,500 square feet of ordinary hazard fuel load. Travel distance shall not exceed 75 feet. 40- <br />BC minimum rating for HazMat areas. <br />CFC 906 <br />Status: Required <br />Notes: Provide fire extinguisher with a 40-BC rating. <br />Printed on 10/14/21 at 09:01:02 Page 4 of 6