Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br /> been addressed for Harney Lane 76 as of October 18 , 2022 . <br /> Open violations from July 28, 2022 inspection <br /> Violation #307 - Failure to keep water out of the secondary containment system ( post-Jul 2003 ) . <br /> OBSERVATION Brine was found in the following locations : <br /> -87 submersible turbine pump (STP) and fill sumps . <br /> -91 fill sump. <br /> REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any water intrusion into the <br /> system by precipitation , infiltration , or surface runoff. <br /> CORRECTIVE ACTION : Per the service technician , approximately 1 /4 of a gallon of liquid was removed from the 87 <br /> and 91 sumps and returned the sensor to its proper location . Immediately contact a properly licensed , trained , and <br /> certified contractor to address the water intrusion into the 87 and 91 fill and STP sumps under permit and inspection <br /> of the EHD . <br /> --------------------------------------------------- <br /> OBSERVATION Brine was found in the Diesel submersible turbine pump (STP ) sump and the fill sump . <br /> REGULATION GUIDANCE: Secondary containment shall be constructed to prevent any water intrusion into the <br /> system by precipitation , infiltration , or surface runoff. <br /> CORRECTIVE ACTION: Immediately remove this liquid , make a hazardous waste determination per Title 22 <br /> hazardous waste regulations , and manage accordingly. Immediately contact a properly licensed , trained , and <br /> certified contractor to address the water intrusion into the Diesel STP and fill sumps under permit and inspection of <br /> the EHD , if needed . <br /> ❑ This violation was corrected ❑ This violation will be corrected by (date) : <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation : <br /> Page 7 of 7 <br />