Laserfiche WebLink
o All double -walled piping shall have continuous monitoring of the secondary <br /> containment using continuous vacuum , pressure , or hydrostatic monitoring of the <br /> double -wall annular space as follows : <br /> Product conveying piping ( continuous vacuum or pressure ) . <br /> Vent piping ; (continuous vacuum , pressure , or hydrostatic ) ; Vapor <br /> recovery piping ; (continuous vacuum , pressure , or hydrostatic) . o Any leak <br /> shall initiate an audible and visual alarm that can immediately be detected by <br /> the UST operator . <br /> o For pressurized piping , the monitoring system shall shut down the turbine pump if a <br /> leak is detected or if the monitoring system fails . <br /> • UST Sump Monitoring for Piping , Riser, and Man -ways — Provide documentation that <br /> the UST sumps will be continuously monitored by one of the following methods : <br /> o For single -walled sumps with single walled piping inside sumps ( e . g . , flex piping , fill <br /> piping , all riser piping , etc . ) . The interior sump space shall be continuously <br /> monitored for pipe joint leaks by using continuous vacuum or pressure . <br /> o For single -walled sumps with continuously monitored double -walled piping inside <br /> sumps using continuous vacuum , pressure , or hydrostatic monitoring of the double - <br /> walled piping (e . g . , NO single -walled flex connections , fill piping , or riser piping ) . o <br /> for double -walled sumps continuously monitored by using continuous vacuum , <br /> pressure , or hydrostatic monitoring of the double -wall , the inside sump piping can <br /> be single walled ( e . g . , flex piping ; fill piping , all riser piping , etc . ) . The internal sump <br /> space must have continuous liquid leak sensors to detect any piping leaks . <br /> o Sumps must be installed on all UST riser piping and manways (e . g . , fill pipes , tank <br /> openings , automatic tank gauging , etc . ) . <br /> o A leak shall initiate an audible and visual alarm that can immediately be detected by <br /> the UST operator. <br /> o For pressurized piping , the monitoring system shall shut down the turbine pump if a <br /> leak is detected or if the monitoring systems fail . <br /> o All sumps must have water-tight lids . <br /> o Double -walled sumps must be installed with the secondary containment portion as <br /> close as possible to the underside of the concrete pad (or higher) , so it reduces a <br /> potential pathway for chemicals to enter the backfill . <br /> • UST Under Dispenser Containment ( UDC ) Monitoring — Provide documentation that the <br /> UDC will be continuously monitored by one of the following methods : <br /> ( 888 ) 239 -9988 SAN DIEGO LOS ANGELES PHOENIX westernpump . com <br /> Page 8 of 11 <br />