Laserfiche WebLink
Tank Assessment Page Tank Name/marking: USED MOTOR OIL <br /> Tank age: 20 YEARS <br /> Remaining service Iife:20 YEARS <br /> Tank Construction: <br /> Shape: RETANGULAR <br /> Orientation: HORIZONTAL <br /> Location (above/below ground): ABOVE GROUND <br /> Material of construction: STEEL <br /> Thickness and method used to determine: 10 GUAGE STEEL (mfg specs) <br /> Lining material & thickness (if applicable): N/A <br /> Corrosion Protection equipment: TWO PART EPDXY COATING <br /> Structural support: THREE INCH STEEL CHANNELS <br /> Other identifying features: BLACK IN COLOR <br /> Piping and ancillary equipment (pumps) <br /> Piping Material of Construction: STEEL BRADIED HOSE <br /> Piping Diameter: 1" <br /> Pump location(s): ON TOP OF TANK <br /> Pump type(s)/capacities: PNUEMATIC 40GPM <br /> Material Storage: <br /> Material and characteristics: USED OIL <br /> Specific Gravity: .8 <br /> Operating Capacity: 1000 GALLONS <br /> Chemical compatibility findings: The materials identified above are compatible <br /> for contact with or proximity to the equipment, tank or tank system in this <br /> assessment. Initials: <br /> Ui <br /> Visual Inspection: <br /> Tank parameters at time of inspection (empty, etc.): '/4 FULL <br /> Acute visual evidence of leaks NONE: <br /> Condition of interior surface:000D <br /> Condition of exterior surface-GOOD <br /> Condition of nozzles, flanges, fittings at tank: GOOD <br /> Condition of piping-GOOD <br /> Visual Inspection findings: A visual inspection of the tank and its affiliated <br /> pumps, piping and ancillary equipment did not reveal signs of leaks, corrosion, <br /> weld cracks or breaks, or scrapes in protective coating which may cause a <br /> release from the tank system. A description of all discrepancies noted during the <br /> visual inspection is included with this report. Initials: : -- <br /> Ili I <br /> North County Recycling & Sanitary Landfill Used Motor Oil <br />